JOURNEYMAN NEC 2023 FREE FULL-LENGTH EXAM

Maryland Journeyman Electrician Practice Test - Full-Length Test 1

A full-length, 70-question practice exam covering all 8 core NEC topic areas, weighted the same way the real exam is. Modeled on Maryland's real licensing exam format.

See Maryland electrician licensing requirements, fees & exam format

FREE FULL-LENGTH EXAM
70
Questions
240 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

About This Exam

70 questions, 240 min, 70% to pass — sized and paced like the Maryland licensing exam. Finish it to see your score and your 3 weakest topics, free.

Open book: the real Maryland exam lets you use the NEC. Keep your code book next to you and practise looking things up.

About the Maryland electrician exam


Full-Length Pro · Maryland
  • 15 Maryland exams: 1 free + 14 Pro
  • Full topic report on every attempt
  • Answer review with explanations + NEC references
  • Unlimited retakes

$19 once for Maryland only · pay once, keep forever

Unlock 14 more Maryland exams — $19
TOPICS COVERED
Special Equipment General Requirements Equipment for General Use Wiring Methods and Materials Load Calculations Wiring and Protection Motor Circuits Special Occupancies
How It Works Watch videoHow It Works

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 240 min for 70 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
See where you stand
After submitting you'll see your score, pass/fail and your 3 weakest topics. The full topic report and answer review with explanations are part of Full-Length Pro.

Frequently Asked Questions

Yes. Test 1 for every state is free: you get your score, pass/fail and your 3 weakest topics. The other 14 Maryland exams, the full topic report and the answer review are part of Full-Length Pro ($19 once for Maryland).

70 questions in 240 minutes, sized and paced like the Maryland journeyman exam.

This exam uses a 70% pass mark. Check your state licensing board for the current official passing score.

It is written to the 2023 NEC. Confirm with your state licensing board which edition is adopted for your exam date.

No. Pro is bought per state and covers Maryland only. If you change states, you can unlock that state separately.

How to Use This Practice Test

This Maryland Journeyman Electrician Practice Test - Full-Length Test 1 has 70 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: This is an open-book exam — tab your NEC index and Articles 210, 250, and 430 before you start.

  • Topics covered: Branch circuits, grounding, wiring methods, load calculations, and motors.
  • Passing score: 70–75% (most states). Aim for 80% on practice tests so the real exam feels easy.
  • Questions: 70 multiple-choice, one correct answer each
JOURNEYMAN · NEC 2023
Maryland Journeyman Electrician Practice Test - Full-Length Test 1
Q1 / 70
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
You passed a full-length exam! Post it on LinkedIn — foremen and recruiters notice.

Maryland Journeyman Electrician Practice Test - Full-Length Test 1 — Question List

Question 1: A nonautomatic arc welder has a 60% duty cycle and primary current of 50A. Table 630.11(A) gives a multiplier of 0.78 for 60% duty cycle. What is the minimum branch circuit conductor ampacity?

  • 33A — using a 0.65 factor
  • 39A — 50A × 0.78
  • 44A — 50A × 0.89 (80% factor)
  • 50A — no duty cycle reduction

NEC Reference: NEC 630.11(A)

Question 2: An electrician installs a motor according to all NEC rules, but the motor manufacturer instructions say to use a specific wiring method and conductor size that is more restrictive than what the NEC requires. Which takes precedence?

  • The NEC always overrides manufacturer instructions
  • The manufacturer installation instructions — they are part of the listing
  • Whichever is less expensive to install
  • The local building code, which supersedes both

NEC Reference: NEC 110.3(B)

Question 3: What is the maximum weight of a luminaire that may be supported only by the screw shell of a lampholder?

  • 4 pounds
  • 6 pounds
  • 8 pounds
  • 10 pounds

NEC Reference: NEC 410.30(A)

Question 4: What is the ampacity of 1/0 copper THWN-2 in a dry location at 104°F (40°C) if the raceway contains four current-carrying conductors?

  • 132
  • 124
  • 165
  • 170

NEC Reference: NEC 310.16

Question 5: A single-family dwelling has a general lighting load of 4,000 VA. What is the calculated demand load?

  • 3350 VA
  • 3550 VA
  • 4000 VA
  • 3850 VA

NEC Reference: NEC Table 220.45

Question 6: Which of the following is the ampacity of 4 AWG SE cable?

  • 70 A
  • 65 A
  • 80 A
  • 85 A

NEC Reference: NEC 338.10(B)(4)(a), Table 310.16

Question 7: What is the minimum feeder or service load for cloth dryers in a dwelling unit?

