NEC 2026 Code Questions Practice Test 9

Free NEC 2026 practice test with 30 questions on Chapters 4, 5 and 6: hazardous (classified) locations, fuel dispensing, health care facilities, temporary wiring, swimming pools, spas and hydromassage tubs, signs, luminaires in closets and bathrooms, appliances and fixed electric heat.

Share this test
Want the real exam format? Take a free full-length exam for your state
TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Before You Start

  • 30 questions, multiple choice
  • 45 minutes, pass mark 70%
  • Main articles: 410, 422, 424, 500-514, 517, 590, 600 and 680

Tip: Pool questions love distances: 6 ft for receptacles, 20 ft for GFCI, 12 ft for luminaires over water, 3 ft for the bonding grid, 5 ft for the equipment disconnect.

30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2026
NEC 2026 Code Questions Practice Test 9
Q1 / 30
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
Rate it and add a quick comment. No sign-up.
Tap one to send it now:
Share your score
Share it and get the NEC 2026 Article Quick Reference free, right now.
Unlocked — thanks for sharing! 🎉
Get the NEC 2026 Article Quick Reference
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Code Questions Practice Test 9 — Question List

Question 1: Per NEC 500.5, a Class I location is one where:

  • Easily ignitible fibers or flyings are handled, stored or processed
  • Flammable gases or vapors may be present in amounts that can ignite or explode
  • Combustible dust is present in the air in quantities that could ignite
  • Only water vapor or steam is present in the air around the equipment

NEC Reference: NEC 2026 — 500.5

Question 2: Per NEC 500.5, a Class II location involves:

  • Flammable gases
  • Combustible dust
  • Ignitible fibers and flyings
  • Explosive solids

NEC Reference: NEC 2026 — 500.5

Question 3: Per NEC 500.5, a "Division 1" location is one where the hazardous material:

  • Is present only during maintenance shutdowns
  • Is never present
  • Is present only under abnormal conditions
  • Is likely to exist under normal operating conditions

NEC Reference: NEC 2026 — 500.5

Question 4: Per NEC 501.15(A)(1), in a Class I, Division 1 location, a conduit seal is required in each conduit entry into an explosionproof enclosure containing arcing devices, located within how far of the enclosure?

  • 36 inches
  • 18 inches
  • 24 inches
  • 12 inches

NEC Reference: NEC 2026 — 501.15(A)(1)

Question 5: Per NEC 501.15(C)(6), the cross-sectional area of the conductors in a conduit seal fitting must not exceed what percentage of the area of rigid metal conduit of the same trade size (unless the seal is identified for a higher fill)?

  • 25%
  • 53%
  • 40%
  • 31%

NEC Reference: NEC 2026 — 501.15(C)(6)

Question 6: Per NEC Table 514.3(B)(1), the area within 18 inches horizontally in all directions from the dispenser enclosure at a motor fuel dispensing facility, extending to grade, is classified as:

  • Class II, Division 1
  • Class I, Division 2
  • Unclassified
  • Class I, Division 1

NEC Reference: NEC 2026 — Table 514.3(B)(1)

Question 7: Per NEC 511.3, in a major repair garage where gasoline-powered vehicles are repaired and mechanical ventilation is not provided, the area up to how high above the floor is classified as Class I, Division 2?

  • 4 feet
  • 3 feet
  • 18 inches
  • 12 inches

NEC Reference: NEC 2026 — 511.3

Question 8: Per NEC 517.13, in patient care spaces of health care facilities, branch circuits serving patient care areas must have an equipment grounding path provided by:

  • An insulated copper equipment grounding conductor only, with any wiring method
  • Both a metal raceway or cable armor that qualifies as an EGC and an insulated copper equipment grounding conductor
  • A metal raceway only, with no wire-type grounding conductor needed
  • The building steel, bonded to each receptacle box

NEC Reference: NEC 2026 — 517.13

Question 9: Per NEC 517.18(B), each patient bed location in a general care (Category 2) space must have at least how many receptacles?

  • 4
  • 8
  • 14
  • 6

NEC Reference: NEC 2026 — 517.18(B)

Question 10: Per NEC 517.19(B), each patient bed location in a critical care (Category 1) space must have at least how many receptacles?

  • 10
  • 14
  • 12
  • 8

NEC Reference: NEC 2026 — 517.19(B)

Question 11: Per NEC 590.6(A)(1), temporary wiring receptacles that are not part of the permanent wiring (125-volt, single-phase, 15-, 20- and 30-ampere) must have:

  • GFCI protection for personnel
  • A surge protector
  • Weather-resistant covers only
  • AFCI protection

NEC Reference: NEC 2026 — 590.6(A)(1)

Question 12: Per NEC 590.3(B), temporary electric power and lighting for holiday decorative lighting is permitted for a period not exceeding:

  • 30 days
  • 90 days
  • 1 year
  • 6 months

NEC Reference: NEC 2026 — 590.3(B)

Question 13: Per NEC 600.5(A), each commercial building and occupancy accessible to pedestrians must have at least one outlet for sign or outline lighting, supplied by a branch circuit rated at least:

  • 30 amperes
  • 20 amperes that supplies no other load
  • 15 amperes
  • 20 amperes that also supplies the storefront receptacles

NEC Reference: NEC 2026 — 600.5(A)

Question 14: Per NEC 600.6, each sign or outline lighting system must have a disconnecting means that:

  • Is located within sight of the sign, or is lockable in the open position if out of sight
  • Is located inside the sign only
  • Is a GFCI receptacle
  • Is the branch-circuit breaker in all cases

NEC Reference: NEC 2026 — 600.6

Question 15: Per NEC 410.16(C), in a clothes closet, surface-mounted incandescent or LED luminaires with a completely enclosed light source must have a clearance from the storage space of at least:

  • 18 inches
  • 6 inches
  • 3 inches
  • 12 inches

NEC Reference: NEC 2026 — 410.16(C)

Question 16: Per NEC 410.10(D), no parts of cord-connected luminaires, chain-, cable- or cord-suspended luminaires, lighting track, pendants or ceiling-suspended fans may be located within a zone measured 3 feet horizontally and how far vertically from the top of a bathtub rim or shower threshold?

