NEC CODE NEC 2026

NEC 2026 Practice Test - Service Entrance Diagram

Short test built around a one-family dwelling service entrance diagram. Tests reading a one-line and applying NEC 2026 emergency disconnect, grounding, and metering rules.

Share this test
Want the real exam format? Take a free full-length exam for your state

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 38 min for 25 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This NEC 2026 Practice Test - Service Entrance Diagram has 25 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 25 multiple-choice, one correct answer each
25
Questions
38 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2026
NEC 2026 Practice Test - Service Entrance Diagram
Q1 / 25
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
One tap, no sign-up.
Share your score
Share it and get the NEC 2026 Article Quick Reference free, right now.
Unlocked — thanks for sharing! 🎉
Get the NEC 2026 Article Quick Reference
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Practice Test - Service Entrance Diagram — Question List

Question 1: In the diagram, the device labeled "EMERGENCY DISCONNECT 230.85" is mounted on the exterior wall between the meter and the indoor service panel. Per the 2026 NEC, what additional marking phrase must appear on this device?

One-family dwelling service entrance: utility pole, drop, weatherhead, meter, exterior emergency disconnect, and indoor service panel with grounding electrode
One-family dwelling service entrance: utility pole, drop, weatherhead, meter, exterior emergency disconnect, and indoor service panel with grounding electrode
  • "EMERGENCY DISCONNECT, METER DISCONNECT"
  • "EMERGENCY DISCONNECT, SERVICE DISCONNECT"
  • "EMERGENCY DISCONNECT, NOT SERVICE EQUIPMENT"
  • No additional marking is required

NEC Reference: NEC 2026 — 230.85(E)(3)

Question 2: In the diagram, the grounding electrode conductor runs from the service panel only to a ground rod. The service conductors are 4/0 AWG copper. What is the largest GEC size the NEC requires for that rod connection?

Service entrance with grounding electrode conductor running from the panel to a ground rod outside the dwelling
Service entrance with grounding electrode conductor running from the panel to a ground rod outside the dwelling
  • 2 AWG copper
  • 4 AWG copper
  • 6 AWG copper
  • 8 AWG copper

NEC Reference: NEC 2026 — 250.66(A)

Question 3: In the diagram, three conductors leave the meter and feed the emergency disconnect. Per the 2026 NEC 230.85, the emergency disconnect must simultaneously open which of these conductors?

Three service conductors entering an exterior emergency disconnect labeled per NEC 230.85
Three service conductors entering an exterior emergency disconnect labeled per NEC 230.85
  • All three conductors
  • Only the two ungrounded conductors
  • Only the grounded (neutral) conductor
  • None — the disconnect is mechanical only

NEC Reference: NEC 2026 — 230.85

Question 4: A meter disconnect is used to meet the 230.85 emergency disconnect requirement. How must it be marked?

  • EMERGENCY DISCONNECT, SERVICE DISCONNECT
  • UTILITY USE ONLY
  • MAIN BREAKER ONLY
  • EMERGENCY DISCONNECT, METER DISCONNECT, NOT SERVICE EQUIPMENT

NEC Reference: NEC 2026 — 230.85

Question 5: The dwelling in the diagram has its main breaker inside the indoor service panel. With the exterior emergency disconnect installed per 230.85, can the indoor main breaker continue to serve as the service disconnect for the purposes of 230.70?

Dwelling with exterior emergency disconnect feeding an indoor service panel that contains the main breaker
Dwelling with exterior emergency disconnect feeding an indoor service panel that contains the main breaker
  • Yes — the two requirements are independent
  • No — only the exterior device can be the service disconnect
  • Only if the indoor breaker is rated above 200A
  • Only with utility approval

NEC Reference: NEC 2026 — 230.70 and 230.85

Question 6: In the panel schedule shown, circuits 1 and 2 are labeled "Kitchen SABC #1" and "Kitchen SABC #2". Per the 2026 NEC, what minimum number of small-appliance branch circuits must be provided in a dwelling kitchen?

Residential panel schedule with two small-appliance branch circuits labeled SABC
Residential panel schedule with two small-appliance branch circuits labeled SABC
  • One
  • Two
  • Three
  • Four

NEC Reference: NEC 2026 — 210.11(C)(1)

Question 7: In the panel schedule, circuit 27/29 is a 50A two-pole "EV Charger". Per the 2026 NEC 625.41, the branch-circuit conductors must be sized at:

Panel schedule with a 50A two-pole EV charger branch circuit
Panel schedule with a 50A two-pole EV charger branch circuit
  • 100% of the EVSE rating
  • 125% of the EVSE rating
  • 150% of the EVSE rating
  • Exactly the EVSE rating

NEC Reference: NEC 2026 — 625.41

Question 8: In the EMT cross-section shown, three 6 AWG THWN and one 10 AWG THWN conductor are in 1-inch EMT (total area 0.864 sq in). Is the fill within Chapter 9 limits?

