JOURNEYMAN NEC 2023 FREE FULL-LENGTH EXAM

California Journeyman Electrician Practice Test - Full-Length Test 1

A full-length, 100-question practice exam covering all 8 core NEC topic areas, weighted the same way the real exam is. Modeled on California's real licensing exam format.

See California electrician licensing requirements, fees & exam format

FREE FULL-LENGTH EXAM
100
Questions
240 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

About This Exam

100 questions, 240 min, 70% to pass — sized and paced like the California licensing exam. Finish it to see your score and your 3 weakest topics, free.

Open book: the real California exam lets you use the NEC. Keep your code book next to you and practise looking things up.

About the California electrician exam


Full-Length Pro · California
  • 15 California exams: 1 free + 14 Pro
  • Full topic report on every attempt
  • Answer review with explanations + NEC references
  • Unlimited retakes

$19 once for California only · pay once, keep forever

Unlock 14 more California exams — $19
TOPICS COVERED
General Requirements Equipment for General Use Wiring and Protection Special Occupancies Load Calculations Wiring Methods and Materials Motor Circuits Special Equipment
How It Works Watch videoHow It Works

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 240 min for 100 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
See where you stand
After submitting you'll see your score, pass/fail and your 3 weakest topics. The full topic report and answer review with explanations are part of Full-Length Pro.

Frequently Asked Questions

Yes. Test 1 for every state is free: you get your score, pass/fail and your 3 weakest topics. The other 14 California exams, the full topic report and the answer review are part of Full-Length Pro ($19 once for California).

100 questions in 240 minutes, sized and paced like the California journeyman exam.

This exam uses a 70% pass mark. Check your state licensing board for the current official passing score.

It is written to the 2023 NEC. Confirm with your state licensing board which edition is adopted for your exam date.

No. Pro is bought per state and covers California only. If you change states, you can unlock that state separately.

How to Use This Practice Test

This California Journeyman Electrician Practice Test - Full-Length Test 1 has 100 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: This is an open-book exam — tab your NEC index and Articles 210, 250, and 430 before you start.

  • Topics covered: Branch circuits, grounding, wiring methods, load calculations, and motors.
  • Passing score: 70–75% (most states). Aim for 80% on practice tests so the real exam feels easy.
  • Questions: 100 multiple-choice, one correct answer each
JOURNEYMAN · NEC 2023
California Journeyman Electrician Practice Test - Full-Length Test 1
Q1 / 100
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
You passed a full-length exam! Post it on LinkedIn — foremen and recruiters notice.

California Journeyman Electrician Practice Test - Full-Length Test 1 — Question List

Question 1: What must be provided for electrical equipment that is exposed to physical damage?

  • Warning signs
  • Working space
  • Enclosures or guards
  • Extra headroom

NEC Reference: NEC 110.27(B)

Question 2: A 3-phase overcurrent device (such as a delta breaker) must not be connected to the bus of a panelboard that has fewer than how many bus bars?

  • 3
  • 2
  • 4
  • 5

NEC Reference: NEC 408.36(C)

Question 3: Instruments, pilot lights and potential transformers on switchboards must be supplied by circuits protected by overcurrent devices rated not more than:

  • 30 amperes
  • 15 amperes
  • 20 amperes
  • 10 amperes

NEC Reference: NEC 408.52

Question 4: A ground ring used as a grounding electrode must encircle the building with at least how many feet of bare copper conductor, and buried at least how deep?

  • At least 10 feet, buried 18 inches deep
  • At least 20 feet, buried 30 inches deep
  • At least 20 feet, buried 18 inches deep
  • At least 30 feet, buried 24 inches deep

NEC Reference: NEC 250.52(A)(4)

Question 5: Amusement rides and attractions must not be located closer than how far in any direction from overhead conductors operating at 600 V or less?

  • 20 feet
  • 15 feet
  • 12 feet
  • 8 feet

NEC Reference: NEC 525.5

Question 6: What is the smallest aluminum conductor permitted for underground service conductors?

