Michigan Journeyman Electrician Practice Test - Full-Length Test 1

A full-length, 80-question practice exam covering all 8 core NEC topic areas, weighted the same way the real exam is. Modeled on Michigan's real licensing exam format.

See Michigan electrician licensing requirements, fees & exam format

FREE FULL-LENGTH EXAM
80
Questions
240 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

About This Exam

80 questions, 240 min, 70% to pass — sized and paced like the Michigan licensing exam. Finish it to see your score and your 3 weakest topics, free.

Open book: the real Michigan exam lets you use the NEC. Keep your code book next to you and practise looking things up.

About the Michigan electrician exam


Full-Length Pro · Michigan
  • 15 Michigan exams: 1 free + 14 Pro
  • Full topic report on every attempt
  • Answer review with explanations + NEC references
  • Unlimited retakes

$19 once for Michigan only · pay once, keep forever

Unlock 14 more Michigan exams — $19
TOPICS COVERED
Motor Circuits Wiring Methods and Materials Wiring and Protection Load Calculations General Requirements Equipment for General Use Special Equipment Special Occupancies
How It Works Watch videoHow It Works

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 240 min for 80 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
See where you stand
After submitting you'll see your score, pass/fail and your 3 weakest topics. The full topic report and answer review with explanations are part of Full-Length Pro.

Frequently Asked Questions

Yes. Test 1 for every state is free: you get your score, pass/fail and your 3 weakest topics. The other 14 Michigan exams, the full topic report and the answer review are part of Full-Length Pro ($19 once for Michigan).

80 questions in 240 minutes, sized and paced like the Michigan journeyman exam.

This exam uses a 70% pass mark. Check your state licensing board for the current official passing score.

It is written to the 2023 NEC. Confirm with your state licensing board which edition is adopted for your exam date.

No. Pro is bought per state and covers Michigan only. If you change states, you can unlock that state separately.

How to Use This Practice Test

This Michigan Journeyman Electrician Practice Test - Full-Length Test 1 has 80 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: This is an open-book exam — tab your NEC index and Articles 210, 250, and 430 before you start.

  • Topics covered: Branch circuits, grounding, wiring methods, load calculations, and motors.
  • Passing score: 70–75% (most states). Aim for 80% on practice tests so the real exam feels easy.
  • Questions: 80 multiple-choice, one correct answer each
JOURNEYMAN · NEC 2023
Michigan Journeyman Electrician Practice Test - Full-Length Test 1
Q1 / 80
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
You passed a full-length exam! Post it on LinkedIn — foremen and recruiters notice.

Michigan Journeyman Electrician Practice Test - Full-Length Test 1 — Question List

Question 1: A feeder serves two motors. The 50HP motor has a 100A branch circuit breaker and the 25HP motor has a 60A branch circuit breaker. The 25HP motor FLA is 34A. What is the maximum feeder overcurrent device size?

  • 100A — match the largest branch circuit breaker
  • 125A — largest breaker plus other motor FLA, capped below 134A
  • 150A — largest breaker plus other motor FLA rounded up
  • 160A — sum of both branch circuit breakers

NEC Reference: NEC 430.62(A)

Question 2: 2/0 THHN copper has an ampacity of 195 A (90°C column). What is its maximum allowable ampacity in a conduit with 5 other current-carrying conductors?

  • 156 amperes
  • 136 amperes
  • 195 amperes
  • 185 amperes

NEC Reference: NEC Table 310.15(C)(1)

Question 3: A dwelling unit has a floor area of 2,000 sq ft. What is the minimum number of 120-volt, 2-wire branch circuits required for the general lighting load?

  • Four 15 amp 2-wire circuit
  • Four 20 amp 2-wire circuit
  • Three 15 amp 2-wire
  • Two 20 amp 2-wire circuit

NEC Reference: NEC 210.11(A), 220.41

Question 4: The commercial panel schedule shows a 400A, 120/208V, 3-phase panel with a mix of continuous and non-continuous loads. The total continuous load on the panel is 240A (3-phase). What is the minimum OCPD rating for the panel feeder breaker?

  • 240 A (match the total continuous load)
  • 300 A (125% of the continuous load)
  • 320 A (133% of the continuous load)
  • 400 A (always use the full panel rating)

NEC Reference: NEC 215.3

Question 5: When counting equipment grounding conductors (EGCs) in a box fill calculation, how many conductor volumes do all the EGCs combined count for?