Cross-section of a 1-inch EMT containing three 6 AWG THWN ungrounded conductors and a 10 AWG THWN equipment grounding conductor
Cross-section of a 1-inch EMT containing three 6 AWG THWN ungrounded conductors and a 10 AWG THWN equipment grounding conductor
  • Only if the EGC is upsized to 8 AWG
  • Yes, about 0.173 sq in is below the 0.346 sq in limit
  • No, the fill exceeds 40%
  • No, four conductors exceed the count limit

NEC Reference: NEC 2026 — Chapter 9, Table 1

Question 9: In the cross-section, the EMT carries three current-carrying conductors. Per Table 310.15(C)(1) of the 2026 NEC, what ampacity adjustment factor applies?

EMT containing three current-carrying conductors used to determine the ampacity adjustment factor
EMT containing three current-carrying conductors used to determine the ampacity adjustment factor
  • 80%
  • 100% (no adjustment for 3 CCCs)
  • 70%
  • 50%

NEC Reference: NEC 2026 — Table 310.15(C)(1)

Question 10: The one-line diagram shows a 10HP, 3-phase, 230V motor with FLC of 28A from Table 430.250. Per 430.22 of the 2026 NEC, what is the minimum branch-circuit conductor ampacity required?

One-line diagram of a 10HP three-phase 230V motor branch circuit with disconnect, controller, overload relay, and motor
One-line diagram of a 10HP three-phase 230V motor branch circuit with disconnect, controller, overload relay, and motor
  • 28A
  • 35A
  • 45A
  • 70A

NEC Reference: NEC 2026 — 430.22 / Table 430.250

Question 11: In the same motor circuit, what is the maximum size of an inverse-time circuit breaker permitted as the branch-circuit short-circuit and ground-fault protective device?

Motor branch circuit with inverse-time circuit breaker as SCGFPD
Motor branch circuit with inverse-time circuit breaker as SCGFPD
  • 50A
  • 60A
  • 70A
  • 100A

NEC Reference: NEC 2026 — Table 430.52(C)(1)

Question 12: The diagram shows the disconnect "in sight of the controller". Per the 2026 NEC 430.102, the disconnect must:

Motor branch circuit showing disconnect in sight of the controller
Motor branch circuit showing disconnect in sight of the controller
  • Be in sight from both the motor location and the driven machinery
  • Be in sight only from the controller
  • Be located at the service equipment only
  • No location requirement applies

NEC Reference: NEC 2026 — 430.102(B)

Question 13: For the same 10HP motor with marked service factor 1.15, what is the maximum overload protection setting (initial) allowed per the 2026 NEC 430.32?

Motor branch circuit with overload relay sized at 125% of FLA
Motor branch circuit with overload relay sized at 125% of FLA
  • 100% of nameplate FLA
  • 115% of nameplate FLA
  • 125% of nameplate FLA
  • 250% of nameplate FLA

NEC Reference: NEC 2026 — 430.32(A)(1)

Question 14: In the panel schedule, circuits 11–14 are labeled "(AFCI)". Per 210.12 of the 2026 NEC, AFCI protection is required for branch circuits supplying outlets in which dwelling rooms?

Residential panel schedule with bedroom and living/dining circuits labeled AFCI
Residential panel schedule with bedroom and living/dining circuits labeled AFCI
  • Bedrooms, living rooms, dining rooms, hallways, and similar
  • Bathrooms only
  • Garage receptacles only
  • Service-entrance feeders

NEC Reference: NEC 2026 — 210.12(A)

Question 15: Circuit 15 is labeled "Outdoor Recep (GFCI)". Per the 2026 NEC, the receptacle on the outside of a dwelling must:

Panel schedule with outdoor receptacle branch circuit labeled GFCI
Panel schedule with outdoor receptacle branch circuit labeled GFCI
  • Be GFCI protected and accessible from grade level
  • Be installed only at the back of the dwelling
  • Be installed at least 6 ft above grade
  • Be a 30A circuit

NEC Reference: NEC 2026 — 210.52(E) / 210.8(A)(3)

Question 16: A service entrance like the one in the dwelling diagram has a meter base and an indoor 200A panel. If the service-entrance conductors are 4/0 aluminum, what is the GEC size to a single ground rod?