  • 8 AWG
  • 6 AWG
  • 10 AWG
  • 12 AWG

NEC Reference: NEC 230.31(B)

Question 7: A feeder serves a heating load of 30 kW and a cooling load of 22 kW, both not in use at the same time. For service-load calculations, the value used is:

  • Sum of both = 52 kW
  • Average = 26 kW
  • Larger only = 30 kW
  • 125% of larger = 37.5 kW

NEC Reference: NEC 220.60

Question 8: A feeder uses two 500 kcmil THWN conductors per phase in parallel. How must the equipment grounding conductor be sized for the parallel set?

  • One EGC sized for the total parallel conductor ampacity is acceptable
  • Each conduit must have its own EGC sized per Table 250.122 for the OCPD rating
  • No EGC is required when using parallel conductors of 500 kcmil or larger
  • The EGC size is based on the conductor size, not the OCPD rating

NEC Reference: NEC 250.122(F)

Question 9: The current carried continuously in bare copper bars in sheet metal auxiliary gutters must not exceed how many amperes per square inch of cross section?

  • 1000 A per sq in
  • 750 A per sq in
  • 700 A per sq in
  • 900 A per sq in

NEC Reference: NEC 366.23

Question 10: What is the minimum load for the required exterior sign or outline lighting for a commercial occupancy as per NEC?

  • 1,200 VA
  • 1,500 VA
  • 1,000 VA
  • 1,800 VA

NEC Reference: NEC 220.14(F)

Question 11: An air conditioning system is fed from its own panel. Per Article 440, the overcurrent protection for the A/C branch circuit is determined by which rule, not just Article 240?

  • Article 240 ampacity rules always govern A/C circuits
  • Article 440 governs — the OCPD is sized per nameplate BCSC, not just conductor ampacity
  • Article 430 motor rules govern all A/C equipment
  • A/C circuits use the same sizing rules as any other appliance

NEC Reference: NEC Article 440

Question 12: What is the calculated load for a single piece of equipment with four receptacles in a retail shop?

  • 360 Volt-Ampere
  • 720 Volt-Ampere
  • 800 Volt-Ampere
  • 180 Volt-Ampere

NEC Reference: NEC 220.14(I)

Question 13: A feeder supplies a 10 HP and a 15 HP motor, both 230 V, 3-phase, protected by inverse-time breakers. What is the maximum feeder protection?

  • 175 A
  • 105 A
  • 125 A
  • 200 A

NEC Reference: NEC 430.250

Question 14: Dry-type transformers rated not more than ____ are permitted to be installed in hollow spaces of buildings.

  • 50 KVA
  • 100 KVA
  • 85 KVA
  • 75 KVA

NEC Reference: NEC 450.13(B)

Question 15: What is the calculated load for a show window that is 10 feet long, measured horizontally along its base?

  • 2000 V-A
  • 1800 V-A
  • 1600 V-A
  • 2200 V-A

NEC Reference: NEC 220.43(A)

Question 16: In a Class I, Division 1 classified area, sealing fittings in conduit runs must be installed within how many inches of an enclosure where the conduit enters or exits?

  • 6 inches
  • 12 inches
  • 18 inches
  • 36 inches

NEC Reference: NEC 501.15(A)(1)

Question 17: A 120-volt, 30-ampere branch circuit supplies lighting outlets and a cord-and-plug connected air conditioner. What is the maximum full-load current of the air conditioner?

  • 15 amperes
  • 24 amperes
  • 30 amperes
  • 20 amperes

NEC Reference: NEC 440.62(C)

Question 18: What is the ampacity of 8 AWG copper THWN at 75°C?

  • 40 A
  • 50 A
  • 55 A
  • 65 A

NEC Reference: NEC Table 310.16

Question 19: What is the maximum size fuse allowed to protect 12 AWG THW copper branch conductor?

