NEC_PRACTICE NEC 2026

NEC 2026 Code Questions Practice Test 6

Free NEC 2026 practice test with 30 questions on wiring methods: protection of cables in framing, Table 300.5 burial depths, raceway and cable support spacing, Chapter 9 conduit fill, Article 314 box fill and pull box sizing.

Share this test
Want the real exam format? Take a free full-length exam for your state
TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Before You Start

  • 30 questions, multiple choice
  • 45 minutes, pass mark 70%
  • Main articles: 300, 314, 334, 344, 352, 358 and Chapter 9

Tip: Box fill volumes: 14 AWG = 2.00 in³, 12 AWG = 2.25 in³, 10 AWG = 2.50 in³. A device counts as two conductors.

30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2026
NEC 2026 Code Questions Practice Test 6
Q1 / 30
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
Rate it and add a quick comment. No sign-up.
Tap one to send it now:
Share your score
Share it and get the NEC 2026 Article Quick Reference free, right now.
Unlocked — thanks for sharing! 🎉
Get the NEC 2026 Article Quick Reference
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Code Questions Practice Test 6 — Question List

Question 1: Per NEC 300.3(B), all conductors of the same circuit, including the neutral and equipment grounding conductors, must generally be:

  • Spaced at least 6 inches apart
  • Contained within the same raceway, cable, trench or cord
  • Run in separate raceways
  • Installed in metal raceway only

NEC Reference: NEC 2026 — 300.3(B)

Question 2: Per NEC 300.4(A)(1), where a cable is run through bored holes in wood framing, the hole edge must be at least how far from the nearest edge of the framing member?

  • 1¼ inches
  • 1½ inches
  • 1 inch
  • 2 inches

NEC Reference: NEC 2026 — 300.4(A)(1)

Question 3: Per NEC 300.4(E), cables and raceways installed under metal-corrugated roof decking must be kept at least how far from the lowest surface of the decking?

  • 2 inches
  • 1 inch
  • 1½ inches
  • 1¼ inches

NEC Reference: NEC 2026 — 300.4(E)

Question 4: Per NEC 300.4(G), where 4 AWG or larger ungrounded conductors enter a cabinet, box or enclosure through a raceway, they must be protected by:

  • A rubber grommet pressed into the knockout opening
  • An identified fitting with a smoothly rounded insulating surface, such as an insulating bushing
  • A standard steel locknut tightened against the enclosure
  • Two layers of electrical tape wrapped around the raceway end

NEC Reference: NEC 2026 — 300.4(G)

Question 5: Per NEC Table 300.5, what is the minimum cover depth for direct-burial cable (such as UF) in a general location not under a building, driveway or slab?

  • 12 inches
  • 6 inches
  • 18 inches
  • 24 inches

NEC Reference: NEC 2026 — Table 300.5

Question 6: Per NEC Table 300.5, what is the minimum cover depth for rigid metal conduit (RMC) in a general location?

  • 24 inches
  • 18 inches
  • 6 inches
  • 12 inches

NEC Reference: NEC 2026 — Table 300.5

Question 7: Per NEC Table 300.5, what is the minimum cover depth for PVC conduit (nonmetallic raceway listed for direct burial without concrete encasement) in a general location?

  • 12 inches
  • 6 inches
  • 18 inches
  • 24 inches

NEC Reference: NEC 2026 — Table 300.5

Question 8: Per NEC Table 300.5, a residential 120-volt, 20-ampere branch circuit with GFCI protection and overcurrent protection of 20 amperes maximum may be buried at a minimum depth of:

  • 24 inches
  • 18 inches
  • 6 inches
  • 12 inches

NEC Reference: NEC 2026 — Table 300.5

Question 9: Per NEC Table 300.5, what is the minimum cover depth for any wiring method under streets, highways, roads, alleys, driveways and parking lots (other than one- and two-family dwelling driveways)?

  • 24 inches
  • 18 inches
  • 36 inches
  • 12 inches

NEC Reference: NEC 2026 — Table 300.5

Question 10: Per NEC 300.5(D)(1), direct-buried conductors and cables emerging from grade must be protected by enclosures or raceways from the minimum cover depth up to at least how high above finished grade?

  • 8 feet
  • 6 feet
  • 3 feet
  • 10 feet

NEC Reference: NEC 2026 — 300.5(D)(1)

Question 11: Per NEC 300.5(D)(3), a warning ribbon must be placed in the trench at least 12 inches above underground service conductors that are not encased in concrete and are buried:

  • 18 inches or more below grade
  • 6 inches or more
  • 12 inches or more
  • 30 inches or more

NEC Reference: NEC 2026 — 300.5(D)(3)

Question 12: Per NEC 300.14, at each outlet, junction and switch point, at least how much free conductor must be left for splices or connection of devices?

  • 6 inches
  • 8 inches
  • 12 inches
  • 3 inches

NEC Reference: NEC 2026 — 300.14

Question 13: Per NEC 358.30(A), EMT must be securely fastened within how far of each outlet box, junction box, cabinet or conduit body?

