NEC CODE NEC 2020

Grounding and Bonding (NEC 250) — NEC 2020 Edition

Free NEC 2020 practice test on grounding and bonding. Covers grounding purpose, grounded conductor identification, grounding electrode conductor sizing, electrode types, and bonding requirements. Simple English, full explanations.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Grounding and Bonding (NEC 250) — NEC 2020 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2020
Grounding and Bonding (NEC 250) — NEC 2020 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Grounding and Bonding (NEC 250) — NEC 2020 Edition — Question List

Question 1: What is the main purpose of grounding an electrical system, per NEC 250.4(A)(1)?

  • To limit voltage from lightning, surges, or unintentional contact
  • To increase system voltage
  • To eliminate all overcurrent devices
  • It has no real safety purpose

NEC Reference: NEC 250.4(A)(1)

Question 2: True or false: the secondary circuits of low-voltage lighting systems are generally not grounded.

  • True
  • False
  • Only for outdoor systems
  • Only for systems over 50 volts

NEC Reference: NEC 411.5

Question 3: True or false: an additional grounding connection must be made at a transformer supplying the service inside a building.

  • True
  • False
  • Only for 3-phase systems
  • Only for 3-wire systems

NEC Reference: NEC 250.24(A)(2)

Question 4: In a delta-connected, 3-phase, 3-wire system, the grounded conductor's ampacity must be less than the rating of what?

  • The ungrounded conductor
  • The secondary conductor
  • The neutral conductor
  • Nothing -- no limit applies

NEC Reference: NEC 250.24(C)(3)

Question 5: True or false: in a single raceway, the grounded conductor may be larger than the largest ungrounded conductor in the raceway.

  • True
  • False
  • Only in metal raceways
  • Only for services

NEC Reference: NEC 250.24(C)(1)

Question 6: In a single-phase, 3-wire electrical system, what is the middle conductor generally required to be?

  • Grounded
  • Ungrounded
  • A hot conductor
  • Not connected at all

NEC Reference: NEC 250.26

Question 7: Grounded (neutral) conductors 6 AWG and smaller are most commonly identified by which color?

  • White or natural gray
  • Red
  • Green
  • Black

NEC Reference: NEC 200.6(A)

Question 8: True or false: the grounded (neutral) conductor can never be interrupted by a circuit breaker or fuse under any circumstances.

  • True
  • False
  • Only for 3-phase systems
  • Only outdoors

NEC Reference: NEC 240.22

Question 9: A single-phase service uses 1/0 AWG aluminum as its largest ungrounded conductor. What size aluminum grounding electrode conductor is required?

  • Aluminum 6 AWG
  • Aluminum 4 AWG
  • Copper 2 AWG
  • Copper 6 AWG

NEC Reference: NEC Table 250.66

Question 10: Lightning protection system ground terminals must generally be bonded to which grounding system?

  • The building or structure grounding electrode system
  • A distribution panelboard only
  • The service entrance only
  • Nothing -- bonding is not required

NEC Reference: NEC 250.106

Question 11: An insulated equipment grounding conductor 6 AWG or smaller is usually identified by what color?

  • Green
  • Orange
  • Brown
  • Pink

NEC Reference: NEC 250.119

Question 12: A concrete-encased grounding electrode (Ufer ground) generally must have at least what length of qualifying conductor or rebar?

  • 20 feet
  • 10 feet
  • 30 feet
  • 50 feet

NEC Reference: NEC 250.52(A)(3)

Question 13: A ground rod must be driven so that how much of its length remains below grade?

  • The full rod length
  • Half of the rod
  • One inch
  • None -- it can stick straight up

NEC Reference: NEC 250.53(G)

Question 14: Where two ground rods are used, they should be spaced at least how far apart?

  • 6 feet apart
  • 1 foot apart
  • 50 feet apart
  • Touching each other

NEC Reference: NEC 250.53(A)(3)

Question 15: Metal water piping in a building must be bonded to what?

