NEC 2026 Code Questions Practice Test 3

Free NEC 2026 practice test with 30 questions on services and feeders: overhead and underground service clearances, service disconnect rules, minimum service sizes, surge protection, ground-fault protection, the 83% dwelling service conductor rule, and the load calculation rules that NEC 2026 moved into the new Article 120.

Share this test
Want the real exam format? Take a free full-length exam for your state
TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Before You Start

  • 30 questions, multiple choice
  • 45 minutes, pass mark 70%
  • Main articles: 120, 215, 230 and 310.12

NEC 2026 note: load calculations are now in Article 120 (they were Article 220). The standard values such as 1500 VA per small-appliance circuit and 5000 VA per dryer are the same.

30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2026
NEC 2026 Code Questions Practice Test 3
Q1 / 30
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
Rate it and add a quick comment. No sign-up.
Tap one to send it now:
Share your score
Share it and get the NEC 2026 Article Quick Reference free, right now.
Unlocked — thanks for sharing! 🎉
Get the NEC 2026 Article Quick Reference
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Code Questions Practice Test 3 — Question List

Question 1: Per NEC 230.2, a building is generally permitted to be supplied by how many services?

  • Only one, unless one of the listed exceptions applies
  • Two, one for lighting and one for power
  • Three for commercial buildings
  • As many as the owner wants

NEC Reference: NEC 2026 — 230.2

Question 2: Per NEC 230.7, conductors other than service conductors are:

  • Permitted in the service raceway if they are a different insulation color
  • Not permitted in the same service raceway or service cable (except grounding conductors and some load management conductors)
  • Permitted in the service raceway if they serve the same building
  • Permitted in the service raceway if they are smaller than the service conductors

NEC Reference: NEC 2026 — 230.7

Question 3: Per NEC 230.24(A), overhead service conductors (300 volts or less) passing over a roof that is not readily accessible, with a slope of 4 in 12 or more, may have a clearance of:

  • 18 inches
  • 8½ feet
  • 10 feet
  • 3 feet

NEC Reference: NEC 2026 — 230.24(A)

Question 4: Per NEC 230.24(B), overhead service conductors over residential property and driveways (300 volts to ground or less) must have a minimum vertical clearance of:

  • 18 feet
  • 15 feet
  • 12 feet
  • 10 feet

NEC Reference: NEC 2026 — 230.24(B)

Question 5: Per NEC 230.24(B), the minimum vertical clearance of overhead service conductors over public streets, alleys, roads and parking areas subject to truck traffic is:

  • 15 feet
  • 12 feet
  • 24 feet
  • 18 feet

NEC Reference: NEC 2026 — 230.24(B)

Question 6: Per NEC 230.9(A), service conductors and drip loops must have a clearance of at least how far from windows that are designed to be opened, doors, porches and balconies?

  • 6 feet
  • 18 inches
  • 10 feet
  • 3 feet

NEC Reference: NEC 2026 — 230.9(A)

Question 7: Per NEC 230.26, the point of attachment of overhead service conductors to a building must be at least how high above finished grade?

  • 8 feet
  • 10 feet
  • 12 feet
  • 15 feet

NEC Reference: NEC 2026 — 230.26

Question 8: Per NEC 230.54(C), a service head (weatherhead) must be located:

  • Inside the building
  • Above the point of attachment of the service-drop or overhead service conductors
  • At least 12 inches below the point of attachment
  • At the same height as the meter

NEC Reference: NEC 2026 — 230.54(C)

Question 9: Per NEC 230.70(A)(1), the service disconnecting means must be installed at:

  • A readily accessible location, either outside the building or inside nearest the point of entrance of the service conductors
  • At the farthest point from the meter, to keep conductors protected
  • Any convenient location inside the building chosen by the owner
  • On the utility pole only, so the utility can operate it

NEC Reference: NEC 2026 — 230.70(A)(1)

Question 10: Per NEC 230.71(B), each service may have how many service disconnecting means at most?

  • Two, one for lighting loads and one for power loads
  • Ten, as long as they are grouped together in one location
  • One only, with no exceptions for any building type
  • Six (switches or breakers in separate enclosures, or in a switchboard or switchgear with separate sections)

NEC Reference: NEC 2026 — 230.71(B)

Question 11: Per NEC 230.79(C), the service disconnecting means for a one-family dwelling must have a rating of not less than:

  • 60 amperes
  • 100 amperes, 3-wire
  • 150 amperes
  • 200 amperes

NEC Reference: NEC 2026 — 230.79(C)

Question 12: Per NEC 230.85, one- and two-family dwelling services must have an emergency disconnecting means installed:

  • In the basement
  • In a readily accessible outdoor location
  • Inside the main panel only
  • On the utility pole

NEC Reference: NEC 2026 — 230.85

Question 13: Per NEC 230.67, services supplying dwelling units must be provided with:

  • A whole-house GFCI device installed at the main breaker
  • A Type 1 or Type 2 surge protective device (SPD)
  • An AFCI main breaker that protects all branch circuits
  • A standby generator connected through a transfer switch

NEC Reference: NEC 2026 — 230.67

Question 14: Per NEC 230.95, ground-fault protection of equipment is required for solidly grounded wye services of more than 150 volts to ground (but not over 1000 volts phase-to-phase) for each service disconnect rated:

  • 2000 amperes or more
  • 400 amperes or more
  • 1000 amperes or more
  • 800 amperes or more

NEC Reference: NEC 2026 — 230.95

Question 15: Per NEC 230.95(A), the maximum setting of the ground-fault protection on a service disconnect is:

  • 3000 amperes
  • 1000 amperes
  • 600 amperes
  • 1200 amperes

NEC Reference: NEC 2026 — 230.95(A)

Question 16: Per NEC 230.31(B) (service laterals) and 230.23(B) (overhead service conductors), the minimum conductor size is generally:

  • 10 AWG copper or 8 AWG aluminum
  • 12 AWG copper
  • 6 AWG copper or 4 AWG aluminum
  • 8 AWG copper or 6 AWG aluminum

NEC Reference: NEC 2026 — 230.31(B)

Question 17: Per NEC 310.12, for a 200-ampere, 120/240-volt single-phase dwelling service, the service conductors may be sized at 83% of the service rating. What ampacity is the minimum?

  • 166 amperes
  • 150 amperes
  • 200 amperes
  • 175 amperes

NEC Reference: NEC 2026 — 310.12

Question 18: Using NEC 310.12 and Table 310.16 (75°C), what is the minimum size copper service conductor for a 200-ampere, 120/240-volt single-phase dwelling service?

  • 3/0 AWG
  • 1/0 AWG
  • 2/0 AWG
  • 4/0 AWG

NEC Reference: NEC 2026 — 310.12

Question 19: Per NEC 230.42(A), service-entrance conductors must have an ampacity of at least:

  • 100% of the noncontinuous load plus 125% of the continuous load
  • 80% of the calculated load
  • The rating of the meter
  • 125% of the noncontinuous load only

NEC Reference: NEC 2026 — 230.42(A)

Question 20: Per NEC 215.2(A)(1), a feeder supplying 80 amperes of continuous load and 40 amperes of noncontinuous load needs conductors with an ampacity of at least:

  • 150 amperes
  • 120 amperes
  • 100 amperes
  • 140 amperes

NEC Reference: NEC 2026 — 215.2(A)(1)

Question 21: Per NEC 230.82, which of the following is permitted to be connected on the supply side of the service disconnecting means?

  • A general lighting panelboard
  • Meters and meter sockets, and emergency disconnects that meet 230.85
  • A dwelling kitchen receptacle circuit
  • A sump pump branch circuit

NEC Reference: NEC 2026 — 230.82

Question 22: Per NEC 230.62(C), service equipment must have barriers placed so that no uninsulated, ungrounded service busbar or terminal will be exposed to accidental contact by people or tools during:

  • Installation of the service drop
  • Utility switching
  • Servicing or maintenance of the load terminations
  • Meter reading

NEC Reference: NEC 2026 — 230.62(C)

Question 23: In NEC 2026 load calculations (Article 120), each 20-ampere small-appliance branch circuit in a dwelling is calculated at:

  • 1200 VA
  • 1500 VA
  • 180 VA
  • 2000 VA

NEC Reference: NEC 2026 — Article 120

Question 24: In a dwelling load calculation, the laundry branch circuit is counted at:

  • 1500 VA
  • 1200 VA
  • 3000 VA
  • 5000 VA

NEC Reference: NEC 2026 — Article 120

Question 25: In a dwelling load calculation, a household electric clothes dryer is counted at:

  • The nameplate rating even if it is less than 5000
  • 5000 watts (VA) or the nameplate rating, whichever is larger
  • 1500 watts
  • 3000 watts

NEC Reference: NEC 2026 — Article 120

Question 26: The demand load for one household electric range rated 12 kW or less (Column C of the range demand table) is:

  • 6 kW
  • 12 kW
  • 8 kW
  • 10 kW

NEC Reference: NEC 2026 — Article 120

Question 27: When heating and air-conditioning loads in a dwelling will not run at the same time (noncoincident loads), the load calculation uses:

  • The smaller load
  • 125% of the smaller load
  • The sum of both loads
  • Only the larger of the two loads

NEC Reference: NEC 2026 — Article 120

Question 28: In a dwelling load calculation, fastened-in-place appliances (other than ranges, dryers, space heating and AC) may have a 75% demand factor applied when there are:

  • Four or more such appliances on the same feeder or service
  • Ten or more such appliances on the same feeder or service
  • Two or more such appliances on the same feeder or service
  • Three or more such appliances on the same feeder or service

NEC Reference: NEC 2026 — Article 120

Question 29: Per NEC 230.51(A), service-entrance cable must be supported within 12 inches of every service head, gooseneck or connection to a raceway or enclosure, and at intervals not exceeding:

  • 24 inches
  • 6 feet
  • 4½ feet
  • 30 inches

NEC Reference: NEC 2026 — 230.51(A)

Question 30: In NEC 2026, the general lighting unit load used for dwelling feeder and service calculations was reduced from 3 VA per square foot to:

  • 1 VA per square foot
  • 2 VA per square foot
  • 2.5 VA per square foot
  • 1.5 VA per square foot

NEC Reference: NEC 2026 — Article 120