  • 5000 watts
  • 2800 watts
  • 4500 watts
  • 6500 watts

NEC Reference: NEC 220.54

Question 8: Up to how many sets of 4-wire feeders may use a common neutral?

  • 2
  • 3
  • 4
  • 5

NEC Reference: NEC 215.4

Question 9: What is the maximum number of receptacles permitted on a 20-ampere, 120-volt branch circuit in a shopping complex?

  • 13
  • 10
  • 18
  • 11

NEC Reference: NEC 220.14(I)

Question 10: Per the 210.19(A)(1) exception for assemblies listed for 100% continuous operation, branch-circuit conductor ampacity may be not less than the continuous load plus the:

  • Noncontinuous load
  • Rated load
  • Maximum load
  • 125% of the noncontinuous load

NEC Reference: NEC 210.19

Question 11: What is the maximum number of service disconnecting means permitted for each service?

  • 4
  • 2
  • 6
  • 8

NEC Reference: NEC 230.71(B)

Question 12: Which circuits must NOT be connected to any system that contains trolley wires with a ground return?

  • Circuits for lighting and power
  • Grounding conductors
  • Ungrounded trolley wires
  • Bonding conductors

NEC Reference: NEC 110.19

Question 13: Per 230.95, ground-fault protection of equipment is required on solidly grounded wye services of more than 150V to ground rated:

  • 400A or more
  • 600A or more
  • 1000A or more
  • 2000A or more

NEC Reference: NEC 230.95

Question 14: What is the maximum rating of a branch circuit supplying the primary of a low-voltage lighting system power supply?

  • 20 amperes
  • 25 amperes
  • 15 amperes
  • 30 amperes

NEC Reference: NEC 411.4

Question 15: A device box is mounted in a concrete block wall. How far can the front edge of the box be set back from the finished wall surface?

  • No setback allowed; the box must be flush
  • ¼ inch maximum setback
  • ½ inch maximum setback
  • 1 inch maximum setback

NEC Reference: NEC 314.20

Question 16: Show window load per 220.43(A) is calculated at not less than:

  • 50 VA per linear foot
  • 100 VA per linear foot
  • 180 VA per linear foot
  • 200 VA per linear foot

NEC Reference: NEC 220.43(A)

Question 17: A motor is in the basement and its disconnect is on the first floor where you cannot see the motor. What does the NEC allow in this situation?

  • A second disconnect must be installed at the motor
  • The disconnect must be capable of being locked in the open position
  • A warning label on the motor is sufficient
  • Nothing extra is needed as long as the disconnect is identified

NEC Reference: NEC 430.102(B)

Question 18: For a 300 ampere electrical circuit, what is the minimum size copper equipment grounding conductor as per NEC?

  • 6 AWG
  • 4 AWG
  • 8 AWG
  • 10 AWG

NEC Reference: NEC 250.122

Question 19: An electric sign outlet has the minimum 1,200 VA load. What load should feeder or service conductors be sized for, treating it as a continuous load?

  • 1,500 VA
  • 1,200 VA
  • 1,800 VA
  • 1,000 VA

NEC Reference: NEC 220.14(F)

Question 20: At least how many entrances of sufficient area must be provided to give access to the working space around electrical equipment?

  • 1
  • 2
  • 3
  • 4

NEC Reference: NEC 110.26

Question 21: A metal underground water pipe is used as a grounding electrode. What additional requirement must be met?

  • The pipe must be at least 10 feet long in contact with the earth
  • At least one supplemental electrode must also be installed
  • The pipe must be bonded to every metallic water fixture in the building
  • The water company must be notified before using the pipe as an electrode

NEC Reference: NEC 250.53(D)(2)

Question 22: Per NEC 220.61(C), the feeder neutral load for nonlinear (harmonic-producing) loads on a 4-wire, wye-connected system is calculated at:

  • 70% of the load above 200A
  • 100% — no reduction permitted
  • 50% of the total
  • 125% of the load

NEC Reference: NEC 220.61(C)

Question 23: The minimum headroom of the working space in front of a panelboard, switchboard, or motor control center must be at least:

  • 6 feet
  • 6.5 feet (2.0 m)
  • 7 feet
  • 8 feet

NEC Reference: NEC 110.26(A)(3)

Question 24: For a permanently installed swimming pool at a house, receptacles that are located between 6 feet and 20 feet from the pool edge must have:

  • AFCI protection
  • GFCI protection
  • Tamper-resistant protection only
  • No special protection — the 6-foot rule is all that applies

NEC Reference: NEC 680.22(A)

Question 25: What is the minimum size of fixture wire permitted by the NEC?

