NEC_PRACTICE NEC 2026

NEC 2026 Code Questions Practice Test 4

Free NEC 2026 practice test with 30 questions on overcurrent protection (Article 240): standard ampere ratings, the "next size up" rule, small-conductor limits, feeder tap rules, where breakers and fuses may be located, fuse types, and arc-energy reduction.

Share this test
Want the real exam format? Take a free full-length exam for your state
TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Before You Start

  • 30 questions, multiple choice
  • 45 minutes, pass mark 70%
  • Main article: 240 (with 110.9 and 110.10)

Tip: Memorize the standard sizes in 240.6(A) up to 400 A and the 240.4(D) limits: 14 AWG = 15 A, 12 AWG = 20 A, 10 AWG = 30 A (copper).

30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2026
NEC 2026 Code Questions Practice Test 4
Q1 / 30
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
Rate it and add a quick comment. No sign-up.
Tap one to send it now:
Share your score
Share it and get the NEC 2026 Article Quick Reference free, right now.
Unlocked — thanks for sharing! 🎉
Get the NEC 2026 Article Quick Reference
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Code Questions Practice Test 4 — Question List

Question 1: Per NEC 240.4(D), unless specifically permitted elsewhere, the overcurrent protection for 14 AWG copper conductors must not exceed:

  • 15 amperes
  • 10 amperes
  • 20 amperes
  • 25 amperes

NEC Reference: NEC 2026 — 240.4(D)

Question 2: Per NEC 240.4(D), the maximum overcurrent protection for 12 AWG aluminum or copper-clad aluminum conductors is:

  • 25 amperes
  • 20 amperes
  • 30 amperes
  • 15 amperes

NEC Reference: NEC 2026 — 240.4(D)

Question 3: Per NEC 240.4(D), the maximum overcurrent protection for 16 AWG copper conductors (where permitted) is:

  • 5 amperes
  • 7 amperes
  • 10 amperes
  • 15 amperes

NEC Reference: NEC 2026 — 240.4(D)

Question 4: Per NEC 240.4(B), the next higher standard overcurrent device rating may be used above the conductor ampacity only if the rating does not exceed:

  • 400 amperes, for any circuit, including receptacle branch circuits
  • 600 amperes, and only for motor and air-conditioning circuits
  • 1200 amperes, for any type of circuit including multioutlet receptacle circuits
  • 800 amperes, and the circuit is not a multioutlet branch circuit supplying receptacles for cord-and-plug loads

NEC Reference: NEC 2026 — 240.4(B)

Question 5: A conductor has an ampacity of 115 amperes after all corrections. Per NEC 240.4(B) and 240.6(A), what is the largest standard overcurrent device that may protect it (not a multioutlet receptacle circuit)?

  • 100 amperes
  • 125 amperes
  • 110 amperes
  • 150 amperes

NEC Reference: NEC 2026 — 240.4(B)

Question 6: Per NEC 240.4(C), where the overcurrent device is rated over 800 amperes, the conductor ampacity must be:

  • Rounded down to the nearest standard size
  • Equal to or greater than the rating of the overcurrent device
  • At least 125% of the device rating
  • At least 80% of the device rating

NEC Reference: NEC 2026 — 240.4(C)

Question 7: Which of the following is NOT a standard ampere rating for fuses and inverse-time circuit breakers in NEC 240.6(A)?

  • 80 amperes
  • 70 amperes
  • 90 amperes
  • 75 amperes

NEC Reference: NEC 2026 — 240.6(A)

Question 8: Which of the following IS a standard ampere rating in NEC 240.6(A)?

  • 105 amperes
  • 120 amperes
  • 130 amperes
  • 110 amperes

NEC Reference: NEC 2026 — 240.6(A)

Question 9: Per NEC 240.6(A), which additional standard ratings apply only to fuses?

  • 1, 3, 6, 10 and 601 amperes
  • 75 and 85 amperes
  • 5, 15 and 25 amperes
  • 12, 18 and 24 amperes

NEC Reference: NEC 2026 — 240.6(A)

Question 10: Per NEC 240.24(A), overcurrent devices must be readily accessible and installed so that the center of the grip of the operating handle, in its highest position, is not more than how high above the floor or working platform?

  • 5 feet 6 inches
  • 7 feet
  • 6 feet 7 inches
  • 6 feet

NEC Reference: NEC 2026 — 240.24(A)

Question 11: Per NEC 240.24(D), overcurrent devices must not be located:

  • In a garage, where vehicles may strike the panel
  • In the vicinity of easily ignitible material, such as in clothes closets
  • In a basement, where moisture may be present
  • Outdoors, unless the enclosure is rated Type 3R

NEC Reference: NEC 2026 — 240.24(D)

Question 12: Per NEC 240.24(E), overcurrent devices in dwelling units and guest rooms of hotels and motels must not be located in:

  • Garages
  • Bathrooms
  • Hallways
  • Kitchens

NEC Reference: NEC 2026 — 240.24(E)

Question 13: Per NEC 240.24(F), overcurrent devices must not be located:

  • In a utility room
  • Below a window
  • Over the steps of a stairway
  • Within 10 feet of a door

NEC Reference: NEC 2026 — 240.24(F)

Question 14: Per NEC 240.21(B)(1), the "10-foot tap rule" requires the ampacity of the tap conductors to be:

  • At least 125% of the load, with no limit tied to the feeder OCPD
  • Not less than the rating of the device they supply, and for field taps leaving the enclosure, not less than 1/10 of the feeder OCPD rating
  • At least 1/3 of the rating of the feeder overcurrent device in all cases
  • Equal to the ampacity of the feeder conductors they are tapped from

NEC Reference: NEC 2026 — 240.21(B)(1)

Question 15: Per NEC 240.21(B)(2), the "25-foot tap rule" requires the tap conductors to have an ampacity of at least:

  • 1/10 of the feeder OCPD rating
  • The full feeder OCPD rating
  • 1/2 of the feeder OCPD rating
  • 1/3 of the rating of the feeder overcurrent device

NEC Reference: NEC 2026 — 240.21(B)(2)

Question 16: A feeder is protected by a 300-ampere breaker. Using the 25-foot tap rule, what is the minimum ampacity of the tap conductors?