  • 3 feet
  • 12 inches
  • 5 feet
  • 18 inches

NEC Reference: NEC 2026 — 358.30(A)

Question 14: Per NEC 358.30(A), EMT must be supported at intervals not exceeding:

  • 12 feet
  • 10 feet
  • 6 feet
  • 8 feet

NEC Reference: NEC 2026 — 358.30(A)

Question 15: Per NEC Table 352.30, rigid PVC conduit in trade sizes 1/2 through 1 inch must be supported at intervals not exceeding:

  • 3 feet
  • 10 feet
  • 6 feet
  • 5 feet

NEC Reference: NEC 2026 — Table 352.30

Question 16: Per NEC 352.44, expansion fittings for PVC conduit are required where the expected length change due to thermal expansion and contraction is:

  • 2 inches or more
  • 1/8 inch or more
  • 1/4 inch or more
  • 1 inch or more

NEC Reference: NEC 2026 — 352.44

Question 17: Per NEC 358.26 (and similar sections for other raceways), the total degrees of bends between pull points must not exceed:

  • 180 degrees
  • 270 degrees
  • 360 degrees
  • 450 degrees

NEC Reference: NEC 2026 — 358.26

Question 18: Per NEC 334.30, Type NM cable must be secured at intervals not exceeding 4½ feet and within how far of every box or cabinet?

  • 8 inches
  • 6 inches
  • 18 inches
  • 12 inches

NEC Reference: NEC 2026 — 334.30

Question 19: Per NEC 330.30(B), Type MC cable must generally be secured at intervals not exceeding:

  • 6 feet
  • 3 feet
  • 4½ feet
  • 10 feet

NEC Reference: NEC 2026 — 330.30(B)

Question 20: Per NEC Chapter 9, Table 1, the maximum fill for a conduit with three or more conductors is:

  • 53%
  • 31%
  • 40%
  • 60%

NEC Reference: NEC 2026 — Chapter 9, Table 1

Question 21: Per NEC Chapter 9, Table 1, Note 4, a conduit nipple not over 24 inches long may be filled to:

  • 53%
  • 60%
  • 40%
  • 75%

NEC Reference: NEC 2026 — Chapter 9, Table 1, Note 4

Question 22: Using Chapter 9 Tables 4 and 5, 1-inch EMT has a total area of 0.864 in² and 12 AWG THHN has an area of 0.0133 in². About how many 12 AWG THHN conductors fit at 40% fill?

  • 35
  • 22
  • 26
  • 16

NEC Reference: NEC 2026 — Chapter 9, Tables 4 and 5

Question 23: Per NEC 376.22(A), the sum of the cross-sectional areas of all conductors in a metal wireway must not exceed what percentage of the wireway's interior area?

  • 20%
  • 40%
  • 53%
  • 75%

NEC Reference: NEC 2026 — 376.22(A)

Question 24: Per NEC Table 314.16(B), each 12 AWG conductor counted in a box fill calculation requires a volume allowance of:

  • 2.50 cubic inches
  • 2.25 cubic inches
  • 2.00 cubic inches
  • 3.00 cubic inches

NEC Reference: NEC 2026 — Table 314.16(B)

Question 25: A single-gang box contains two 12/2 NM cables with ground (4 insulated 12 AWG conductors and 2 grounds), internal cable clamps, and one duplex receptacle. Per NEC 314.16(B), what is the required box volume?

  • 20.25 cubic inches
  • 18.00 cubic inches
  • 15.75 cubic inches
  • 13.50 cubic inches

NEC Reference: NEC 2026 — 314.16(B)

Question 26: Per NEC 314.16(B)(1), which conductors are NOT counted in a box fill calculation?

  • Conductors that do not leave the box, such as pigtails, and up to four fixture wires smaller than 14 AWG from a domed luminaire canopy
  • Conductors that pass through the box without a splice or termination
  • Every conductor that ends in the box, including those spliced to devices
  • All equipment grounding conductors, no matter how many enter the box

NEC Reference: NEC 2026 — 314.16(B)(1)

Question 27: Per NEC 314.20, in walls or ceilings of noncombustible material such as drywall or plaster, the front edge of a box may be set back from the finished surface by not more than:

  • 1/2 inch
  • 3/8 inch
  • 1/4 inch
  • 1/8 inch

NEC Reference: NEC 2026 — 314.20

Question 28: Per NEC 314.28(A)(1), for a straight pull containing 4 AWG or larger conductors, the length of the box must be at least how many times the trade size of the largest raceway?

  • 10 times
  • 4 times
  • 8 times
  • 6 times

NEC Reference: NEC 2026 — 314.28(A)(1)

Question 29: A pull box has a 3-inch and a 2-inch conduit entering the same wall for an angle pull. Per NEC 314.28(A)(2), what is the minimum distance to the opposite wall?

  • 30 inches
  • 20 inches
  • 24 inches
  • 18 inches

NEC Reference: NEC 2026 — 314.28(A)(2)

Question 30: Per NEC 314.27(C), an outlet box used as the sole support of a ceiling-suspended (paddle) fan must be listed for that use and may support a fan weighing up to:

  • 70 pounds
  • 35 pounds
  • 50 pounds
  • 100 pounds

NEC Reference: NEC 2026 — 314.27(C)

EXAM CARD NEC_PRACTICE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2026
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)