  • 18 AWG
  • 16 AWG
  • 10 AWG
  • 12 AWG

NEC Reference: NEC 402.6

Question 26: How many current-carrying conductors may be in a raceway or cable before adjustment factors must be applied?

  • 4
  • 3
  • 5
  • 6

NEC Reference: NEC 310.15(B)(3)(a)

Question 27: Panelboards must be mounted in which of the following?

  • Cutout boxes
  • Cabinets
  • All of these
  • Enclosures designed for the purpose

NEC Reference: NEC 408.38

Question 28: A cable clamp inside a device box counts for how many conductor volumes in the box fill calculation?

  • Zero — clamps are part of the box hardware and are ignored
  • One conductor volume for all clamps combined
  • One conductor volume per clamp
  • Two conductor volumes regardless of clamp size

NEC Reference: NEC 314.16(B)(2)

Question 29: A 4800-watt fixed electric space heater is connected to a 240-volt, single-phase, 2-wire circuit. What is the minimum size copper conductor for the branch circuit?

  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG

NEC Reference: NEC 424.3(B)

Question 30: A 277/480V, 3-phase, 4-wire wye service in a commercial building is rated at 2000A. Per 230.95, does this service require ground-fault protection of equipment (GFP)?

  • No — GFP is only required on services above 2500A
  • Yes — voltage to ground exceeds 150V and the service rating is 1000A or more
  • No — 277/480V systems are exempt from the GFP requirement
  • Yes — GFP is required on all commercial services regardless of voltage

NEC Reference: NEC 230.95

Question 31: What is the corrected ampacity of 2/0 copper THWN-2 in a dry location where the ambient temperature is 45°C?

  • 170 Amperes
  • 188 Amperes
  • 139 Amperes
  • 160 Amperes

NEC Reference: NEC 310.16

Question 32: Multiwire branch circuits are not permitted in Class I, Division 1 locations.

  • True
  • False

NEC Reference: NEC 501.40

Question 33: A motor nameplate shows FLA = 40A and service factor = 1.15. What is the highest trip setting allowed on the overload relay?

  • 40 A (match the FLA exactly)
  • 46 A (115% of FLA)
  • 50 A (125% of FLA)
  • 56 A (140% of FLA)

NEC Reference: NEC 430.32(A)(1)

Question 34: For a 400A service with 600 kcmil copper conductors, what is the minimum GEC size per Table 250.66?

  • 1/0 AWG copper
  • 4 AWG copper
  • 2 AWG copper
  • 3/0 AWG copper

NEC Reference: NEC Table 250.66

Question 35: When one or more equipment grounding conductors or bonding jumpers enter a box, how many conductors are counted for box fill?

  • A single conductor
  • Two conductors
  • One for each grounding conductor
  • Zero

NEC Reference: NEC 314.16(B)(5)

Question 36: What is the minimum size of copper THWN conductors for a single-phase 10 HP motor on a 240-volt supply, with 75°C terminals?

  • 4 AWG THWN Copper
  • 6 AWG THWN Copper
  • 8 AWG THWN Copper
  • 10 AWG THWN Copper

NEC Reference: NEC 430.248

Question 37: Threaded conduit in hazardous locations must be made ____ to prevent sparking when fault current flows through it.

  • Sealed
  • Bonded
  • Wrenchtight
  • Rugged plastic

NEC Reference: NEC 500.8(E)

Question 38: A mechanical contractor wants to run a water supply pipe through the dedicated electrical space directly above a 200A panelboard. Is this permitted?

  • Yes — water pipe above the panel is fine as long as it does not drip
  • No — foreign systems including pipes are not permitted in the dedicated electrical space
  • Yes — but a drip shield must be installed above the panel
  • Yes — the pipe is permitted if it runs parallel to the panel, not over it

NEC Reference: NEC 110.26(F)(1)(b)

Question 39: If the replacement compressor motor draws 35 amperes current, what is the minimum rating for disconnecting means used to protect the motor?

  • 40.25 amperes
  • 42 amperes
  • 38.5 amperes
  • 43.75 amperes

NEC Reference: NEC 440.12(A)(1)

Question 40: What is the maximum length of a 120-volt flexible cord supplying a room air conditioner?

  • 10 ft
  • 6 ft
  • 8 ft
  • 9 ft

NEC Reference: NEC 440.64

Question 41: Which of the following is NOT a standard overcurrent device size listed in 240.6(A)?

  • 45A
  • 55A
  • 110A
  • 175A

NEC Reference: NEC 240.6(A)

Question 42: What is the minimum ampere rating of the short-circuit and ground-fault protective device permitted for an individual motor-compressor?