  • Zero — equipment grounding conductors are always ignored in box fill
  • One conductor volume for all EGCs combined
  • One conductor volume per EGC
  • Two conductor volumes for all EGCs combined

NEC Reference: NEC 314.16(B)(5)

Question 6: A single rod, pipe or plate electrode that does not need a supplemental electrode must have a resistance to earth of not more than how many ohms?

  • 25
  • 30
  • 20
  • 50

NEC Reference: NEC 250.53(A)(2)

Question 7: A 480V service has 25,000A available SCC. The minimum AIC rating of OCPDs at the service must be:

  • 10,000A AIC
  • 14,000A AIC
  • 25,000A AIC or higher
  • No AIC rating required for service equipment

NEC Reference: NEC 110.9

Question 8: Service conductors supplying the entire load of one dwelling unit may have an ampacity of not less than what percent of the service rating?

  • 83
  • 75
  • 95
  • 80

NEC Reference: NEC 310.12

Question 9: A single-phase motor has a full-load current of 50 A. What is the minimum branch-circuit conductor ampacity?

  • 62.5 amperes
  • 75 amperes
  • 57.5 amperes
  • 50 amperes

NEC Reference: NEC 430.22

Question 10: In a remote subpanel (not the service), how must the neutral bus and the equipment grounding bus be connected?

  • They must be bonded together, same as the main service panel
  • They must be kept on separate buses and not connected together
  • Only connected together if the subpanel is in the same building
  • No grounding bus is needed in a subpanel

NEC Reference: NEC 250.142(B)

Question 11: What is the minimum fixture wire size that shall be permitted?

  • 12 AWG
  • 14 AWG
  • 16 AWG
  • 18 AWG

NEC Reference: NEC 402.6

Question 12: A branch circuit overcurrent device protecting a continuous load (a load that runs for 3 hours or more) must be rated at least how much compared to the load current?

  • 100% of the continuous load
  • 115% of the continuous load
  • 125% of the continuous load
  • 150% of the continuous load

NEC Reference: NEC 210.20(A)

Question 13: The pool diagram shows a wet-niche luminaire installed in the pool wall 18 inches below the waterline. What is the maximum voltage allowed between conductors for a wet-niche pool luminaire?

  • 120V
  • 150V
  • 240V
  • No limit — the fixture listing determines the voltage

NEC Reference: NEC 680.23(A)(4)

Question 14: A non-dwelling occupancy has a receptacle load of 15 kVA. What demand factor applies to the portion above 10 kVA?

  • 50 %
  • 75 %
  • 90 %
  • 82 %

NEC Reference: NEC 220.44

Question 15: An 80,000 sq ft hospital: after the demand factors are applied, what is the general lighting demand load?

  • 35,600 VA
  • 128,000 VA
  • 42,000 VA
  • 51,200 VA

NEC Reference: NEC Table 220.42(A), Table 220.45

Question 16: For a 200A, 120/240V service with 3/0 AWG copper service conductors, what is the minimum size copper grounding electrode conductor (GEC)?

  • 6 AWG copper
  • 4 AWG copper
  • 2 AWG copper
  • 1/0 AWG copper

NEC Reference: NEC Table 250.66

Question 17: A motor-generator arc welder has a primary current rating of 30 A and a 30% duty cycle. What is the minimum size copper branch-circuit conductor (60°C)?

  • 12 AWG
  • 10 AWG
  • 14 AWG
  • 8 AWG

NEC Reference: NEC 630.11(A)

Question 18: What is the minimum clearance of service-drop conductors over residential property where the voltage exceeds 300 volts to ground?

  • 10 feet
  • 15 feet
  • 8 feet
  • 12 feet

NEC Reference: NEC 230.24(B)(3)

Question 19: A 2,400 sq ft single-family dwelling has the following: range 12 kW, dryer 5 kW, water heater 4.5 kW, dishwasher 1.2 kW, disposal 0.8 kW, A/C 6 kW (240V), heat 7 kW. Using the optional method (220.82), the first 10 kVA at:

  • 50%
  • 75%
  • 100%
  • 125%

NEC Reference: NEC 220.82(B)(1)

Question 20: A 5 HP, 230-volt single-phase motor has a full-load current of 32 A. What minimum THWN copper conductor size is required for the branch circuit?

  • No 8 THWN
  • No 6 THWN
  • No 10 THWN
  • No 12 THWN

NEC Reference: NEC 430.22

Question 21: What is the smallest copper underground service conductor permitted to supply limited loads of a single branch circuit?