  • 15 amperes
  • 20 amperes
  • 25 amperes
  • 30 amperes

NEC Reference: NEC 240.4(D)(5)

Question 20: The over load protection must be provided for the motor if it is rated more than ____ Hp.

  • 1/8 Hp
  • 1/4 Hp
  • 1/2 Hp
  • 1 Hp

NEC Reference: NEC 430.32(A)

Question 21: What is the minimum rating of the service disconnecting means for a one-family dwelling?

  • 100 ampere for a 3 wire service
  • 140 ampere for a 2 wire service
  • 50 ampere for a 3 wire service
  • 80 ampere for a 2 wire service

NEC Reference: NEC 230.79

Question 22: How many small appliance branch circuits are required at minimum for the kitchen and dining area of a single-family dwelling?

  • One 20A circuit
  • Two 20A circuits
  • Three 20A circuits
  • One 30A circuit

NEC Reference: NEC 210.11(C)(1)

Question 23: A panelboard is equipped with snap switches rated 30 amperes or less. Its overcurrent protection must not exceed:

  • 30 amperes
  • 150 amperes
  • 200 amperes
  • 225 amperes

NEC Reference: NEC 408.36(A)

Question 24: The overcurrent protection for a feeder or branch circuit must be located where the conductors receive their supply. When is it permitted to place the overcurrent device away from the supply point?

  • Whenever the load end breaker is close to the equipment
  • When one of the specific tap rule exceptions in 240.21 applies
  • For any feeder run longer than 25 feet
  • The OCPD location is always flexible — it can go anywhere in the circuit

NEC Reference: NEC 240.21(A)

Question 25: A nonautomatic arc welder has a 60% duty cycle and primary current of 50A. Table 630.11(A) gives a multiplier of 0.78 for 60% duty cycle. What is the minimum branch circuit conductor ampacity?

  • 33A — using a 0.65 factor
  • 39A — 50A × 0.78
  • 44A — 50A × 0.89 (80% factor)
  • 50A — no duty cycle reduction

NEC Reference: NEC 630.11(A)

Question 26: Under which condition may conductors of different circuits occupy the same raceway?

  • If the insulation rating voltage is not less than the maximum circuit voltage
  • If the insulating rating voltage is greater than the maximum circuit voltage
  • If the two circuits have same voltage
  • If the two circuits have same insulation rating voltage

NEC Reference: NEC 300.3(C)(1)

Question 27: Overhead service conductors must not be smaller than ____ copper.

  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG

NEC Reference: NEC 230.23(B)

Question 28: A Quick Recovery electric heater is rated at 4500 watts 240 volts. What rating of circuit breaker is required for protecting it?

  • 30 Amperes
  • 25 Amperes
  • 20 Amperes
  • 15 Amperes

NEC Reference: NEC 422.13

Question 29: Insulated equipment grounding conductors are identified by which color?

  • Red
  • Green (or green with yellow stripes)
  • Gray
  • White

NEC Reference: NEC 250.119

Question 30: Which circuits must NOT be connected to any system that contains trolley wires with a ground return?

  • Circuits for lighting and power
  • Grounding conductors
  • Ungrounded trolley wires
  • Bonding conductors

NEC Reference: NEC 110.19

Question 31: A hermetic refrigerant motor-compressor has a rated-load current of 34 A. What is the minimum ampere rating of its disconnecting means?

  • 45 amperes
  • 34 amperes
  • 50 amperes
  • 40 amperes

NEC Reference: NEC 440.12(A)(1)

Question 32: A single-family dwelling has one air conditioner rated 4 kW and fixed heating equipment rated 3 kW. What is the calculated load for both?

  • 4 KW
  • 7 KW
  • 3.5 KW
  • 3 KW

NEC Reference: NEC 220.60

Question 33: What is the minimum ampere rating of short circuit ground fault protective device that can be used for individual motor-compressor?

