NEC 2020 Code Questions Practice Test 1

Free NEC 2020 practice test with 30 questions covering GFCI and AFCI protection, grounding electrode conductor sizing, box fill calculations, tamper-resistant receptacles, motor overload protection, and service mast requirements. Every question includes an NEC 2020 code reference and a full explanation.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 46 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

How to Use This Practice Test

This NEC 2020 Code Questions Practice Test 1 has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Mixed-format test — questions jump between topics just like the real exam. Don't spend more than 90 seconds on any one question.

  • Topics covered: All NEC chapters — branch circuits, grounding, conductors, wiring methods, motors, and more.
  • Passing score: Aim for 80%+ consistently before scheduling your exam.
  • Questions: 30 multiple-choice, one correct answer each
46
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2020
NEC 2020 Code Questions Practice Test 1
Q1 / 46
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2020 Code Questions Practice Test 1 — Question List

Question 1: A 2/0 THWN conductor is placed in a dry location where the ambient temperature is 45<sup>0</sup>C. What is corrected ampacity of the conductor?

  • 170 Amperes
  • 160 Amperes
  • 165 Amperes
  • 175 Amperes

NEC Reference: NEC 310.15(B)(16)

Question 2: Which of the following locations Type AC cable cannot be used?

  • Dry Location
  • Wet Location
  • Cable Trays
  • Branch circuits for exposed work

Question 3: When a single generator is used to supply emergency load plus other loads, a single transfer switch can be sufficient to use.

  • True
  • False

NEC Reference: NEC 700.5(D)

Question 4: Mutli-wire branch circuits shall be permitted in class I division I locations.

  • True
  • False

NEC Reference: NEC 501.40

Question 5: Proper Grounding in electrical circuit limits ................. and protects the circuit.

  • high voltage
  • high current
  • high power

Question 6: The branch circuits that are connected to luminaries of dwelling units shall have maximum voltage of ..................

  • 120 volts
  • 240 volts
  • 208 volts
  • 480 volts

NEC Reference: NEC 210.6

Question 7: The ampacity of the branch conductor that supplies a power supply to the motor which has FLC of 25 amperes is ...............

  • 32 amperers
  • 25 amperes
  • 28 amperes
  • 30 amperes

NEC Reference: NEC 430.22(A)

Question 8: Branch circuits and feeders to motor controllers, driving machines shall not exceed of…….. volts

  • 600 volts
  • 480 volts
  • 240 volts
  • 120 volts

NEC Reference: NEC 620.3(A)

Question 9: What is the maximum ampere rating of a power supply feeder of mobile homes?

  • 25 amperes
  • 50 amperes
  • 75 amperes
  • 45 amperes

NEC Reference: NEC 550.10

Question 10: Dispensing devices for liquefied petroleum gas shall be located not less than …………….. feet from any dispensing device for Class I liquids

  • 5 feet
  • 10 feet
  • 8 feet
  • 4 feet

NEC Reference: NEC 514.3(B)(2)

Question 11: 125 volt, 15 and 20 ampere receptacles that serve dwelling unit kitchen countertop surfaces require:

  • No protection is required
  • GFCI protection
  • AFCI protection only
  • A dedicated 50 ampere circuit

NEC Reference: NEC 210.8(A)(6)

Question 12: 125 volt, 15 and 20 ampere receptacles that serve dwelling unit kitchen countertop surfaces require:

  • No protection is required
  • GFCI protection
  • AFCI protection only
  • A dedicated 50 ampere circuit

NEC Reference: NEC 210.8(A)(6)

Question 13: AFCI protection is required for 120 volt, 15 and 20 ampere branch circuits supplying outlets in which areas of a dwelling unit?

  • Bathrooms only
  • Garages only
  • Essentially all areas of the dwelling unit
  • Only circuits over 20 amperes

NEC Reference: NEC 210.12(A)

Question 14: AFCI protection is required for 120 volt, 15 and 20 ampere branch circuits supplying outlets in which areas of a dwelling unit?

  • Bathrooms only
  • Garages only
  • Essentially all areas of the dwelling unit
  • Only circuits over 20 amperes

NEC Reference: NEC 210.12(A)

Question 15: For box fill calculations, a single switch or receptacle mounted on one strap counts as how many conductors?

