NEC 2026 Code Questions Practice Test 5

Free NEC 2026 practice test with 30 questions on Article 250: the grounding electrode system, ground rod rules, GEC sizing with Table 250.66, EGC sizing with Table 250.122, main and system bonding jumpers, service bonding, piping bonding, and buildings supplied by a feeder.

Share this test
Want the real exam format? Take a free full-length exam for your state
TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Before You Start

  • 30 questions, multiple choice
  • 45 minutes, pass mark 70%
  • Main article: 250 (Tables 250.66, 250.102(C)(1) and 250.122)

Tip: GEC sizing (Table 250.66) is based on the service conductor size. EGC sizing (Table 250.122) is based on the breaker size.

30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2026
NEC 2026 Code Questions Practice Test 5
Q1 / 30
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
Rate it and add a quick comment. No sign-up.
Tap one to send it now:
Share your score
Share it and get the NEC 2026 Article Quick Reference free, right now.
Unlocked — thanks for sharing! 🎉
Get the NEC 2026 Article Quick Reference
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Code Questions Practice Test 5 — Question List

Question 1: Per NEC 250.4(A)(5), the earth is NOT considered an effective ground-fault current path because:

  • It is always too dry to carry any current during a ground fault
  • It carries the normal neutral current from the utility transformer
  • Its resistance is too high to let enough current flow to open the overcurrent device
  • It is not bonded to the service equipment at the main panel

NEC Reference: NEC 2026 — 250.4(A)(5)

Question 2: Per NEC 250.50, when several grounding electrodes listed in 250.52(A)(1) through (A)(7) are present at a building, they must be:

  • Used one at a time
  • Isolated from each other
  • Connected only if the AHJ asks
  • Bonded together to form the grounding electrode system

NEC Reference: NEC 2026 — 250.50

Question 3: Per NEC 250.52(A)(1), a metal underground water pipe qualifies as a grounding electrode if it is in direct contact with the earth for at least:

  • 5 feet
  • 8 feet
  • 20 feet
  • 10 feet

NEC Reference: NEC 2026 — 250.52(A)(1)

Question 4: Per NEC 250.52(A)(3), a concrete-encased electrode must be at least how long when made of 1/2-inch steel reinforcing bar?

  • 25 feet
  • 20 feet
  • 10 feet
  • 8 feet

NEC Reference: NEC 2026 — 250.52(A)(3)

Question 5: Per NEC 250.52(A)(4), a ground ring encircling a building must be at least 20 feet long and made of bare copper not smaller than:

  • 4 AWG
  • 6 AWG
  • 2 AWG
  • 1/0 AWG

NEC Reference: NEC 2026 — 250.52(A)(4)

Question 6: Per NEC 250.52(A)(5), a rod or pipe electrode must be at least how long?

  • 8 feet
  • 6 feet
  • 10 feet
  • 5 feet

NEC Reference: NEC 2026 — 250.52(A)(5)

Question 7: Per NEC 250.52(B), which of the following may NOT be used as a grounding electrode?

  • A ground ring
  • Concrete-encased rebar
  • Metal underground gas piping
  • A listed ground rod

NEC Reference: NEC 2026 — 250.52(B)

Question 8: Per NEC 250.53(A)(2), a single rod, pipe or plate electrode must be supplemented by an additional electrode unless:

  • The service is 100 amperes or less
  • It is 10 feet long
  • It is copper
  • The single electrode has a resistance to earth of 25 ohms or less

NEC Reference: NEC 2026 — 250.53(A)(2)

Question 9: Per NEC 250.53(A)(3), when two ground rods are used, they must be spaced at least how far apart?

  • 10 feet
  • 3 feet
  • 8 feet
  • 6 feet

NEC Reference: NEC 2026 — 250.53(A)(3)

Question 10: Per NEC 250.53(A)(4), where rock bottom is encountered, a ground rod may be driven at an angle not more than how many degrees from vertical?

  • 60 degrees
  • 45 degrees
  • 90 degrees
  • 30 degrees

NEC Reference: NEC 2026 — 250.53(A)(4)

Question 11: Per NEC Table 250.66, what is the minimum copper grounding electrode conductor for a service with 3/0 AWG copper service-entrance conductors?

  • 4 AWG
  • 6 AWG
  • 2 AWG
  • 8 AWG

NEC Reference: NEC 2026 — Table 250.66

Question 12: Per NEC Table 250.66, what size copper GEC is required for 350 kcmil copper service-entrance conductors?

  • 4 AWG
  • 2/0 AWG
  • 1/0 AWG
  • 2 AWG

NEC Reference: NEC 2026 — Table 250.66

Question 13: Per NEC 250.66(A), the portion of the GEC that is the sole connection to a ground rod is not required to be larger than:

  • 2 AWG copper
  • 6 AWG copper or 4 AWG aluminum
  • 8 AWG copper
  • 4 AWG copper

NEC Reference: NEC 2026 — 250.66(A)

Question 14: Per NEC 250.66(B), the GEC that is the sole connection to a concrete-encased electrode is not required to be larger than:

  • 6 AWG copper
  • 2 AWG copper
  • 1/0 AWG copper
  • 4 AWG copper

NEC Reference: NEC 2026 — 250.66(B)