  • 12 amperes
  • 15 amperes
  • 20 amperes
  • 18 amperes

NEC Reference: NEC 440.22(A)

Question 34: In a wet location, a surface-mounted cabinet must be mounted so there is at least how much air space between the enclosure and the wall?

  • 1/4 inch
  • 1/2 inch
  • 3/4 inch
  • 1 inch

NEC Reference: NEC 312.2

Question 35: A panelboard contains snap switches rated 30 amperes or less. What is the maximum rating of its overcurrent protection?

  • 30 amperes
  • 120 amperes
  • 45 amperes
  • 200 amperes

NEC Reference: NEC 408.36(A)

Question 36: Which of the following loads is NOT permitted to be connected to a small appliance branch circuit (SABC)?

  • A toaster plugged into a counter receptacle
  • A refrigerator in the kitchen
  • A microwave on the counter
  • A ceiling light fixture in the kitchen

NEC Reference: NEC 210.52(B)(2)

Question 37: What is the corrected ampacity of 1/0 copper THWN in a wet location where the ambient temperature is 40°C?

  • 123 Amperes
  • 132 Amperes
  • 150 Amperes
  • 141 Amperes

NEC Reference: NEC 310.16

Question 38: What is the smallest conductor permitted for the pool equipotential bonding grid?

  • 8 AWG solid copper
  • 12 AWG copper
  • 10 AWG copper
  • 6 AWG aluminum

NEC Reference: NEC 680.26(B)

Question 39: For a single-family dwelling unit, what is the minimum allowable rating of 3-wire service-entrance conductors?

  • 120 amperes
  • 100 amperes
  • 150 amperes
  • 200 amperes

NEC Reference: NEC 230.42(B)

Question 40: A 240-volt, single-phase room air conditioner rated not more than ____ may be considered a single motor unit.

  • 30 amperes
  • 40 amperes
  • 50 amperes
  • 60 amperes

NEC Reference: NEC 440.62(A)(2)

Question 41: A 19,000 sq ft commercial building has one hundred eighty 15 A and 20 A, 120 V receptacles. What is the calculated receptacle load?

  • 21,200 VA
  • 18,000 VA
  • 19,600 VA
  • 23,500 VA

NEC Reference: NEC 220.14(I), 220.44

Question 42: A service is supplied by three parallel sets of 400 kcmil copper conductors. What size copper grounding electrode conductor is required?

  • 3/0 AWG
  • 2/0 AWG
  • 2 AWG
  • 4 AWG

NEC Reference: NEC Table 250.66

Question 43: Every commercial occupancy that is accessible to pedestrians must have at least one circuit dedicated to what?

  • An outdoor GFCI circuit
  • A sign or outline lighting outlet
  • An emergency lighting circuit
  • A dedicated circuit for the cash register

NEC Reference: NEC 600.5(A)

Question 44: What is the minimum general lighting load of a 110,000 sq ft school?

  • 330 KVA
  • 220 KVA
  • 165 KVA
  • 440 KVA

NEC Reference: NEC Table 220.42(A)

Question 45: What is the general lighting load of a 2,500 sq ft dwelling unit that has 20 receptacles and 15 luminaires rated 100 W each?

  • 7500 Volt-Amperes
  • 11000 Volt-Amperes
  • 9500 Volt-Amperes
  • 12000 Volt-Amperes

NEC Reference: NEC 220.41, 220.14(J)

Question 46: Service drop conductors at the point where they enter a dwelling (over a porch or walkway accessible only to pedestrians) must be at least how many feet above the ground?

  • 8 feet
  • 10 feet
  • 12 feet
  • 15 feet

NEC Reference: NEC 230.24(B)(1)

Question 47: How many receptacles must be installed at a minimum for each patient bed in a Category 1 (critical care) patient bed location?

  • 4 receptacles
  • 8 receptacles
  • 12 receptacles
  • 14 receptacles

NEC Reference: NEC 517.19(B)

Question 48: What is the minimum load included for each outlet for a heavy-duty lampholder?

