NEC 2026 Code Questions Practice Test 8

Free NEC 2026 practice test with 30 questions on motors and transformers: using the motor FLC tables, sizing motor conductors, overloads and short-circuit protection, motor disconnects, Article 440 compressor circuits, and Table 450.3(B) transformer protection.

Share this test
Want the real exam format? Take a free full-length exam for your state
TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Before You Start

  • 30 questions, multiple choice
  • 45 minutes, pass mark 70%
  • Main articles: 430 (Tables 430.248, 430.250, 430.52), 440 and 450

Tip: Use the table FLC (not the nameplate) for conductors, short-circuit protection and disconnects. Use the nameplate current only for overloads.

30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2026
NEC 2026 Code Questions Practice Test 8
Q1 / 30
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
Rate it and add a quick comment. No sign-up.
Tap one to send it now:
Share your score
Share it and get the NEC 2026 Article Quick Reference free, right now.
Unlocked — thanks for sharing! 🎉
Get the NEC 2026 Article Quick Reference
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Code Questions Practice Test 8 — Question List

Question 1: Per NEC 430.6(A)(1), when sizing motor branch-circuit conductors, short-circuit protection and disconnects for a general motor, the full-load current used is taken from:

  • The motor nameplate full-load current, because it is the actual value
  • The overload heater selection chart supplied with the starter
  • The FLC tables in Article 430 (Tables 430.247 through 430.250)
  • The locked-rotor current marked on the motor nameplate

NEC Reference: NEC 2026 — 430.6(A)(1)

Question 2: Per NEC Table 430.250, what is the full-load current of a 10 hp, 460-volt, three-phase induction motor?

  • 28 amperes
  • 14 amperes
  • 11 amperes
  • 21 amperes

NEC Reference: NEC 2026 — Table 430.250

Question 3: Per NEC Table 430.250, what is the full-load current of a 25 hp, 460-volt, three-phase motor?

  • 40 amperes
  • 27 amperes
  • 68 amperes
  • 34 amperes

NEC Reference: NEC 2026 — Table 430.250

Question 4: Per NEC Table 430.248, what is the full-load current of a 3 hp, 230-volt, single-phase motor?

  • 17 amperes
  • 34 amperes
  • 28 amperes
  • 12 amperes

NEC Reference: NEC 2026 — Table 430.248

Question 5: Per NEC 430.22, branch-circuit conductors for a single continuous-duty motor must have an ampacity of at least:

  • 150% of the motor FLC
  • 100% of the motor FLC
  • 115% of the motor FLC
  • 125% of the motor full-load current

NEC Reference: NEC 2026 — 430.22

Question 6: A 15 hp, 460-volt, three-phase motor has a table FLC of 21 amperes. Per NEC 430.22, what is the minimum branch-circuit conductor ampacity?

  • 21 amperes
  • 26.25 amperes
  • 24.15 amperes
  • 31.5 amperes

NEC Reference: NEC 2026 — 430.22

Question 7: Per NEC 430.24, conductors supplying several motors must have an ampacity of at least:

  • 125% of the total of all motor FLCs
  • 150% of the largest motor only
  • 125% of the largest motor FLC plus the sum of the other motors' FLCs
  • 100% of the sum of all FLCs

NEC Reference: NEC 2026 — 430.24

Question 8: Three motors with table FLCs of 34 A, 21 A and 14 A are on one feeder. Per NEC 430.24, what is the minimum feeder conductor ampacity?

  • 73.5 amperes
  • 69 amperes
  • 86.25 amperes
  • 77.5 amperes

NEC Reference: NEC 2026 — 430.24

Question 9: Per NEC 430.32(A)(1), overload protection for a motor with a marked service factor of 1.15 or greater must be set at no more than what percentage of the nameplate full-load current?