Question 15: Per NEC 250.64(C), the grounding electrode conductor must be installed in one continuous length without a splice, except it may be spliced by:

  • Split-bolt connectors wrapped with electrical tape
  • Twist-on wire connectors listed for the conductor size
  • Set-screw lugs mounted on an insulated terminal block
  • Irreversible compression-type connectors or exothermic welding

NEC Reference: NEC 2026 — 250.64(C)

Question 16: Per NEC 250.64(E), ferrous metal raceways enclosing a grounding electrode conductor must be:

  • Made of PVC instead
  • Isolated from the enclosure
  • Painted green
  • Electrically continuous and bonded at each end to the GEC

NEC Reference: NEC 2026 — 250.64(E)

Question 17: Per NEC 250.68(A), the connection of a grounding electrode conductor to a ground rod that is driven in the earth:

  • Must be in a junction box
  • Must be inside the building
  • Must be accessible at all times
  • Is not required to be accessible

NEC Reference: NEC 2026 — 250.68(A)

Question 18: Per NEC 250.70, a ground clamp used on a grounding electrode must not have more than one conductor connected to it unless:

  • The clamp is bronze
  • The clamp is listed for multiple conductors
  • The conductors are the same size
  • They are both copper

NEC Reference: NEC 2026 — 250.70

Question 19: Per NEC 250.28, the main bonding jumper connects:

  • The neutral conductor to the metal water pipe inside the building
  • The equipment grounding conductors and service enclosure to the grounded (neutral) conductor at the service
  • Two ground rods together so they act as one electrode
  • The grounding electrode conductor to the ground rod outside the building

NEC Reference: NEC 2026 — 250.28

Question 20: Per NEC 250.24(A)(5), on the load side of the service disconnecting means, a grounding connection to the grounded (neutral) conductor is:

  • Not permitted (except as allowed in 250.30, 250.32 and certain other sections)
  • Permitted anywhere, as long as the conductors are the same size
  • Required at each receptacle box that has a metal enclosure
  • Required at every subpanel to give fault current a local path

NEC Reference: NEC 2026 — 250.24(A)(5)

Question 21: Per NEC 250.92(B), service raceways connected with standard locknuts only:

  • Are acceptable only when the service raceway is PVC conduit
  • Must be painted with conductive paint to complete the bond
  • Are always acceptable, because the raceways are threaded into the enclosure
  • Are not sufficiently bonded; bonding jumpers, threaded hubs, bonding-type locknuts or other listed means are needed

NEC Reference: NEC 2026 — 250.92(B)

Question 22: Per NEC 250.94, an intersystem bonding termination at the service must have the capacity for connecting at least how many intersystem bonding conductors?

  • Three
  • Two
  • One
  • Six

NEC Reference: NEC 2026 — 250.94

Question 23: Per NEC 250.104(A)(1), the bonding jumper for interior metal water piping in a building is sized using:

  • Table 250.122, based on the main breaker size
  • Table 250.102(C)(1), based on the size of the service-entrance conductors
  • The size of the water pipe
  • Table 310.16

NEC Reference: NEC 2026 — 250.104(A)(1)

Question 24: Per NEC 250.104(B), metal gas piping that is likely to become energized is considered bonded by:

  • The equipment grounding conductor of the circuit that is likely to energize it
  • The water pipe bonding jumper only, at the water heater
  • A separate ground rod driven next to the gas meter
  • The neutral conductor of the appliance branch circuit

NEC Reference: NEC 2026 — 250.104(B)

Question 25: Per NEC Table 250.122, what is the minimum copper equipment grounding conductor for a circuit protected by a 60-ampere breaker?

  • 10 AWG
  • 8 AWG
  • 12 AWG
  • 6 AWG

NEC Reference: NEC 2026 — Table 250.122

Question 26: Per NEC Table 250.122, what is the minimum copper EGC for a feeder protected by a 400-ampere breaker?

  • 2 AWG
  • 3 AWG
  • 1 AWG
  • 4 AWG

NEC Reference: NEC 2026 — Table 250.122

Question 27: Per NEC 250.122(B), when ungrounded conductors are increased in size for voltage drop, the equipment grounding conductor must be:

  • Left at the Table 250.122 size
  • Increased in size proportionally, based on circular mil area
  • Doubled in every case
  • Removed

NEC Reference: NEC 2026 — 250.122(B)

Question 28: Per NEC 250.119, equipment grounding conductors that are insulated or covered must have a finish that is:

  • Green, or green with one or more yellow stripes
  • White or gray
  • Orange
  • Black with a green stripe

NEC Reference: NEC 2026 — 250.119

Question 29: Per NEC 250.32(B)(1), a detached building supplied by a feeder must have an equipment grounding conductor run with the feeder, and the neutral at the detached building's disconnect must be:

  • Connected to the ground rod only
  • Omitted
  • Bonded to the enclosure
  • Isolated from the equipment grounding conductors (not bonded)

NEC Reference: NEC 2026 — 250.32(B)(1)

Question 30: Per NEC 250.30(A), a separately derived system such as a 480-to-208Y/120-volt transformer requires:

  • A ground rod only
  • A system bonding jumper, a grounding electrode conductor, and connection to a grounding electrode
  • No grounding at all
  • A connection to the neutral of the primary system

NEC Reference: NEC 2026 — 250.30(A)