  • 600 volt-amperes
  • 560 volt-amperes
  • 460 volt-amperes
  • 760 volt-amperes

NEC Reference: NEC 220.14(E)

Question 49: What is the minimum size copper conductor permitted for overhead spans up to 50 ft (1000 V or less)?

  • 8 AWG
  • 10 AWG
  • 6 AWG
  • 12 AWG

NEC Reference: NEC 225.6(a)

Question 50: A raceway carries 6 current-carrying THWN conductors in a 40°C ambient. The 75°C ampacity from Table 310.16 must be multiplied by what combined factor?

  • 0.80
  • 0.88
  • 0.70 (about)
  • 0.65

NEC Reference: NEC 310.15(B)(1) / Table 310.15(C)(1)

Question 51: A retail shop has 20 duplex receptacles, each on its own yoke. What is the calculated load for these receptacles?

  • 300 volt-amperes
  • 3,600 volt-amperes
  • 1,800 volt-amperes
  • 36,000 volt-amperes

NEC Reference: NEC 220.14(I)

Question 52: Exposed live parts of a motor operating at 120 volts must be guarded.

  • True
  • False

NEC Reference: NEC 430.232

Question 53: What percentage of rated ampacity is allowed for each conductor when a flexible cord has eight current-carrying conductors?

  • 80
  • 70
  • 60
  • 50

NEC Reference: NEC 400.5(A)(3)

Question 54: All 125-volt, 15- and 20-ampere receptacles installed in dwelling unit bathrooms require:

  • Non-grounding receptacles
  • Weatherproof receptacles
  • Protective guards
  • GFCI protection

NEC Reference: NEC 210.8(A)(1)

Question 55: What size service conductors are required for a dwelling load with a calculated load is 190 A. The service disconnect breaker is rated at 200 A?

  • 1/0 AWG
  • 2/0 AWG
  • 3/0 AWG
  • 4/0 AWG

NEC Reference: NEC 310.12

Question 56: If four current-carrying conductors are in a raceway, each conductor's allowable ampacity is reduced to:

  • 80 % of ampere rating of the conductor
  • Maximum ampere rating of the conductor
  • 70 % of ampere rating of the conductor
  • 60 % of ampere rating of the conductor

NEC Reference: NEC Table 310.15(C)(1)

Question 57: Electrical equipment at 120/240 volts has exposed live parts on the front only (Condition 1). What minimum working space depth is required in front of it?

  • 4 feet
  • 3 feet
  • 5 feet
  • 2 feet

NEC Reference: NEC Table 110.26(A)(1)

Question 58: For a permanently connected appliance rated not more than 300 volt-amperes or ____, the branch-circuit overcurrent device can serve as the disconnecting means.

  • 1/2 horsepower
  • 3/4 horsepower
  • 1 horsepower
  • 1/8 horsepower

NEC Reference: NEC 422.31(A)

Question 59: The maximum fill percentage allowed for conductors inside a metallic wireway is:

  • 10%
  • 20%
  • 40%
  • 53%

NEC Reference: NEC 376.22(A)

Question 60: What size overcurrent device is required for a 24 A continuous load?

  • 30 amperes
  • 24 amperes
  • 28 ampers
  • 26 amperes

NEC Reference: NEC 210.20(A)

Question 61: Underground service raceways or ducts entering a building must be sealed.

  • True
  • False

NEC Reference: NEC 230.8

Question 62: Five current-carrying conductors, each with an ampacity of 25 A, are in the same cable. What is the adjusted ampacity of each conductor?

  • 25 amperes
  • 20 amperes
  • 30 amperes
  • 22.5 amperes

NEC Reference: NEC Table 310.15(C)(1)

Question 63: Service-entrance cables must be supported by straps within what distance of every service head?