  • 10 A
  • 15 A
  • 20 A
  • 25 A

NEC Reference: NEC 440.22(A)

Question 43: A 2/0 copper THWN-2 conductor is in a dry location where the ambient temperature is 45°C. What is its corrected ampacity (90°C column)?

  • 170 Amperes
  • 160 Amperes
  • 165 Amperes
  • 175 Amperes

NEC Reference: NEC 310.16

Question 44: Each grounded conductor must terminate within the panelboard in an individual terminal.

  • True
  • False

NEC Reference: NEC 408.41

Question 45: The recreational park is having fifteen 20 A supply facilities, ten 20A and 30 A supply facilities and twenty five 50A supply facilities is operated at 120/240 V single phase. What is the service demand load for the recreational park?

  • 480 A
  • 533 A
  • 686 A
  • 564 A

NEC Reference: NEC 551.73(A)

Question 46: What is the minimum load for a household electric clothes dryer in a dwelling unit?

  • 5,000 volt-amperes
  • 1,500 volt-amperes
  • 3,000 volt-amperes
  • 4,000 volt-amperes

NEC Reference: NEC 220.54

Question 47: The mobile home park which has 25 site facilities is fed from a 240 V service feeder. What is the demand load for mobile home park?

  • 400 A
  • 450 A
  • 500 A
  • 380 A

NEC Reference: NEC 550.31

Question 48: Before any adjustment or correction factors, branch-circuit conductors must have an ampacity of not less than:

  • Continuous load plus non-continuous load
  • Continuous load plus 125 % of non-continuous load
  • 125% of Continuous load plus non-continuous load
  • 125% of Continuous load

NEC Reference: NEC 210.19(A)(1)

Question 49: What is the general lighting load (in volt-amperes per square foot) used for a single-family dwelling when doing a standard load calculation?

  • 1.5 VA/sq ft
  • 2 VA/sq ft
  • 3 VA/sq ft
  • 3.5 VA/sq ft

NEC Reference: NEC 220.41

Question 50: If a 20 ampere AC snap switch is used to disconnect a 1.5 HP motor what must be the maximum full load current of a motor?

  • 16 amperes
  • 20 amperes
  • 15 amperes
  • 17 amperes

NEC Reference: NEC 430.109(C)(2)

Question 51: How many number of 500 kcmil THWN conductors that can be installed in a 4 in. * 4 in. wireway?

  • 4 conductors
  • 5 conductors
  • 6 conductors
  • 7 conductors

NEC Reference: NEC 376.22(A)

Question 52: The laundry branch circuit required in a dwelling must be a 30-ampere circuit with no other outlets.

  • True
  • False

NEC Reference: NEC 210.11(C)(2)

Question 53: A transformer secondary supplying impedance heating elements is GFCI protected. What is the maximum secondary voltage?

  • 30 volts
  • 80 volts
  • 50 volts
  • 60 volts

NEC Reference: NEC 426.32, 427.27

Question 54: Type UF cable is rated for underground and wet locations. Can it also be used for interior branch circuit wiring inside a building?

  • No — Type UF is only approved for underground use
  • Yes — it can be used for interior branch circuits where NM cable is allowed
  • Yes — but only in wet or damp interior locations
  • No — Type UF requires conduit protection when installed indoors

NEC Reference: NEC 340.10(B)(4)

Question 55: A breaker is used to switch fluorescent lighting on and off many times a day. What special rating must this breaker have?

  • The breaker must be rated GFCI
  • The breaker must be rated SWD (switching duty) or HID
  • Any standard breaker is acceptable for lighting
  • The breaker must be rated for continuous operation

NEC Reference: NEC 240.83(D)

Question 56: The total general lighting connected load of a dwelling unit is 11,000 VA. What is the demand load?

  • 5,800 VA
  • 11,000 VA
  • 9,000 VA
  • 3,150 VA

NEC Reference: NEC Table 220.45

Question 57: What is the maximum overall length of the power supply cord for mobile homes?

  • 36 1/2 feet
  • 21 feet
  • 28 1/2 feet
  • 20 feet

NEC Reference: NEC 550.10(D)

Question 58: The secondary circuits of Article 411 low-voltage lighting systems must not be grounded.

  • True
  • False

NEC Reference: NEC 411.6

Question 59: 210.20(A) requires branch-circuit OCPD at not less than 125% of continuous load + 100% of non-continuous, except where:

  • The breaker and enclosure are listed for 100% continuous operation
  • The load is below 16A
  • The branch circuit is GFCI protected
  • No exception applies

NEC Reference: NEC 210.20(A) Exception

Question 60: Field-installed secondary wiring for electric signs of 1000 volts or less must use conductors not smaller than:

  • 18 AWG
  • 16 AWG
  • 14 AWG
  • 12 AWG

NEC Reference: NEC 600.31

Question 61: What is the minimum size copper EGC for a circuit protected by a 200A overcurrent device?