  • 12 AWG
  • 8 AWG
  • 6 AWG
  • 10 AWG

NEC Reference: NEC 230.31

Question 22: Signs and outline lighting must be at least how many feet above areas accessible to vehicles, unless protected from physical damage?

  • 14
  • 12
  • 8
  • 15

NEC Reference: NEC 600.9

Question 23: A 1,600 sq ft dwelling unit has 16 receptacles and 15 luminaires rated 100 W each. What is the general lighting load of the dwelling unit?

  • 4,800 VA
  • 1,600 VA
  • 3,200 VA
  • 6,400 VA

NEC Reference: NEC 220.41

Question 24: For a single-family dwelling unit, what is the minimum allowable rating of 3-wire service-entrance conductors?

  • 100 amperes
  • 150 amperes
  • 200 amperes
  • 180 amperes

NEC Reference: NEC 230.42(B)

Question 25: What is the minimum load required for the exterior sign or outline lighting outlet of a commercial occupancy?

  • 1,200 VA
  • 1,800 VA
  • 1,500 VA
  • 2,100 VA

NEC Reference: NEC 220.14(F)

Question 26: Resistance-type heating elements in electric space-heating equipment must be protected at not more than:

  • 60 amperes
  • 40 amperes
  • 70 amperes
  • 20 amperes

NEC Reference: NEC 424.22(B)

Question 27: A generator rated 65 volts or less is driven by a single motor. It is considered protected by the motor's overcurrent device if that device opens when the generator delivers not more than what percent of its full-load rated current?

  • 125
  • 150
  • 115
  • 170

NEC Reference: NEC 445.12(B)

Question 28: On a panelboard or switchboard supplied by a 3-phase, 4-wire delta system with a high leg, the high-leg conductor must be connected to which phase?

  • A, or First
  • B, or Center Phase
  • C or Third phase
  • Any Phase

NEC Reference: NEC 408.3(E)(1)

Question 29: Type AC cable is permitted to be installed in which locations?

  • Exposed work only
  • Concealed work only
  • Damp and wet locations
  • Both concealed and exposed work

NEC Reference: NEC 320.10

Question 30: A building has five household electric clothes dryers rated 5 kW each. What is the calculated dryer demand load?

  • 21,250 VA
  • 25,000 VA
  • 5,000 VA
  • 18,750 VA

NEC Reference: NEC 220.54

Question 31: What is the smallest fixture wire size permitted?

  • 18 AWG
  • 12 AWG
  • 14 AWG
  • 20 AWG

NEC Reference: NEC 402.6

Question 32: In an electrical system at what point branch circuit overcurrent protection device should be located?

  • At the equipment ground location
  • At the end of branch circuit
  • At the panelboard where they receive power supply
  • At the power outlet where power is consumed

NEC Reference: NEC 240.21

Question 33: The equipotential bonding grid for a permanently installed swimming pool must use a solid copper conductor no smaller than:

  • 12 AWG stranded copper
  • 10 AWG solid copper
  • 8 AWG solid copper
  • 6 AWG stranded aluminum

NEC Reference: NEC 680.26(B)(2)

Question 34: Three motors share a feeder at 460V, 3-phase — 20HP (27A FLA), 15HP (21A FLA), and 10HP (14A FLA). What is the minimum ampacity for the feeder conductors?

  • 62 A (sum of all three FLAs)
  • 69 A (125% of largest plus the rest)
  • 78 A (125% of the total)
  • 88 A (125% of each motor added)

NEC Reference: NEC 430.24

Question 35: For a service or feeder calculation, how is a laundry branch circuit load (one 20A circuit) included in the calculation?

  • 2,400 VA (20 A × 120 V)
  • 1,500 VA per laundry circuit
  • 1,000 VA flat rate per circuit
  • The actual appliance nameplate wattage only

NEC Reference: NEC 220.52(B)

Question 36: You install 1/0 AWG THHN conductors (90°C insulation, 170A per Table 310.16). The terminations on the panel and equipment are marked "75°C." Which ampacity column from Table 310.16 must you use?

  • The 90°C column — the wire is rated 90°C so that is the limiting factor
  • The 75°C column — the terminal rating limits you to 75°C ampacity
  • The 60°C column — always use the most conservative value
  • Either column — the higher of the two values governs

NEC Reference: NEC 110.14(C)(1)

Question 37: Type UF cable installed as direct burial in a general outdoor location (not under a driveway or building) must have a minimum cover depth of:

  • 12 inches
  • 18 inches
  • 24 inches
  • 30 inches

NEC Reference: NEC Table 300.5

Question 38: What size service conductors are required for a dwelling load with a calculated load is 190 A. The service disconnect breaker is rated at 200 A?