  • 24 inches
  • 36 inches
  • 12 inches
  • 15 inches

NEC Reference: NEC 230.51(A)

Question 64: Flexible cords and cables used to power rides and equipment at carnivals and fairs must be rated for:

  • Light use only — carnival voltages are low
  • Any listed flexible cord rated for the voltage and current
  • Hard-usage or extra-hard-usage service
  • Type NM cable only — flexible cords are not allowed outdoors

NEC Reference: NEC 525.20(B)

Question 65: An electrician installs a motor according to all NEC rules, but the motor manufacturer instructions say to use a specific wiring method and conductor size that is more restrictive than what the NEC requires. Which takes precedence?

  • The NEC always overrides manufacturer instructions
  • The manufacturer installation instructions — they are part of the listing
  • Whichever is less expensive to install
  • The local building code, which supersedes both

NEC Reference: NEC 110.3(B)

Question 66: A ground ring used as a grounding electrode must use a copper conductor not smaller than what size?

  • 6 AWG bare copper
  • 4 AWG bare copper
  • 2 AWG bare copper
  • 1/0 AWG bare copper

NEC Reference: NEC 250.52(A)(4)

Question 67: What is the maximum overcurrent protection for 16 AWG copper conductors?

  • 15 A
  • 7 A
  • 20 A
  • 10 A

NEC Reference: NEC 240.4(D)(2)

Question 68: A branch-circuit-rated circuit breaker is marked for use with 18 AWG copper and supplies a continuous load of 5.6 A. What overcurrent protection may be used?

  • 7 amperes
  • 10 amperes
  • 15 amperes
  • 20 amperes

NEC Reference: NEC 240.4(D)(1)

Question 69: At least how many entrances of sufficient area must be provided to give access to the working space around electrical equipment?

  • 1
  • 2
  • 3
  • 4

NEC Reference: NEC 110.26

Question 70: A transformer secondary in a building has a 2-wire, 240V secondary with a 50A rated secondary conductor. A feeder tap from the secondary conductor runs 15 feet to a panelboard. No OCPD is at the tap point. Under 240.21(C)(1), is this tap permitted?

  • Yes — transformer secondary taps have no length limit
  • No — 15 feet exceeds the 10-foot secondary tap rule; the 25-foot rule conditions must be checked instead
  • Yes — 15 feet is permitted as long as the conductors are in conduit
  • No — any transformer secondary must have an OCPD directly at the secondary terminals

NEC Reference: NEC 240.21(C)

Question 71: What is the smallest standard ampere rating for fuses and inverse-time circuit breakers in Table 240.6(A)?

  • 10 amperes
  • 15 amperes
  • 20 amperes
  • 25 amperes

NEC Reference: NEC 240.6(A)

Question 72: An Article 411 low-voltage lighting system operates at 30 volts ac or less. What peak voltage does that correspond to?

  • 34 volts
  • 30 volts
  • 38.2 volts
  • 42.4 volts

NEC Reference: NEC 411.1

Question 73: The rating of the overcurrent device protecting a panelboard must ____ the panelboard rating.

  • Not be greater than
  • Be 125% of
  • Be greater than
  • Be 115% of

NEC Reference: NEC 408.36

Question 74: Field-installed secondary wiring for electric signs of 1000 volts or less must use conductors not smaller than:

  • 18 AWG
  • 16 AWG
  • 14 AWG
  • 12 AWG

NEC Reference: NEC 600.31

Question 75: Adjustment factors for more than three current-carrying conductors do not apply to conductors in raceways not exceeding what length?

  • 24 inch
  • 28 inch
  • 18 inch
  • 20 inch

NEC Reference: NEC 310.15(C)(1)(b)

Question 76: For outside branch circuits 1000 V or less, overhead conductors for spans up to 50 ft must not be smaller than:

  • 18 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG

NEC Reference: NEC 225.6(A)(1)

Question 77: The minimum headroom of the working space in front of a panelboard, switchboard, or motor control center must be at least:

  • 6 feet
  • 6.5 feet (2.0 m)
  • 7 feet
  • 8 feet

NEC Reference: NEC 110.26(A)(3)

Question 78: An all-electric restaurant has a connected load of 150 kVA on a 120/208 V, 3-phase supply. Using the optional method, what is the required service conductor ampacity?

