Box Fill Calculator

Calculate the required cubic-inch volume for a junction or device box per NEC 314.16(B). Enter the conductor counts, device yokes, clamps, support fittings, and grounding conductors — the calculator sums the volume allowances and compares the total to your box.

Each conductor counts as 1×. Conductors that pass through unbroken count once. (314.16(B)(1))

Each yoke counts as 2× the largest conductor. (314.16(B)(4))

Each fitting (hickey, fixture stud) = 1×. (314.16(B)(3))

Each additional EGC set = 0.25× of the largest conductor.

Required
20.25 in³
Available
21.00 in³
Headroom
0.75 in³
✓ Box volume is sufficient — install meets NEC 314.16.
Show calculation breakdown
  • 6 × 12 AWG insulated conductors: 13.50 in³
  • 1 × device yoke (2× 12 AWG each): 4.50 in³
  • Equipment grounding conductor(s) (1× 12 AWG total): 2.25 in³
  • Total required: 20.25 in³

How the counts work (314.16(B))

  • (B)(1) Conductor fill — each insulated conductor entering, leaving, or terminating in the box counts as based on its size.
  • (B)(2) Clamp fill — one or more cable clamps inside the box = the largest conductor entering.
  • (B)(3) Support fittings — each fixture stud or hickey = the largest conductor.
  • (B)(4) Device yoke — each yoke or strap (with a switch, receptacle, etc.) = the largest conductor connected to it.
  • (B)(5) Equipment grounding conductors — all of them together = ; an additional set of isolated/equipment grounds adds 0.25×.
Required (in³) = Σ (count · volume_per_conductor)
volume_per_conductor — Table 314.16(B)

Test your knowledge

Educational tool only. Verify against the current NEC. Not a substitute for a licensed engineer.