  • 6½ feet
  • 6 feet
  • 8 feet
  • 10 feet

NEC Reference: NEC 2026 — 410.10(D)

Question 17: Per NEC 410.116(B), a recessed luminaire that is not identified for contact with insulation (not Type IC) must have thermal insulation kept at least how far away from the luminaire?

  • 1/2 inch
  • 12 inches
  • 3 inches
  • 6 inches

NEC Reference: NEC 2026 — 410.116(B)

Question 18: Per NEC 422.16(B)(2), the cord for a built-in dishwasher must be not less than 3 feet and not more than how long, measured from the face of the attachment plug to the plane of the rear of the appliance?

  • 6 feet
  • 4 feet
  • 10 feet
  • 6½ feet

NEC Reference: NEC 2026 — 422.16(B)(2)

Question 19: Per NEC 422.13, a fixed storage-type water heater with a capacity of 120 gallons or less is considered a continuous load, so the branch circuit must be rated at least:

  • 125% of the water heater's nameplate rating
  • 80% of the nameplate rating
  • 150% of the nameplate rating
  • 100% of the nameplate rating

NEC Reference: NEC 2026 — 422.13

Question 20: Per NEC 422.31(B), a permanently connected appliance rated over 300 VA or 1/8 hp may use the branch-circuit breaker as its disconnect if the breaker is:

  • A GFCI breaker located anywhere in the dwelling
  • Within sight from the appliance, or lockable in the open position
  • Any breaker in the building, as long as it is labeled
  • Rated 15 amperes, regardless of where it is located

NEC Reference: NEC 2026 — 422.31(B)

Question 21: Per NEC 424.4(B), fixed electric space-heating equipment is considered a continuous load, so its branch-circuit conductors and overcurrent devices must be sized at not less than:

  • 100% of the heater load
  • 150% of the heater load
  • 125% of the total load of the heaters
  • 115% of the heater load

NEC Reference: NEC 2026 — 424.4(B)

Question 22: Per NEC 424.9, permanently installed electric baseboard heaters with factory-installed receptacle outlets (or listed receptacle sections) may be used:

  • As the required receptacle outlet for the wall space they occupy, but the receptacles must not be connected to the heater circuit
  • To supply cord-connected equipment that sits directly above the heater
  • Only in bathrooms, where they replace the required basin receptacle
  • On the same branch circuit as the heater, sharing its overcurrent device

NEC Reference: NEC 2026 — 424.9

Question 23: Per NEC 680.22(A)(2), a receptacle supplying a pool pump motor must be located at least how far from the inside walls of the pool?

  • 10 feet, no GFCI
  • 20 feet
  • 6 feet, with GFCI protection
  • 3 feet, with GFCI

NEC Reference: NEC 2026 — 680.22(A)(2)

Question 24: Per NEC 680.22(A)(4), all 15- and 20-ampere, 125-volt through 250-volt receptacles within how far of the inside walls of a pool must be GFCI protected?

  • 20 feet
  • 10 feet
  • 6 feet
  • 15 feet

NEC Reference: NEC 2026 — 680.22(A)(4)

Question 25: Per NEC 680.22(A)(1), at a dwelling unit with a permanently installed pool, at least one 125-volt, 15- or 20-ampere receptacle must be located not less than 6 feet and not more than how far from the inside wall of the pool?

  • 20 feet
  • 10 feet
  • 25 feet
  • 15 feet

NEC Reference: NEC 2026 — 680.22(A)(1)

Question 26: Per NEC 680.22(B)(1), new outdoor luminaires installed above a pool must be at least how high above the maximum water level?

  • 12 feet
  • 8 feet
  • 10 feet
  • 14 feet

NEC Reference: NEC 2026 — 680.22(B)(1)

Question 27: Per NEC 680.26(B)(2), the perimeter equipotential bonding for a pool must extend at least how far horizontally beyond the inside walls of the pool?

  • 5 feet
  • 6 feet
  • 18 inches
  • 3 feet

NEC Reference: NEC 2026 — 680.26(B)(2)

Question 28: Per NEC 680.26(B), the minimum size of the solid copper conductor used for pool equipotential bonding is:

  • 8 AWG
  • 10 AWG
  • 6 AWG
  • 4 AWG

NEC Reference: NEC 2026 — 680.26(B)

Question 29: Per NEC Article 680, a maintenance disconnecting means for pool, spa and hot tub equipment (other than lighting) must be readily accessible, within sight, and located at least how far horizontally from the inside walls (unless separated by a barrier)?

  • 6 feet
  • 3 feet
  • 5 feet
  • 10 feet

NEC Reference: NEC 2026 — 680.13

Question 30: Per NEC 680.71, hydromassage bathtubs and their associated electrical components must be on:

  • Any 15-ampere circuit
  • An individual branch circuit with a readily accessible GFCI
  • A shared bathroom receptacle circuit
  • An AFCI-only circuit

NEC Reference: NEC 2026 — 680.71

EXAM CARD NEC_PRACTICE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2026
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)