  • 444 A
  • 333 A
  • 416 A
  • 577 A

NEC Reference: NEC 220.88

Question 79: What size inverse-time circuit breaker is permitted for a 10 HP, 230-volt, 3-phase motor?

  • 70A
  • 56 A
  • 40A
  • 30 A

NEC Reference: NEC 430.250

Question 80: Overhead conductors for festoon lighting must not be smaller than:

  • 8 AWG
  • 6 AWG
  • 12 AWG
  • 10 AWG

NEC Reference: NEC 225.6(B)

Question 81: What is the branch-circuit calculated load for a single 12 kW electric range in a dwelling unit?

  • 6 KW
  • 8 KW
  • 12 KW
  • 15 KW

NEC Reference: NEC 220.55

Question 82: A mechanical contractor wants to run a water supply pipe through the dedicated electrical space directly above a 200A panelboard. Is this permitted?

  • Yes — water pipe above the panel is fine as long as it does not drip
  • No — foreign systems including pipes are not permitted in the dedicated electrical space
  • Yes — but a drip shield must be installed above the panel
  • Yes — the pipe is permitted if it runs parallel to the panel, not over it

NEC Reference: NEC 110.26(F)(1)(b)

Question 83: Splices and taps in a cabinet or cutout box must not fill more than what percent of the cross-sectional area at that point?

  • 75
  • 70
  • 60
  • 80

NEC Reference: NEC 312.8

Question 84: A roof-mounted A/C unit must have a disconnecting means located per 440.14 within sight from the equipment OR:

  • Lockable in the open position per 110.25
  • Inside the air handler
  • At the service panel only
  • Within 100 feet

NEC Reference: NEC 440.14

Question 85: An Oregon dwelling has 1,600 square feet of living area. Using 220.41's 3 VA per square foot general lighting load, what is the total general lighting load?

  • 3,200 VA
  • 4,800 VA
  • 6,400 VA
  • 8,000 VA

NEC Reference: NEC 220.41

Question 86: What is the maximum total of bends permitted in an EMT run between pull points?

  • 60 degrees
  • 90 degrees
  • 180 degrees
  • 360 degrees

NEC Reference: NEC 358.26

Question 87: A branch circuit supplies a continuous load of 16 amperes. Per NEC 210.19(A)(1), what is the minimum ampacity the branch circuit conductor must have?

  • 16 amperes
  • 18 amperes
  • 20 amperes
  • 25 amperes

NEC Reference: NEC 210.19(A)(1)

Question 88: A demand factor is applied to certain dwelling loads because not all loads are likely to operate:

  • At the same time
  • At full voltage
  • On the same phase
  • From the same panelboard

NEC Reference: NEC Table 220.45

Question 89: Conductors feeding through a cabinet, cutout box, or meter socket enclosure that are not connected to equipment in the enclosure are permitted only if the conductor fill does not exceed what percentage of the cross-sectional area?

  • 40 %
  • 20 %
  • 60 %
  • 100 %

NEC Reference: NEC 312.8

Question 90: In a standard 2-wire branch circuit, how does the size of the neutral conductor compare to the hot conductor?

  • Half the size of the hot conductor
  • At least the same size as the hot conductor
  • Double the size of the hot conductor
  • No neutral is needed in a 2-wire circuit

NEC Reference: NEC 210.19(A)

Question 91: A clothes dryer nameplate reads 4,700 watts. Under 220.54, what value must be used for load calculation purposes?

  • 4,700 watts
  • 5,000 watts
  • 3,760 watts
  • 9,400 watts

NEC Reference: NEC 220.54

Question 92: What size branch-circuit conductor is required for an 18-ampere motor-compressor connected to a 240-volt circuit, with terminals rated at 75 C?