  • 1/0 AWG
  • 2/0 AWG
  • 3/0 AWG
  • 4/0 AWG

NEC Reference: NEC 310.12

Question 39: In a box fill calculation, a single-pole switch or duplex receptacle counts for how many conductor volumes?

  • Zero — devices do not count toward box fill
  • One conductor volume
  • Two conductor volumes (based on the largest conductor attached)
  • Four conductor volumes

NEC Reference: NEC 314.16(B)(4)

Question 40: A series-rated system uses a combination of OCPDs where a downstream breaker with a lower AIC rating is "backed up" by an upstream higher-rated breaker. What is required for this system to be code-compliant?

  • The downstream breaker must be at least 10,000A AIC
  • The combination of upstream and downstream OCPDs must be tested and listed together
  • Series-rated systems are never allowed under the NEC
  • Any combination is acceptable as long as the upstream device is 200% of the downstream

NEC Reference: NEC 240.86

Question 41: The NEC defines a continuous load as a load that is expected to continue without interruption for at least:

  • 1 hour
  • 2 hours
  • 3 hours
  • 8 hours

NEC Reference: NEC Article 100 (Definitions)

Question 42: An industrial heating appliance on a 40 A branch circuit is supplied by a tap conductor. What is the minimum tap conductor ampacity?

  • 20 amperes
  • 10 amperes
  • 30 amperes
  • 25 amperes

NEC Reference: NEC 210.19(A)(4)

Question 43: A 30-ampere branch circuit with heavy-duty lampholders may supply fixed lighting units in:

  • Single family dwelling unit
  • Multi family dwelling unit
  • Any occupancy
  • Any occupancy other than dwelling unit

NEC Reference: NEC 210.23(B)

Question 44: An intersystem bonding termination (IBT) is required at each building or structure served. What is its purpose?

  • To provide a ground fault path for the service entrance
  • To give communications systems a bonding point to the building grounding electrode system
  • To replace the need for ground rods at the service
  • To connect AFCI and GFCI devices to the same ground bus

NEC Reference: NEC 250.94

Question 45: Working space depth in front of a 480Y/277V switchboard with exposed live parts on both sides of the working space is (Condition 3, Table 110.26(A)(1)):

  • 3 ft
  • 3.5 ft
  • 4 ft
  • 6 ft

NEC Reference: NEC Table 110.26(A)(1)

Question 46: When sizing conductors for an air conditioning condensing unit, which current value do you use?

  • The FLA value from Table 430.250 based on horsepower
  • The rated-load current or branch-circuit selection current from the nameplate
  • The locked-rotor current divided by 6
  • The compressor horsepower × 1.5

NEC Reference: NEC 440.6

Question 47: All conductors of a circuit must be installed in the same raceway, cable, trench, cord or cable tray, except as permitted.

  • True
  • False

NEC Reference: NEC 300.3(B)

Question 48: What demand factor applies to six household electric clothes dryers?

  • 80%
  • 75%
  • 70%
  • 78%

NEC Reference: NEC Table 220.54

Question 49: What is the minimum size of lighting track conductors?

  • 12 AWG
  • 14 AWG
  • 16 AWG
  • 10 AWG

NEC Reference: NEC 410.155(B)

Question 50: The voltage at the supply end of a feeder is 240 V. With the recommended maximum 3% feeder voltage drop, what is the minimum voltage at the load end of the feeder?

  • 232.8 volts
  • 240 volts
  • 235 volts
  • 228 volts

NEC Reference: NEC 215.2(A)(4)

Question 51: The branch-circuit short-circuit and ground-fault protective device for a single motor-compressor must in no case exceed what percent of its rated-load current?

  • 175 %
  • 225 %
  • 220 %
  • 150 %

NEC Reference: NEC 440.22(A)

Question 52: Type NM cable (Romex) must be supported at maximum intervals of how many feet, and within how many inches of every box or cabinet?

  • Every 6 feet, within 6 inches of boxes
  • Every 4½ feet, within 12 inches of boxes
  • Every 10 feet, within 3 feet of boxes
  • Every 8 feet, within 24 inches of boxes

NEC Reference: NEC 334.30(A)

Question 53: Which of the following color is used to identify intrinsically safe conductors?