  • Zero
  • One
  • Two
  • Three

NEC Reference: NEC 314.16(B)(4)

Question 16: For box fill calculations, a single switch or receptacle mounted on one strap counts as how many conductors?

  • Zero
  • One
  • Two
  • Three

NEC Reference: NEC 314.16(B)(4)

Question 17: Under NEC Table 110.26(A)(1), Condition 2 (exposed live parts on one side and grounded parts on the other) at 0-150 volts to ground requires a minimum working space depth of:

  • 2 feet
  • 3 feet
  • 4 feet
  • 5 feet

NEC Reference: NEC 110.26(A)(1)

Question 18: Under NEC Table 110.26(A)(1), Condition 2 (exposed live parts on one side and grounded parts on the other) at 0-150 volts to ground requires a minimum working space depth of:

  • 2 feet
  • 3 feet
  • 4 feet
  • 5 feet

NEC Reference: NEC 110.26(A)(1)

Question 19: A service is supplied by 2 AWG copper ungrounded conductors. What is the minimum size copper grounding electrode conductor required?

  • 10 AWG
  • 8 AWG
  • 6 AWG
  • 4 AWG

NEC Reference: NEC 250.66

Question 20: A service is supplied by 2 AWG copper ungrounded conductors. What is the minimum size copper grounding electrode conductor required?

  • 10 AWG
  • 8 AWG
  • 6 AWG
  • 4 AWG

NEC Reference: NEC 250.66

Question 21: A branch circuit is protected by a 60 ampere overcurrent device. What is the minimum size copper equipment grounding conductor required?

  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG

NEC Reference: NEC 250.122

Question 22: A branch circuit is protected by a 60 ampere overcurrent device. What is the minimum size copper equipment grounding conductor required?

  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG

NEC Reference: NEC 250.122

Question 23: In dwelling unit habitable rooms, receptacles must be placed so that no point along the floor line is more than how far from a receptacle outlet?

  • 4 feet
  • 6 feet
  • 8 feet
  • 10 feet

NEC Reference: NEC 210.52(A)(1)

Question 24: In dwelling unit habitable rooms, receptacles must be placed so that no point along the floor line is more than how far from a receptacle outlet?

  • 4 feet
  • 6 feet
  • 8 feet
  • 10 feet

NEC Reference: NEC 210.52(A)(1)

Question 25: Tamper-resistant receptacles are required in which areas of a dwelling unit?

  • Only rooms where small children regularly stay
  • Essentially all dwelling unit receptacles
  • Only outdoor receptacles
  • Only garage receptacles

NEC Reference: NEC 406.12

Question 26: Tamper-resistant receptacles are required in which areas of a dwelling unit?

  • Only rooms where small children regularly stay
  • Essentially all dwelling unit receptacles
  • Only outdoor receptacles
  • Only garage receptacles

NEC Reference: NEC 406.12

Question 27: A single raceway contains 4/0 AWG copper service-entrance conductors. What size copper supply-side bonding jumper is required?

  • 4 AWG
  • 2 AWG
  • 1/0 AWG
  • 3/0 AWG

NEC Reference: NEC 250.102(C)

Question 28: A single raceway contains 4/0 AWG copper service-entrance conductors. What size copper supply-side bonding jumper is required?

  • 4 AWG
  • 2 AWG
  • 1/0 AWG
  • 3/0 AWG

NEC Reference: NEC 250.102(C)

Question 29: A lighting and appliance branch-circuit panelboard must be protected by an overcurrent device with a rating not greater than the panelboard rating, except where the panelboard is rated:

  • 200 amperes or more
  • 400 amperes or more
  • 100 amperes or more
  • 600 amperes or more

NEC Reference: NEC 408.36

Question 30: A lighting and appliance branch-circuit panelboard must be protected by an overcurrent device with a rating not greater than the panelboard rating, except where the panelboard is rated:

  • 200 amperes or more
  • 400 amperes or more
  • 100 amperes or more
  • 600 amperes or more

NEC Reference: NEC 408.36

Question 31: Where a service mast is used for the support of service-drop conductors, it must be of adequate strength or supported by which method?