  • 140%
  • 100%
  • 125%
  • 115%

NEC Reference: NEC 2026 — 430.32(A)(1)

Question 10: Per NEC 430.32(A)(1), a motor with a service factor of 1.0 and no marked temperature rise of 40°C or less must have overload protection at no more than:

  • 100% of the nameplate current
  • 140% of the nameplate current
  • 115% of the nameplate current
  • 125% of the nameplate current

NEC Reference: NEC 2026 — 430.32(A)(1)

Question 11: Per NEC 430.32(C), if the selected overload relay will not allow the motor to start, the overload may be increased to no more than what percentage for a motor with a 1.15 service factor?

  • 140%
  • 150%
  • 130%
  • 125%

NEC Reference: NEC 2026 — 430.32(C)

Question 12: Per NEC Table 430.52, the maximum rating of an inverse-time circuit breaker for motor branch-circuit short-circuit and ground-fault protection (typical AC polyphase motor) is:

  • 300% of FLC
  • 800% of FLC
  • 250% of FLC
  • 175% of FLC

NEC Reference: NEC 2026 — Table 430.52

Question 13: Per NEC Table 430.52, the maximum rating of a dual-element (time-delay) fuse for motor short-circuit protection is:

  • 250% of FLC
  • 125% of FLC
  • 300% of FLC
  • 175% of FLC

NEC Reference: NEC 2026 — Table 430.52

Question 14: A motor has a table FLC of 28 A. Using an inverse-time breaker at 250% per Table 430.52 and the next-size-up rule in 430.52(C)(1) Exception 1, what is the maximum breaker size?

  • 70 amperes
  • 50 amperes
  • 80 amperes
  • 60 amperes

NEC Reference: NEC 2026 — Table 430.52 and 430.52(C)(1) Exception No. 1

Question 15: Per NEC 430.52(C)(1) Exception 2(c), if the motor will not start, an inverse-time breaker for a motor with FLC of 100 amperes or less may be increased to a maximum of:

  • 400% of FLC
  • 250% of FLC
  • 300% of FLC
  • 500% of FLC

NEC Reference: NEC 2026 — 430.52(C)(1)

Question 16: Per NEC 430.62(A), the rating of the feeder overcurrent device for several motors must not be greater than:

  • 125% of the sum of the full-load currents of all motors on the feeder
  • 250% of the full-load current of the largest motor on the feeder
  • The largest branch-circuit short-circuit device rating plus the sum of the FLCs of the other motors
  • The sum of the branch-circuit device ratings of every motor on the feeder

NEC Reference: NEC 2026 — 430.62(A)

Question 17: Per NEC 430.102(B), a motor disconnecting means must be in sight from the motor location and driven machinery, unless:

  • The motor is smaller than 50 horsepower and is controlled by a starter
  • The motor is three-phase and its controller is in the same room
  • The controller disconnect is individually lockable in the open position and the other exception conditions are met
  • The motor is installed outdoors where a disconnect would be damaged

NEC Reference: NEC 2026 — 430.102(B)

Question 18: Per NEC 430.110(A), the disconnecting means for a motor circuit rated 1000 volts or less must have an ampere rating of at least:

  • 125% of the motor FLC
  • 100% of the motor FLC
  • 150% of the motor FLC
  • 115% of the motor full-load current

NEC Reference: NEC 2026 — 430.110(A)

Question 19: Per NEC 430.109(C), for stationary motors of 2 hp or less and 300 volts or less, an AC general-use snap switch may be used as the disconnect if the motor FLC is not more than:

  • 80% of the switch's ampere rating
  • 125% of the switch rating
  • 50% of the switch rating
  • 100% of the switch rating

NEC Reference: NEC 2026 — 430.109(C)

Question 20: Per NEC 430.72(B), motor control circuit conductors that extend beyond the controller enclosure (remote control circuit) must be protected by:

  • An overcurrent device rated per Table 430.72(B), based on the conductor size
  • No protection, because control circuits carry very little current
  • The motor overload relay, which also protects the control wiring
  • A GFCI device installed in the controller enclosure

NEC Reference: NEC 2026 — 430.72(B)

Question 21: Per NEC 440.12(A)(1), the disconnecting means for a hermetic refrigerant motor-compressor must have an ampere rating of at least:

  • 100% of the locked-rotor current marked on the compressor nameplate
  • 115% of the nameplate rated-load current or branch-circuit selection current, whichever is greater
  • 175% of the rated-load current, the same as the short-circuit device
  • 125% of the rated-load current marked on the compressor nameplate

NEC Reference: NEC 2026 — 440.12(A)(1)

Question 22: Per NEC 440.14, the disconnecting means for air-conditioning or refrigerating equipment must be:

  • Installed only inside the building
  • Located on the equipment's access panel
  • Located within 100 feet
  • Located within sight from and readily accessible from the equipment

NEC Reference: NEC 2026 — 440.14

Question 23: Per NEC 440.22(A), the short-circuit and ground-fault protective device for a single motor-compressor generally must not exceed:

  • 250% of the RLC, with the next standard size permitted
  • 300% of the RLC, the same as a nontime-delay fuse for motors
  • 125% of the RLC, the same as the branch-circuit conductors
  • 175% of the RLC or BCSC (may be increased to 225% if needed to start)

NEC Reference: NEC 2026 — 440.22(A)

Question 24: Per NEC 440.32, branch-circuit conductors supplying a single motor-compressor must have an ampacity of at least:

  • 125% of the rated-load current or branch-circuit selection current, whichever is greater
  • 175% of the rated-load current, the same as the OCPD
  • 100% of the rated-load current marked on the nameplate
  • 115% of the rated-load current, the same as the disconnect

NEC Reference: NEC 2026 — 440.32

Question 25: Per NEC Table 450.3(B), for a transformer of 1000 volts or less with primary-only protection and a rated primary current of 9 amperes or more, the primary overcurrent device may be rated at up to:

  • 167%
  • 125% of the rated primary current
  • 250%
  • 300%

NEC Reference: NEC 2026 — Table 450.3(B)

Question 26: A 45 kVA, 480-volt three-phase transformer has a rated primary current of about 54 A. Using primary-only protection at 125% per Table 450.3(B) and the next-size-up note, what is the largest primary breaker?

  • 60 amperes
  • 80 amperes
  • 100 amperes
  • 70 amperes

NEC Reference: NEC 2026 — Table 450.3(B)

Question 27: Per NEC Table 450.3(B), when a transformer has both primary and secondary protection (secondary current 9 amperes or more), the primary device may be up to:

  • 250% of rated primary current, with the secondary device at 125%
  • 167% of the rated primary current, with secondary protection at 100%
  • 300% of the rated primary current, with secondary protection at 167%
  • 125% of the rated primary current, with no secondary protection

NEC Reference: NEC 2026 — Table 450.3(B)

Question 28: Per NEC 450.14, a transformer disconnecting means is required. It must be:

  • Installed on the secondary side only, next to the first panelboard
  • Located inside the transformer enclosure behind the access cover
  • Located within sight of the transformer, or if remote, lockable in the open position with its location marked on the transformer
  • A fused switch only, located at the main service equipment

NEC Reference: NEC 2026 — 450.14

Question 29: Per NEC 450.13(B), dry-type transformers of 1000 volts or less and not over 50 kVA are permitted in hollow spaces of buildings (such as above a lay-in ceiling) if:

  • They are rated at least 600 kVA so they run cooler in the closed space
  • They are not permanently closed in by the structure and meet the ventilation and separation rules
  • They are mounted on the floor above and supported by the ceiling grid
  • They are oil-filled units installed in a sealed metal tray

NEC Reference: NEC 2026 — 450.13(B)

Question 30: Per NEC 450.21(A), dry-type transformers rated 112½ kVA or less installed indoors must have a separation from combustible material of at least:

  • 3 feet, measured from any side of the transformer enclosure
  • 12 inches, unless separated by a fire-resistant, heat-insulated barrier
  • 24 inches, unless the room has automatic sprinklers
  • 6 inches, unless the transformer is mounted on a concrete pad

NEC Reference: NEC 2026 — 450.21(A)