  • 4 AWG aluminum (or 6 AWG copper)
  • 2 AWG aluminum
  • 1/0 AWG aluminum
  • 4/0 AWG aluminum to match the service

NEC Reference: NEC 2026 — 250.66(A)

Question 17: For the dwelling in the diagram, the indoor service panel is the service equipment. What does 230.66 require of it?

  • It must be listed and marked as suitable for use as service equipment
  • It must be located outdoors
  • It must be supplied through a meter disconnect
  • It must have no more than 20 circuits

NEC Reference: NEC 2026 — 230.66

Question 18: In the panel schedule, the electric dryer circuit (240 V, 2-pole) is GFCI protected. Which NEC section requires GFCI protection for the dryer outlet in a dwelling?

  • 215.9, feeder ground-fault protection
  • 422.5(A)(7), which covers dishwashers
  • No GFCI is required for electric dryers
  • 210.8, the dwelling GFCI rules (including the specific-appliance list)

NEC Reference: NEC 2026 — 210.8

Question 19: In the conduit cross-section, the EGC is shown as a 10 AWG copper conductor. Per 250.122 of the 2026 NEC, the minimum EGC size is determined by:

EMT cross-section showing a 10 AWG copper EGC alongside the ungrounded conductors
EMT cross-section showing a 10 AWG copper EGC alongside the ungrounded conductors
  • The rating of the upstream OCPD per Table 250.122
  • The size of the largest ungrounded conductor
  • The number of conductors in the raceway
  • The length of the raceway

NEC Reference: NEC 2026 — Table 250.122

Question 20: The dwelling in the service-entrance diagram has a 200A panel with 40 circuit positions. Per the 2026 NEC, the maximum number of overcurrent devices in a panelboard is:

  • The number marked on the panelboard listing label
  • Always 42, by NEC mandate
  • Always 30, by NEC mandate
  • No limit at all

NEC Reference: NEC 2026 — 408.54

Question 21: In the panel schedule, circuit 17/19 is the "A/C Condenser (240V 2P)" on a 40A breaker. The compressor nameplate MCA is 32A and MOCP is 50A. Per 440.22(A) of the 2026 NEC, is the 40A breaker acceptable?

Panel schedule showing a 40A two-pole breaker for the A/C condenser branch circuit
Panel schedule showing a 40A two-pole breaker for the A/C condenser branch circuit
  • Yes — 40A is at or above MCA and at or below the MOCP
  • No — 40A exceeds the MOCP
  • No — only the exact MOCP value is permitted
  • Only acceptable for inverse-time CBs, not fuses

NEC Reference: NEC 2026 — 440.4(B) / 440.22(C)

Question 22: The conduit shown carries a 120/240 V single-phase, 3-wire feeder (two ungrounded conductors and a neutral). Is the neutral counted as a current-carrying conductor for adjustment factors?

EMT cross-section showing three 6 AWG THWN conductors used to determine current-carrying neutral status
EMT cross-section showing three 6 AWG THWN conductors used to determine current-carrying neutral status
  • Yes, always
  • Only if it is bonded at both ends
  • No, it carries only the unbalanced current of the two ungrounded conductors
  • Yes, whenever the loads are non-linear

NEC Reference: NEC 2026 — 310.15(E)

Question 23: The motor circuit one-line shows the OL relay between the controller and the motor. Per the 2026 NEC, motor running overload protection may be omitted only when:

Motor branch circuit showing the overload relay between controller and motor
Motor branch circuit showing the overload relay between controller and motor
  • The motor is small enough to fall under the 430.32(D)/(E) exemptions
  • The disconnect is in sight of the controller
  • The branch-circuit OCPD is sized at 250% of FLC
  • The motor is permanently energized

NEC Reference: NEC 2026 — 430.32

Question 24: In the panel schedule, the 200A main breaker feeds a single-phase 120/240V load center. Per 230.79 of the 2026 NEC, the minimum permitted service disconnect rating for a one-family dwelling with a calculated service load of 100A is:

Panel schedule showing a 200A main breaker exceeding the 100A minimum required by 230.79
Panel schedule showing a 200A main breaker exceeding the 100A minimum required by 230.79
  • 60A
  • 100A
  • 150A
  • 200A

NEC Reference: NEC 2026 — 230.79(C)

Question 25: Reading the service entrance diagram together with the panel schedule, the indoor service panel functions as which combination of equipment per the 2026 NEC?

  • Service equipment + service disconnect + branch-circuit panelboard
  • Emergency disconnect only
  • A subpanel only
  • A motor controller

NEC Reference: NEC 2026 — 230.66 / 230.70 / 230.85

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions25
Time limit38 min
Pass score70%
Code editionNEC 2026
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)