  • 150 amperes
  • 100 amperes
  • 30 amperes
  • 300 amperes

NEC Reference: NEC 2026 — 240.21(B)(2)

Question 17: Per NEC 240.15(A), an overcurrent device must be connected:

  • In series with each ungrounded conductor
  • In the equipment grounding conductor
  • In series with the grounded (neutral) conductor
  • In parallel with each load

NEC Reference: NEC 2026 — 240.15(A)

Question 18: Per NEC 240.22, an overcurrent device generally must not be connected in series with:

  • Any ungrounded conductor
  • A motor branch circuit
  • Any conductor that is intentionally grounded
  • A feeder over 100 amperes

NEC Reference: NEC 2026 — 240.22

Question 19: Per NEC 240.51(A), plug fuses of the Edison-base type are classified at not over 125 volts and:

  • 30 amperes and below
  • 100 amperes and below
  • 60 amperes and below
  • 15 amperes only

NEC Reference: NEC 2026 — 240.51(A)

Question 20: Per NEC 240.54, Type S fuses and adapters are designed so that:

  • A fuse of a higher ampere classification cannot be used in an adapter for a lower classification
  • They are rated for 600 volts
  • Any size fuse fits any holder
  • They can be used in Edison-base holders without adapters

NEC Reference: NEC 2026 — 240.54

Question 21: Per NEC 240.83(D), circuit breakers used as switches in 120-volt and 277-volt fluorescent lighting circuits must be listed and marked:

  • SWD or HID
  • CL
  • HACR
  • GFCI

NEC Reference: NEC 2026 — 240.83(D)

Question 22: Per NEC 240.86, a series-rated combination of breakers or fuses is permitted where:

  • The electrician calculates it on site
  • The downstream breaker has a higher interrupting rating
  • The AHJ verbally approves any combination
  • The combination has been tested and is marked on the end-use equipment

NEC Reference: NEC 2026 — 240.86

Question 23: Per NEC 240.87, arc-energy reduction is required where the highest continuous current trip setting of a circuit breaker is, or can be adjusted to:

  • 1200 amperes or higher
  • 2000 amperes or higher
  • 400 amperes or higher
  • 800 amperes or higher

NEC Reference: NEC 2026 — 240.87

Question 24: Per NEC 240.87(B), which of the following is an accepted arc-energy reduction method?

  • Using aluminum bus
  • An energy-reducing maintenance switch with a local status indicator
  • Installing a larger main breaker
  • Adding a surge protective device

NEC Reference: NEC 2026 — 240.87(B)

Question 25: Per NEC 240.21(C)(2), secondary conductors from a transformer that are not over 10 feet long must have an ampacity that is:

  • Equal to the transformer kVA rating divided by the primary voltage
  • At least 125% of the transformer primary current rating
  • At least 1/3 of the rating of the primary overcurrent device
  • Not less than the combined computed loads and not less than the rating of the device they terminate in

NEC Reference: NEC 2026 — 240.21(C)(2)

Question 26: Per NEC 240.10, supplementary overcurrent protection (such as a small fuse inside a luminaire):

  • Can replace the branch-circuit breaker
  • Must be rated at least 100 amperes
  • Is not a substitute for required branch-circuit overcurrent protection
  • Must be readily accessible

NEC Reference: NEC 2026 — 240.10

Question 27: Per NEC 240.4(F), the primary overcurrent device of a single-phase transformer with a 2-wire (single-voltage) secondary may protect the secondary conductors if:

  • The secondary conductors are at least 10 feet long and run outdoors
  • The transformer is larger than 1000 kVA and has a delta primary
  • The primary device does not exceed the secondary conductor ampacity multiplied by the secondary-to-primary voltage ratio
  • The secondary is a 4-wire wye system with a grounded neutral

NEC Reference: NEC 2026 — 240.4(F)

Question 28: Per NEC 240.21(B)(3), the "25-foot transformer feeder tap" (primary plus secondary) limits the total length of primary plus secondary conductors to:

  • 10 feet
  • 25 feet
  • 50 feet
  • 100 feet

NEC Reference: NEC 2026 — 240.21(B)(3)

Question 29: Per NEC 240.21(B)(5), outside feeder taps of unlimited length are permitted when:

  • The tap conductors are smaller than 6 AWG and protected by a GFCI device
  • The tap conductors run inside the building for at least 25 feet before ending in a breaker
  • The tap conductors are outdoors (except at the termination), protected from damage, and end at a single OCPD that is part of or next to the building disconnect
  • The tap is supplied from a 15-ampere breaker and ends at a receptacle

NEC Reference: NEC 2026 — 240.21(B)(5)

Question 30: Per NEC 240.6(C), an adjustable-trip circuit breaker with restricted access to its adjusting means may have its ampere rating considered to be:

  • The maximum possible setting in all cases
  • The frame size
  • 80% of the frame size
  • The adjusted (long-time pickup) current setting

NEC Reference: NEC 2026 — 240.6(C)

EXAM CARD NEC_PRACTICE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2026
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)