  • The service equipment or grounding electrode system
  • Nothing at all
  • The nearest fence
  • A telephone pole

NEC Reference: NEC 250.104(A)

Question 16: A grounding electrode conductor may be made of what material?

  • Copper, aluminum, or copper-clad aluminum
  • Plastic only
  • Wood
  • Rubber

NEC Reference: NEC 250.62

Question 17: The main bonding jumper connects the equipment grounding conductor to the grounded conductor at what location?

  • At the service
  • At every subpanel equally
  • Nowhere -- it is optional
  • At the utility pole

NEC Reference: NEC 250.28

Question 18: A service uses 2 AWG copper as its largest ungrounded conductor. What size copper grounding electrode conductor is required?

  • 8 AWG
  • 10 AWG
  • 6 AWG
  • 4 AWG

NEC Reference: NEC Table 250.66

Question 19: A circuit is protected by a 60-ampere overcurrent device. What is the minimum size copper equipment grounding conductor required?

  • 10 AWG
  • 12 AWG
  • 8 AWG
  • 14 AWG

NEC Reference: NEC Table 250.122

Question 20: Grounding connections generally must be made using what type of fittings or methods?

  • Listed pressure connectors or clamps
  • Any random splice, no listing needed
  • Electrical tape only
  • Nothing is required

NEC Reference: NEC 250.8

Question 21: The bonding jumper size for the water piping system is based on what?

  • The largest ungrounded service conductor
  • The pipe color
  • The homeowner's preference
  • Nothing -- any size works

NEC Reference: NEC Table 250.66

Question 22: An isolated ground receptacle is generally used to reduce what, for sensitive electronic equipment?

  • Electrical noise
  • The room temperature
  • The building's square footage
  • Nothing useful

NEC Reference: NEC 250.146(D)

Question 23: An intersystem bonding termination is generally provided at the service to bond what type of systems to the building grounding electrode system?

  • Communications systems
  • Nothing -- it has no purpose
  • Only gas piping
  • Only HVAC ductwork

NEC Reference: NEC 250.94

Question 24: A metal underground water pipe in direct contact with earth for at least 10 feet is used as a grounding electrode. What additional requirement applies?

  • It must be supplemented by an additional electrode
  • No supplement is ever required
  • It must be removed instead
  • It must be painted

NEC Reference: NEC 250.53(D)(2)

Question 25: Metal piping systems (other than water piping) that may become energized, such as gas piping, generally must be what?

  • Bonded to the equipment grounding system
  • Left completely isolated
  • Removed entirely
  • Painted a bright color only

NEC Reference: NEC 250.104(B)

Question 26: A portable generator that only supplies equipment mounted on the generator, or cord-and-plug equipment through its own receptacles, may be exempt from what requirement?

  • A grounding electrode connection
  • Any grounding at all, permanently
  • A fuel cap
  • An oil change

NEC Reference: NEC 250.34

Question 27: A grounding electrode conductor exposed to physical damage must generally be what?

  • Protected, such as in a raceway
  • Left completely bare and exposed
  • Removed entirely
  • Painted red

NEC Reference: NEC 250.64(B)

Question 28: A separately derived system, such as the secondary of a step-down transformer, requires what type of bonding jumper at the source?

  • A system bonding jumper
  • No bonding jumper at all
  • A telephone wire
  • A padlock

NEC Reference: NEC 250.30(A)(1)

Question 29: Where multiple grounding electrodes are present at a building, what does NEC 250.50 require?

  • All present qualifying electrodes must be bonded together
  • Only one electrode may ever be used
  • They must be kept completely separate
  • Nothing -- bonding is optional

NEC Reference: NEC 250.50

Question 30: Which of the following can serve as an equipment grounding conductor, per NEC 250.118?

  • A copper conductor, or in some cases the metal raceway
  • A garden hose
  • A wooden dowel
  • Nothing is ever permitted

NEC Reference: NEC 250.118

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)