Grounding and Bonding (NEC 250) — NEC 2023 Edition

Free NEC 2023 practice test on grounding and bonding. Covers grounding purpose, grounded conductor identification, grounding electrode conductor sizing, electrode types, and bonding requirements. Simple English, full explanations.

Share this test
TOPICS COVERED
NEC Questions NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Grounding and Bonding (NEC 250) — NEC 2023 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

Student Reviews 4.0 / 5  ·  1 review

R
Rhonda F.

Grounding and bonding is honestly the hardest section of the NEC for most people and this quiz does a good job covering it. I had to look up a few things in the code book after but that's kind of the point. Good questions.

NEC CODE · NEC 2023
Grounding and Bonding (NEC 250) — NEC 2023 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time
My Missed Questions

Electrician Reviews

4.0 (1 review)
R
Rhonda F.
Feb 12, 2026

Grounding and bonding is honestly the hardest section of the NEC for most people and this quiz does a good job covering it. I had to look up a few things in the code book after but that's kind of the point. Good questions.

Leave a Review

5 stars
0/1000

Grounding and Bonding (NEC 250) — NEC 2023 Edition — Question List

Question 1: Why are electrical systems connected to earth (grounded), according to 250.4(A)(1)?

  • To limit voltage from lightning, line surges or contact with higher-voltage lines
  • To remove the need for overcurrent devices
  • To carry the normal load current back to the source
  • To raise the voltage to ground

NEC Reference: NEC 250.4(A)(1)

Question 2: The grounding electrode conductor runs only to ground rods, and the service conductors are 3/0 copper. What is the largest GEC size the NEC requires for that connection?

  • 2 AWG copper
  • 4 AWG copper
  • 6 AWG copper
  • 8 AWG copper

NEC Reference: NEC 250.66(A)

Question 3: The transformer supplying a building service is located outside the building. Where must an additional grounding connection of the grounded service conductor be made?

  • No additional connection is required
  • At every subpanel in the building
  • Only inside at the service panel
  • At the transformer or elsewhere outside the building

NEC Reference: NEC 250.24(A)(2)

Question 4: A 3-phase, 3-wire delta service has a grounded (corner-grounded) conductor. How must the grounded service conductor be sized?

  • 12.5% of the ungrounded conductor area
  • Not smaller than the GEC from Table 250.66
  • One size smaller than the ungrounded conductors
  • Ampacity not less than that of the ungrounded conductors

NEC Reference: NEC 250.24

Question 5: In a single-raceway service, the grounded (neutral) service conductor must be at least what size?

  • The size required by Table 250.102(C)(1)
  • The EGC size from Table 250.122
  • The size of the largest ungrounded conductor
  • Half the size of the ungrounded conductors

NEC Reference: NEC 250.24

Question 6: In a single-phase, 3-wire electrical system, what is the middle conductor generally required to be?

  • Grounded
  • Ungrounded
  • A hot conductor
  • Not connected at all

NEC Reference: NEC 250.26

Question 7: Grounded (neutral) conductors 6 AWG and smaller are most commonly identified by which color?

  • White or natural gray
  • Red
  • Green
  • Black

NEC Reference: NEC 200.6(A)

Question 8: When may an overcurrent device be connected in series with an intentionally grounded conductor?

  • Whenever a single-pole fuse is used
  • When it opens all conductors of the circuit at the same time
  • Whenever the circuit is 120 volts
  • Only in dwelling units

NEC Reference: NEC 240.22

Question 9: A single-phase service uses 1/0 AWG aluminum as its largest ungrounded conductor. What size aluminum grounding electrode conductor is required?

  • Aluminum 6 AWG
  • Aluminum 4 AWG
  • Copper 2 AWG
  • Copper 6 AWG

NEC Reference: NEC Table 250.66

Question 10: Lightning protection system ground terminals must generally be bonded to which grounding system?

  • The building or structure grounding electrode system
  • A distribution panelboard only
  • The service entrance only
  • Nothing -- bonding is not required

NEC Reference: NEC 250.106

Question 11: An insulated equipment grounding conductor 6 AWG or smaller is usually identified by what color?

  • Green
  • Orange
  • Brown
  • Pink

NEC Reference: NEC 250.119

Question 12: A concrete-encased grounding electrode (Ufer ground) generally must have at least what length of qualifying conductor or rebar?

  • 20 feet
  • 10 feet
  • 30 feet
  • 50 feet

NEC Reference: NEC 250.52(A)(3)

Question 13: At least how much of a rod or pipe electrode must be in contact with the soil?

  • 6 ft
  • 7 ft
  • 8 ft
  • 10 ft

NEC Reference: NEC 250.53(A)(4)

Question 14: Where two ground rods are used, they should be spaced at least how far apart?