  • 10 AWG copper
  • 8 AWG copper
  • 6 AWG copper
  • 4 AWG copper

NEC Reference: NEC Table 250.122

Question 62: FMC must be supported and secured at intervals not exceeding:

  • 3½ feet
  • 4½ feet
  • 5½ feet
  • 6½ feet

NEC Reference: NEC 348.30(A)

Question 63: To qualify as a concrete-encased grounding electrode, a rebar or conductor encased in concrete must be at least how long?

  • 8 feet
  • 10 feet
  • 20 feet
  • 30 feet

NEC Reference: NEC 250.52(A)(3)

Question 64: What is the smallest grounding electrode conductor (GEC) for an electric service using a 1200 kcmil copper ungrounded service conductor?

  • 2/0 copper
  • 3/0 copper
  • 1/0 copper
  • 4 AWG copper

NEC Reference: NEC Table 250.66

Question 65: The interior metal water piping system must be bonded to the electrical service. Where must this bond be made, and what size conductor is required?

  • At any accessible point, sized by Table 310.16
  • At or near the service, sized by Table 250.102(C)(1) based on service conductor size
  • At every metal fixture, using 14 AWG minimum
  • Only at the water heater, using 6 AWG minimum

NEC Reference: NEC 250.104(A)

Question 66: A Maryland commercial building has a feeder tap 20 feet long inside a large single-story warehouse. Per 240.21(B)(2), what is one condition of the 25-foot tap rule?

  • The tap conductor ampacity must be at least one-third the ampacity of the feeder overcurrent device
  • The tap can be any size regardless of the feeder rating
  • Taps over 10 feet are never permitted under any rule
  • The tap must always match the feeder conductor size exactly

NEC Reference: NEC 240.21(B)(2)

Question 67: Table 220.45 applies a 100 percent demand factor to what portion of a dwelling general lighting load?

  • The first 3,000 VA
  • Everything above 120,000 VA
  • Only the kitchen portion of the load
  • The entire load, no matter the size

NEC Reference: NEC Table 220.45

Question 68: A Colorado contractor calculates conduit fill for three 10 AWG THHN conductors in an EMT raceway. Per Chapter 9, Table 1, what percent fill applies for three or more conductors?

  • 31 percent
  • 40 percent
  • 53 percent
  • 60 percent

NEC Reference: NEC Ch. 9, Table 1

Question 69: A panelboard has multiple branch circuits sharing a common neutral (multiwire branch circuit) supplying receptacles in different rooms. Per 210.4(B), what device requirement applies?

  • A means to simultaneously disconnect all ungrounded conductors at the panelboard
  • No special disconnect means is required
  • Each conductor must have its own separate panelboard
  • Multiwire branch circuits are prohibited entirely

NEC Reference: NEC 210.4(B)

Question 70: A Washington homeowner installs a 22 kW standby generator at a one-family dwelling. Per 445.18(C), what emergency shutdown means is required?

  • A remote emergency stop switch outside the dwelling at a readily accessible location
  • No shutdown means is required for any generator
  • A stop switch that must be kept inside a locked shed
  • Only the utility may shut down a standby generator

NEC Reference: NEC 445.18(C)

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
WHY GO PRO

Full-Length Pro for Maryland

You just practiced on one full-length, Maryland-style exam built to mirror the real licensing test — timing, weighting, and difficulty included.

14 More Maryland Exams15 in total, 1 free + 14 Pro
Full Topic ReportEvery attempt, topic-by-topic
Answer ReviewEvery explanation and NEC reference

$19 once for Maryland · pay once, keep forever

Unlock 14 more Maryland exams — $19
EXAM CARD JOURNEYMAN FREE
Questions70
Time limit240 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)
About This Exam

70 questions, 240 min, 70% to pass — sized and paced like the Maryland licensing exam. Finish it to see your score and your 3 weakest topics, free.

Open book: the real Maryland exam lets you use the NEC. Keep your code book next to you and practise looking things up.

About the Maryland electrician exam


Full-Length Pro · Maryland
  • 15 Maryland exams: 1 free + 14 Pro
  • Full topic report on every attempt
  • Answer review with explanations + NEC references
  • Unlimited retakes

$19 once for Maryland only · pay once, keep forever

Unlock 14 more Maryland exams — $19