  • Green
  • Yellow
  • Red
  • Light blue

NEC Reference: NEC 504.80(C)

Question 54: Conductors run in parallel per 310.10(G) must be:

  • Same length, material, size, insulation, and termination method
  • Different sizes mixed for ampacity flexibility
  • Different lengths but same insulation
  • 6 AWG minimum

NEC Reference: NEC 310.10(G)

Question 55: In Class I, Division 1 locations, boxes and fittings for joints and splices must be:

  • Explosion proof
  • Water proof
  • Dust proof
  • Fire proof

NEC Reference: NEC 500.7(A)

Question 56: Type NM cable (Romex) is NOT permitted to be installed in which of the following locations?

  • Inside the walls of a wood-frame house
  • Embedded in poured concrete or aggregate fill
  • In an attic space with loose insulation
  • In a crawl space with direct support from the floor joists

NEC Reference: NEC 334.12(A)(3)

Question 57: What is the nominal voltage of a lead-acid cell?

  • 2 volts
  • 1.2 volts
  • 1.7 volts
  • 2.2 volts

NEC Reference: NEC 480.2

Question 58: A 45 kVA, 480–208Y/120V transformer has both primary and secondary overcurrent protection. The primary current works out to about 93.75A. What is the maximum size primary OCPD?

  • 100A
  • 125A
  • 225A
  • 250A

NEC Reference: NEC 450.3(B)

Question 59: EMT shall be securely fastened in place at least every ____

  • 10 ft
  • 8 ft
  • 15 ft
  • 20 ft

NEC Reference: NEC 358.30(A)

Question 60: A motor-compressor with a rated-load current of 20 A is on a 240-volt single-phase supply. What branch-circuit protection rating is normally used?

  • 35 amperes
  • 20 amperes
  • 25 amperes
  • 30 amperes

NEC Reference: NEC 440.22(A)

Question 61: A multiwire branch circuit generally may supply only:

  • Line-to-line loads
  • Line-to-neutral loads
  • Receptacle loads only
  • Service loads

NEC Reference: NEC 210.4(C)

Question 62: What is the maximum continuous load that can be connected to 240 volts 20 ampere branch circuit?

  • 16 amperes
  • 20 amperes
  • 14 amperes
  • 10 amperes

NEC Reference: NEC 210.20

Question 63: What is the minimum rating of a 3-wire service disconnecting means for a one-family dwelling?

  • 100 Amperes
  • 150 Amperes
  • 50 Amperes
  • 90 Amperes

NEC Reference: NEC 230.79(C)

Question 64: What is the general lighting unit load for retail stores, per NEC Table 220.42(A)?

  • 1.9 VA per sq ft
  • 3 VA per sq ft
  • 4 VA per sq ft
  • 5 VA per sq ft

NEC Reference: NEC Table 220.42(A)

Question 65: The secondary voltage of a transformer supplying impedance heating elements must not be over ____ volts if it is not GFCI protected.

  • 30
  • 80
  • 50
  • 40

NEC Reference: NEC 426.32, 427.27

Question 66: A 30-ampere branch circuit may supply fixed lighting units with heavy-duty lampholders in:

  • Single family dwelling unit
  • Multi family dwelling unit
  • Any occupancy
  • Any occupancy other than dwelling unit

NEC Reference: NEC 210.23

Question 67: On a 25-ampere branch circuit, what is the minimum size copper THW conductor?

  • 14 AWG
  • 8 AWG
  • 12 AWG
  • 10 AWG

NEC Reference: NEC Table 310.16, 240.4(D)

Question 68: In a load calculation for a commercial kitchen with one electric cooking appliance, what demand factor applies?

  • 100%
  • 80%
  • 90%
  • 75%

NEC Reference: NEC 220.56

Question 69: Lightning protection systems must be bonded to the building electrical grounding system. Why is this required?

  • To improve the lightning protection system performance
  • To prevent dangerous voltage differences (sideflash) between the two systems during a lightning strike
  • So the lightning protection can use the building ground rods instead of its own
  • To allow the main panel breaker to trip when lightning hits

NEC Reference: NEC 250.106

Question 70: An inverse-time circuit breaker is the most common type used in branch circuit and feeder panels. What does "inverse time" mean about how it operates?

  • It trips instantly at any current above its rating
  • It trips faster at higher currents and slower at lower overcurrent levels
  • It trips only after a fixed time delay regardless of current level
  • The trip direction is reversible, meaning it can be reset from either end

NEC Reference: NEC 240.2 (Definitions)

Question 71: A hospital essential electrical system must be divided into three separate branches. What are those three branches?

