Conduit Fill Calculator

Check whether your conductor combination fits within NEC raceway fill limits per Chapter 9, Table 1: one conductor up to 53%, two conductors up to 31%, three or more up to 40%. Pick the raceway type and trade size, then add conductors. The calculator sums conductor areas from Chapter 9 Table 5 and compares against the raceway internal area from Table 4.

Conductor area
0.0399 sq in
3 conductors
Allowed at 40%
0.3456 sq in
Raceway internal: 0.8640 sq in
Fill: 4.62% of internal area
✓ PASS — within NEC fill limits

NEC fill limits (Chapter 9, Table 1)

  • 1 conductor: 53% maximum fill
  • 2 conductors: 31% maximum fill
  • 3 or more conductors: 40% maximum fill

For lead-sheathed cables and certain other special conditions, different fill limits apply — see Chapter 9 Notes.