NEC 2026 Code Questions Practice Test 7

Free NEC 2026 practice test with 30 questions on conductors: reading Table 310.16, applying ambient temperature correction and more-than-three-conductor adjustment, counting neutrals, conductor insulation types, parallel conductors, identification, and the Article 400 rules for flexible cords.

Share this test
Want the real exam format? Take a free full-length exam for your state
TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Before You Start

  • 30 questions, multiple choice
  • 45 minutes, pass mark 70%
  • Main articles: 310, 200, 400 (Tables 310.16 and 310.15(C)(1))

Tip: Start derating from the 90°C column when the insulation allows it, but the final answer can never be higher than the termination temperature limit in 110.14(C).

30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2026
NEC 2026 Code Questions Practice Test 7
Q1 / 30
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
Rate it and add a quick comment. No sign-up.
Tap one to send it now:
Share your score
Share it and get the NEC 2026 Article Quick Reference free, right now.
Unlocked — thanks for sharing! 🎉
Get the NEC 2026 Article Quick Reference
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Code Questions Practice Test 7 — Question List

Question 1: Per NEC Table 310.16, what is the ampacity of 8 AWG THWN copper (75°C column)?

  • 50 amperes
  • 55 amperes
  • 45 amperes
  • 40 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 2: Per NEC Table 310.16, what is the ampacity of 6 AWG THWN copper (75°C column)?

  • 65 amperes
  • 60 amperes
  • 75 amperes
  • 55 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 3: Per NEC Table 310.16, what is the ampacity of 3 AWG THWN copper (75°C column)?

  • 100 amperes
  • 85 amperes
  • 95 amperes
  • 115 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 4: Per NEC Table 310.16, what is the ampacity of 4/0 AWG aluminum XHHW at 75°C?

  • 205 amperes
  • 150 amperes
  • 180 amperes
  • 230 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 5: Per NEC Table 310.16, what is the ampacity of 500 kcmil THWN copper at 75°C?

  • 380 amperes
  • 320 amperes
  • 400 amperes
  • 430 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 6: Table 310.16 ampacities are based on an ambient temperature of:

  • 40°C (104°F)
  • 25°C (77°F)
  • 30°C (86°F)
  • 20°C (68°F)

NEC Reference: NEC 2026 — Table 310.16

Question 7: Per the NEC ambient temperature correction table (310.15(B)), a 90°C conductor in an ambient of 40°C (104°F) has a correction factor of:

  • 0.91
  • 0.88
  • 0.82
  • 0.96

NEC Reference: NEC 2026 — Table 310.15(B)(1)(1)

Question 8: Per NEC Table 310.15(C)(1), what adjustment factor applies when a raceway contains 4 to 6 current-carrying conductors?

  • 80%
  • 50%
  • 70%
  • 45%

NEC Reference: NEC 2026 — Table 310.15(C)(1)

Question 9: Per NEC Table 310.15(C)(1), what adjustment factor applies to 9 current-carrying conductors in one raceway?

  • 70%
  • 60%
  • 50%
  • 80%

NEC Reference: NEC 2026 — Table 310.15(C)(1)

Question 10: A raceway has six current-carrying 12 AWG THHN copper conductors in a 30°C ambient. Starting from the 90°C column (30 A), what is the adjusted ampacity?

  • 30 amperes
  • 24 amperes
  • 21 amperes
  • 20 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 11: Per NEC 310.15(E)(1), a neutral conductor that carries only the unbalanced current of other conductors of the same circuit (such as a 120/240 V 3-wire circuit):

  • Counts only if it is larger than the hots
  • Is always counted
  • Is not counted as a current-carrying conductor
  • Counts as two conductors

NEC Reference: NEC 2026 — 310.15(E)(1)

Question 12: Per NEC 310.15(E)(3), on a 4-wire, 3-phase wye circuit where the major portion of the load is nonlinear (such as LED drivers and computers), the neutral:

  • Must be half size
  • Must be removed
  • Is considered a current-carrying conductor
  • Is never counted

NEC Reference: NEC 2026 — 310.15(E)(3)

Question 13: Per NEC 310.15(E)(2), in a 3-wire circuit made of two phase conductors and the neutral of a 4-wire, 3-phase wye system, the neutral:

  • Is never used
  • Is not counted
  • Counts only above 100 amperes
  • Is considered a current-carrying conductor

NEC Reference: NEC 2026 — 310.15(E)(2)

Question 14: Per NEC 310.15(F), equipment grounding and bonding conductors are:

  • Counted only if insulated
  • Not counted when applying the adjustment factors
  • Counted as half a conductor
  • Counted as current-carrying conductors

NEC Reference: NEC 2026 — 310.15(F)

Question 15: Per NEC 310.15(B)(2), raceways or cables exposed to direct sunlight on or above rooftops at a distance of less than 7/8 inch above the roof must have a temperature adder of:

  • No temperature adder is needed
  • 17°C (30°F)
  • 22°C (40°F)
  • 33°C (60°F)

NEC Reference: NEC 2026 — 310.15(B)(2)

Question 16: Per NEC 310.10(G), conductors in parallel are generally permitted for sizes:

  • 250 kcmil and larger
  • 2 AWG and larger
  • 1/0 AWG and larger
  • 4 AWG and larger

NEC Reference: NEC 2026 — 310.10(G)

Question 17: Per NEC 310.10(G)(2), each set of parallel conductors must be:

  • The same length, conductor material, size, insulation type, and terminated in the same manner
  • Cut to different lengths so the current divides evenly between sets
  • Installed in the same raceway only, with no other rules for the conductors
  • Of different sizes on each phase, as long as the total ampacity is correct

NEC Reference: NEC 2026 — 310.10(G)(2)

Question 18: Per NEC 310.3(C), conductors installed in raceways must be stranded when they are size:

  • 6 AWG and larger
  • 8 AWG and larger
  • 10 AWG and larger
  • 4 AWG and larger

NEC Reference: NEC 2026 — 310.3(C)

Question 19: Per NEC 310.3(A), the minimum size of copper conductors for general wiring (600 volts or less) is:

  • 16 AWG
  • 14 AWG
  • 18 AWG
  • 12 AWG

NEC Reference: NEC 2026 — 310.3(A)

Question 20: Per NEC Table 310.4(1), the letter "W" in an insulation type such as THWN indicates the conductor is suitable for:

  • Wire sizes larger than 1/0
  • Use in walls only
  • Wet locations
  • White neutral use

NEC Reference: NEC 2026 — Table 310.4(1)

Question 21: Which insulation type is rated 90°C in both wet and dry locations?

  • THWN-2
  • THW
  • THWN
  • TW

NEC Reference: NEC 2026 — Table 310.16

Question 22: Per NEC 200.6(A), grounded (neutral) conductors 6 AWG or smaller must be identified by:

  • Green tape applied at each end and at every junction box
  • Black insulation with white tape at the panelboard only
  • Any insulation color, as long as a label is placed at the panel
  • A continuous white or gray outer finish, or three continuous white or gray stripes on other than green insulation

NEC Reference: NEC 2026 — 200.6(A)

Question 23: Per NEC 200.6(B), grounded conductors 4 AWG or larger may be identified by:

  • Distinctive white or gray markings at their terminations at the time of installation
  • Green insulation or green tape at each termination
  • A label at the panel, with no marking needed at other terminations
  • Red tape applied at the panelboard end only

NEC Reference: NEC 2026 — 200.6(B)

Question 24: Per NEC 200.7(C)(1), when white wire in a cable is used as an ungrounded conductor for a switch loop, it must be:

  • Cut short at the switch so it cannot be used as a neutral
  • Permanently re-identified (by tape, paint or other effective means) at each location where it is visible and accessible
  • Connected to the neutral bar at the panel like any other white wire
  • Left white, since the cable color code already identifies its use

NEC Reference: NEC 2026 — 200.7(C)(1)

Question 25: Per NEC 400.12, flexible cords and cables must NOT be used:

  • For pendant luminaires
  • For portable appliances
  • As a substitute for the fixed wiring of a structure
  • For connecting a range where permitted

NEC Reference: NEC 2026 — 400.12

Question 26: Per NEC 400.10, which is a permitted use of flexible cord?

  • Connection of portable appliances where frequent interchange is necessary
  • Running through a hole in a wall to another room
  • Concealing above a suspended ceiling
  • Attaching to the building surface as permanent wiring

NEC Reference: NEC 2026 — 400.10

Question 27: Per NEC 400.14, flexible cords must be connected to devices and fittings so that:

  • They are always grounded
  • The insulation is removed for 2 inches
  • They can be pulled out easily
  • Tension is not transmitted to joints or terminals

NEC Reference: NEC 2026 — 400.14

Question 28: Per NEC 400.23, the equipment grounding conductor in a flexible cord must be identified by:

  • White or gray insulation, the same as the grounded conductor
  • Black insulation with a white tracer stripe
  • Green insulation, or green with one or more yellow stripes
  • A raised ridge molded into the outer jacket of the cord

NEC Reference: NEC 2026 — 400.23

Question 29: A 10 AWG THHN copper branch circuit (40 A at 90°C) has 8 current-carrying conductors in a raceway at 30°C. What is the adjusted ampacity?

  • 35 amperes
  • 28 amperes
  • 32 amperes
  • 20 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 30: Per NEC 310.15(C)(1), adjustment factors do not apply to conductors in raceways having a length not exceeding:

  • 12 inches
  • 10 feet
  • 24 inches
  • 36 inches

NEC Reference: NEC 2026 — 310.15(C)(1)

EXAM CARD NEC_PRACTICE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2026
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)