  • It never needs additional support
  • Adequate strength or braces/guy wires
  • A separate structure must always be built
  • It must be buried below grade

NEC Reference: NEC 230.28

Question 32: Where a service mast is used for the support of service-drop conductors, it must be of adequate strength or supported by which method?

  • It never needs additional support
  • Adequate strength or braces/guy wires
  • A separate structure must always be built
  • It must be buried below grade

NEC Reference: NEC 230.28

Question 33: Direct-buried service conductors not encased in concrete, under a residential driveway, generally require a minimum burial depth of:

  • 6 inches
  • 12 inches
  • 24 inches
  • 36 inches

NEC Reference: NEC 300.5

Question 34: Direct-buried service conductors not encased in concrete, under a residential driveway, generally require a minimum burial depth of:

  • 6 inches
  • 12 inches
  • 24 inches
  • 36 inches

NEC Reference: NEC 300.5

Question 35: A continuous-duty motor with a marked service factor of 1.15 or greater requires overload protection sized at not more than what percentage of the motor nameplate full-load current?

  • 100 %
  • 115 %
  • 125 %
  • 150 %

NEC Reference: NEC 430.32(A)(1)

Question 36: A continuous-duty motor with a marked service factor of 1.15 or greater requires overload protection sized at not more than what percentage of the motor nameplate full-load current?

  • 100 %
  • 115 %
  • 125 %
  • 150 %

NEC Reference: NEC 430.32(A)(1)

Question 37: Under the 25-foot transformer secondary conductor tap rule, the secondary conductors must terminate in a single overcurrent device rated no more than the conductor ampacity, and the conductors must be protected from physical damage. What is the maximum length permitted for these secondary conductors?

  • 10 feet
  • 15 feet
  • 25 feet
  • 50 feet

NEC Reference: NEC 240.21(C)(6)

Question 38: Under the 25-foot transformer secondary conductor tap rule, the secondary conductors must terminate in a single overcurrent device rated no more than the conductor ampacity, and the conductors must be protected from physical damage. What is the maximum length permitted for these secondary conductors?

  • 10 feet
  • 15 feet
  • 25 feet
  • 50 feet

NEC Reference: NEC 240.21(C)(6)

Question 39: What is the purpose of the equipotential bonding grid required around a permanently installed swimming pool?

  • To reduce voltage gradients around the pool
  • To increase the pool water pH
  • To provide a path for lightning to ground only
  • It has no safety function, only structural

NEC Reference: NEC 680.26(B)

Question 40: What is the purpose of the equipotential bonding grid required around a permanently installed swimming pool?

  • To reduce voltage gradients around the pool
  • To increase the pool water pH
  • To provide a path for lightning to ground only
  • It has no safety function, only structural

NEC Reference: NEC 680.26(B)

Question 41: Emergency power systems must be tested periodically to ensure the system is functioning correctly. Who is generally responsible for this periodic testing and maintenance?

NEC Reference: NEC 700.3

Question 42: Emergency power systems must be tested periodically to ensure the system is functioning correctly. Who is generally responsible for this periodic testing and maintenance?

  • The premises owner
  • The local fire department only
  • The utility company
  • No periodic testing is required

NEC Reference: NEC 700.3

Question 43: A 15 or 20 ampere, 125 or 250 volt receptacle installed outdoors in a wet location must be provided with an enclosure that is weatherproof:

  • Only while no plug is inserted
  • Whether or not a plug is inserted
  • Only during rain
  • A weatherproof cover is never required outdoors

NEC Reference: NEC 406.9(B)(1)

Question 44: When 4 or more conductors are installed in a single raceway, the maximum fill permitted is what percentage of the raceway cross-sectional area?

  • 31 %
  • 40 %
  • 53 %
  • 60 %

NEC Reference: NEC Chapter 9, Table 1

Question 45: A grounded (neutral) conductor 6 AWG or smaller must be identified by which color(s)?

  • Black
  • White or gray
  • Red
  • Green

NEC Reference: NEC 200.6(A)

Question 46: Flexible cords and cables are prohibited from being used as a substitute for which of the following?

  • The fixed wiring of a structure
  • Connecting a portable lamp
  • Connecting a power tool
  • Temporary holiday lighting

NEC Reference: NEC 400.12

EXAM CARD NEC_PRACTICE
Questions46
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)