  • Emergency, standby, and optional standby
  • Life safety, critical, and equipment branches
  • Primary, secondary, and tertiary circuits
  • Normal power, backup power, and UPS circuits

NEC Reference: NEC 517.30(B)(1)

Question 72: Motor branch circuit protection devices can also protect the motor against overloads.

  • True
  • False

NEC Reference: NEC 430.51

Question 73: What is the key difference between a GFCI device (210.8) and ground-fault protection of equipment (GFP per 230.95)?

  • They are the same thing — GFP and GFCI both trip at 5 mA
  • GFCI trips at ~5 mA to protect people; GFP trips at much higher currents to protect equipment
  • GFP trips faster than GFCI but at the same current level
  • GFCI is for residential; GFP is only for outdoor commercial

NEC Reference: NEC 210.8, 230.95

Question 74: Intrinsically safe wiring (Article 504) must be kept separated from non-intrinsically safe circuits. What is the minimum separation required in the same enclosure?

  • No separation is required if both circuits are in conduit
  • At least 50 mm (2 inches) or separated by a grounded metal partition
  • At least 6 inches at every point
  • They can share space as long as the IS circuit source is fused at 1A

NEC Reference: NEC 504.30(A)

Question 75: According to NEC 210.12(B), where are arc fault circuit interrupters (AFCI) required in a dwelling unit?

  • Only bedroom circuits
  • Only where GFCI is not installed
  • 15- and 20-A, 120-V circuits supplying outlets in kitchens, family rooms, dining and living rooms, bedrooms, hallways, closets, laundry areas and similar rooms
  • Only kitchens and dining areas

NEC Reference: NEC 210.12(B)

Question 76: A Maryland dwelling has a whole-house surge protective device (SPD) at the service. Per 230.67(A), is this required?

  • Yes, all dwelling unit services require a surge protective device
  • No, SPDs are never required
  • SPDs are only required for services over 400 amps
  • SPDs are required only in commercial occupancies

NEC Reference: NEC 230.67(A)

Question 77: What is the general purpose of an equipment bonding jumper on equipment installed in a Class I hazardous location?

  • Maintain a reliable low-impedance fault-current path
  • Reduce voltage drop only
  • Improve lighting levels
  • It has no real safety purpose

NEC Reference: NEC 501.30

Question 78: What is the minimum size conductor allowed to be run in parallel per NEC 310.10(H)(1)?

  • No. 4 AWG
  • No. 2 AWG
  • 1/0 AWG
  • No. 8 AWG

NEC Reference: NEC 310.10(G)(1)

Question 79: A flexible metal conduit (FMC) whip supplying a rooftop unit measures 7 feet. Under 250.118, can it serve as the sole equipment grounding path?

  • Yes, FMC always qualifies as an equipment ground
  • No, past 6 feet a separate equipment grounding conductor is required
  • Yes, but only for circuits under 20 amps
  • No, FMC is never permitted as a grounding path

NEC Reference: NEC 250.118

Question 80: A permanently connected motor-operated appliance rated over 1/8 horsepower, that is not readily accessible, must be provided with a disconnecting means that is:

  • Capable of being locked in the open position
  • Not required at all
  • Always within sight, with no exceptions
  • Only a cord-and-plug is acceptable

NEC Reference: NEC 422.31(C)

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
WHY GO PRO

Full-Length Pro for Michigan

You just practiced on one full-length, Michigan-style exam built to mirror the real licensing test — timing, weighting, and difficulty included.

14 More Michigan Exams15 in total, 1 free + 14 Pro
Full Topic ReportEvery attempt, topic-by-topic
Answer ReviewEvery explanation and NEC reference

$19 once for Michigan · pay once, keep forever

Unlock 14 more Michigan exams — $19
EXAM CARD JOURNEYMAN FREE
Questions80
Time limit240 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)
About This Exam

80 questions, 240 min, 70% to pass — sized and paced like the Michigan licensing exam. Finish it to see your score and your 3 weakest topics, free.

Open book: the real Michigan exam lets you use the NEC. Keep your code book next to you and practise looking things up.

About the Michigan electrician exam


Full-Length Pro · Michigan
  • 15 Michigan exams: 1 free + 14 Pro
  • Full topic report on every attempt
  • Answer review with explanations + NEC references
  • Unlimited retakes

$19 once for Michigan only · pay once, keep forever

Unlock 14 more Michigan exams — $19