NEC Code Questions Practice Test-10
Q1 / 10
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC Code Questions Practice Test-10 — Question List

Question 1: What is the required size of a neutral conductor for a dwelling unit with a calculated load of 220 A. The unbalanced load is 120 A and service disconnect rating is 250A.

  • 1 AWG
  • 2 AWG
  • 3 AWG
  • 4 AWG

NEC Reference: NEC 310.15(B)(16)

Question 2: If a service is fed by three parallel sets of 400 kcmil conductors, what is the required conductor size for GEC?

  • 3/0 AWG
  • 2/0 AWG
  • 2 AWG
  • 4 AWG

NEC Reference: NEC 250.166

Question 3: A 400 breaker protects a set of 450 kcmil feeder conductors. A feeder fed from 450 kcmil feeder that supply disconnects with 25 A over current device. What is the minimum size conductor for these tap?

  • 8 AWG
  • 6 AWG
  • 4 AWG
  • 16 AWG

NEC Reference: NEC 310.15(B)(16)

Question 4: What size service entrance conductors are required for 250 A continuous three phase load if the terminals are at ambient temperature of 70 C?

  • 3/0 AWG
  • 250 kcmil
  • 400 kcmil
  • 2/0 AWG

NEC Reference: NEC 312.5

Question 5: Under which of the following condition the on-site generator is not considered as separately derived system?

  • When the generator does not have neutral conductor
  • When the generator is placed near the feeder service conductor panel board
  • Generator having transfer witch that switches the neutral conductor also
  • When generator neutral conductor is solidly interconnected service supply system neutral conductor

NEC Reference: NEC 250.30

Question 6: When the circuits are protected by a over current device rating of 1000 A, what size bonding jumper is required for each metal raceway?

  • 1/0 AWG
  • 2/0 AWG
  • 3/0 AWG
  • 4 AWG

NEC Reference: NEC 250.122

Question 7: When five conductors each with an ampacity of 25 A bundled through NM cable, what is the adjusted ampacity of each cable.

  • 25 amperes
  • 20 amperes
  • 30 amperes
  • 22.5 amperes

NEC Reference: NEC 310.15(B)(3)(a)

Question 8: A 40 KVA , 480 V three phase transformer has a primary over current protection device is rated at 75 A. What is the size of primary conductor that can be used?

  • 2 AWG
  • 4 AWG
  • 3 AWG
  • 1 AWG

NEC Reference: NEC 310.15(B)(16)

Question 9: How many number of 500 kcmil THWN conductors that can be installed in a 4 in. * 4 in. wireway?

  • 4 conductors
  • 5 conductors
  • 6 conductors
  • 7 conductors

NEC Reference: NEC 376.22(A)

Question 10: What size service entrance conductors are required for 250 A continuous three phase load if the terminals are at ambient temperature of 70 C?

  • 3/0 AWG
  • 250 kcmil
  • 400 kcmil
  • 2/0 AWG

NEC Reference: NEC 312.5