  • 12 AWG
  • 10 AWG
  • 14 AWG
  • 8 AWG

NEC Reference: NEC 440.32 / Table 310.16

Question 93: Conductors are permitted to be connected in parallel (electrically joined at both ends) only when they are sized:

  • 1/0 AWG and larger
  • 14 AWG and larger
  • 8 AWG and larger
  • Any size is permitted to be paralleled

NEC Reference: NEC 310.10(G)(1)

Question 94: The 10-foot feeder tap rule (240.21(B)(1)) allows a smaller conductor to be tapped from a feeder without an OCPD at the tap point. What is a key condition that must be met?

  • Tap conductors must be in free air only, not in conduit
  • Tap conductors must be at least 1/10 the rating of the feeder OCPD and enclosed in a raceway
  • Tap conductors must match the ampacity of the full feeder
  • Tap conductors longer than 10 feet are acceptable if in conduit

NEC Reference: NEC 240.21(B)(1)

Question 95: Fixed outdoor electric de-icing and snow-melting equipment must be protected by:

  • Ground-fault protection of equipment (GFPE)
  • No protection at all
  • A simple fuse only, no GFPE
  • AFCI protection only

NEC Reference: NEC 426.28

Question 96: Per Article 100, how does the NEC define "identified" as applied to equipment suitability?

  • Recognizable as suitable for the specific purpose, use, or application, per a qualified testing lab
  • "Identified" simply means the equipment has a serial number
  • Identified equipment need not be evaluated by any testing entity
  • "Identified" and "listed" mean the exact same thing in every context

NEC Reference: NEC Art. 100

Question 97: Per NEC 230.42(B), ungrounded service-entrance conductors for a specific installation generally must not be smaller than what, relative to the service disconnecting means?

  • The rating of the service disconnecting means
  • 125% of the disconnect rating
  • Half the disconnect rating
  • The utility transformer rating

NEC Reference: NEC 230.42(B)

Question 98: A motor nameplate shows FLA = 40A and service factor = 1.15. What is the highest trip setting allowed on the overload relay?

  • 40A — match the FLA exactly
  • 46A — 115% of FLA
  • 50A — 125% of FLA
  • 56A — 140% of FLA

NEC Reference: NEC 430.32(A)(1)

Question 99: Which NEC article generally covers intrinsically safe systems, including conductor color identification requirements?

  • Article 504
  • Article 500
  • Article 725
  • Article 501

NEC Reference: NEC Article 504

Question 100: A Maryland contractor installs a junction box in a finished ceiling but leaves it accessible via a removable ceiling tile. Per 314.29, is this compliant?

  • Yes, a removable ceiling tile provides access without removing building structure
  • No, all junction boxes must be surface mounted and fully exposed
  • No, boxes above a ceiling are always prohibited regardless of access
  • Accessibility rules do not apply to junction boxes

NEC Reference: NEC 314.29

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
WHY GO PRO

Full-Length Pro for California

You just practiced on one full-length, California-style exam built to mirror the real licensing test — timing, weighting, and difficulty included.

14 More California Exams15 in total, 1 free + 14 Pro
Full Topic ReportEvery attempt, topic-by-topic
Answer ReviewEvery explanation and NEC reference

$19 once for California · pay once, keep forever

Unlock 14 more California exams — $19
EXAM CARD JOURNEYMAN FREE
Questions100
Time limit240 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)
About This Exam

100 questions, 240 min, 70% to pass — sized and paced like the California licensing exam. Finish it to see your score and your 3 weakest topics, free.

Open book: the real California exam lets you use the NEC. Keep your code book next to you and practise looking things up.

About the California electrician exam


Full-Length Pro · California
  • 15 California exams: 1 free + 14 Pro
  • Full topic report on every attempt
  • Answer review with explanations + NEC references
  • Unlimited retakes

$19 once for California only · pay once, keep forever

Unlock 14 more California exams — $19