  • 6 feet apart
  • 1 foot apart
  • 50 feet apart
  • Touching each other

NEC Reference: NEC 250.53(A)(3)

Question 15: Metal water piping in a building served by a service must be bonded to which of the following?

  • The nearest receptacle EGC only
  • The gas piping only
  • The structural steel only
  • The service equipment enclosure, grounded conductor at the service, GEC or electrode

NEC Reference: NEC 250.104(A)(1)

Question 16: Which materials are permitted for a grounding electrode conductor?

  • Copper, aluminum or copper-clad aluminum
  • Copper only
  • Stainless steel only
  • Galvanized steel only

NEC Reference: NEC 250.62

Question 17: Where is the main bonding jumper installed to connect the equipment grounding conductors to the grounded conductor?

  • At each separate building feeder panel
  • At the service
  • At every subpanel
  • At the last panelboard on the feeder

NEC Reference: NEC 250.28

Question 18: A service uses 2 AWG copper as its largest ungrounded conductor. What size copper grounding electrode conductor is required?

  • 8 AWG
  • 10 AWG
  • 6 AWG
  • 4 AWG

NEC Reference: NEC Table 250.66

Question 19: A circuit is protected by a 60-ampere overcurrent device. What is the minimum size copper equipment grounding conductor required?

  • 10 AWG
  • 12 AWG
  • 8 AWG
  • 14 AWG

NEC Reference: NEC Table 250.122

Question 20: Which method is NOT permitted for connecting grounding and bonding conductors?

  • A listed clamp
  • A listed pressure connector
  • A connection that depends solely on solder
  • Exothermic welding

NEC Reference: NEC 250.8

Question 21: The bonding jumper size for the water piping system is based on what?

  • The largest ungrounded service conductor
  • The pipe color
  • The homeowner's preference
  • Nothing -- any size works

NEC Reference: NEC 250.104(A)(1) / Table 250.102(C)(1)

Question 22: Isolated ground receptacles are installed mainly for what purpose?

  • To provide GFCI protection
  • To reduce electrical noise on sensitive electronic equipment
  • To increase the available fault current
  • To eliminate the need for an EGC

NEC Reference: NEC 250.146(D)

Question 23: An intersystem bonding termination at the service is provided for bonding which systems?

  • Lightning protection systems only
  • Building structural steel
  • Metal gas piping
  • Communications systems such as telephone and CATV

NEC Reference: NEC 250.94

Question 24: A metal underground water pipe is used as a grounding electrode. What else does the NEC require?

  • It must be encased in concrete
  • It must be bonded to the gas piping
  • It must be supplemented by an additional electrode
  • It must be at least 30 ft long

NEC Reference: NEC 250.53(D)(2)

Question 25: Metal gas piping that is likely to become energized must be treated how?

  • Bonded to the equipment grounding conductor of the circuit likely to energize it
  • Connected to the grounded conductor at each appliance
  • Used as the grounding electrode
  • Isolated with dielectric unions only

NEC Reference: NEC 250.104(B)

Question 26: A portable generator supplies only cord-and-plug equipment through its own receptacles. What is it NOT required to have?

  • A connection to a grounding electrode
  • Overcurrent protection
  • Bonding of its frame to the receptacle grounding terminals
  • Equipment grounding terminals on its receptacles

NEC Reference: NEC 250.34(A)

Question 27: A grounding electrode conductor is exposed to physical damage. How must it be protected?

  • Stapled tight to the surface
  • Coated with insulating varnish
  • Wrapped with electrical tape
  • In RMC, IMC, Schedule 80 PVC, RTRC-XW, EMT or cable armor

NEC Reference: NEC 250.64(B)

Question 28: A separately derived system, such as the secondary of a step-down transformer, needs what bonding connection at the source or first disconnect?

  • A main bonding jumper at the service only
  • A system bonding jumper
  • An equipment bonding jumper on the load side only
  • No bonding connection

NEC Reference: NEC 250.30(A)(1)

Question 29: Where multiple grounding electrodes are present at a building (such as a water pipe, ground rod, and concrete-encased electrode), what does NEC 250.50 require?

  • All present qualifying electrodes must be bonded together
  • Only one electrode may ever be used
  • They must be kept completely separate
  • Nothing -- bonding is optional

NEC Reference: NEC 250.50

Question 30: Which of the following is permitted as an equipment grounding conductor under 250.118?

  • The jacket of a flexible cord
  • The outer sheath of NM cable
  • Rigid metal conduit
  • PVC conduit

NEC Reference: NEC 250.118

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026