NEC_PRACTICE NEC 2023

NEC 2023 Code Questions Practice Test 6

Free NEC 2023 practice test with 30 questions covering kitchen countertop receptacle spacing, the fire pump exception to the one-service rule, cartridge fuse marking, equipment grounding conductors for separate buildings, and induced currents in ferrous enclosures. Full NEC 2023 references.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

How to Use This Practice Test

This NEC 2023 Code Questions Practice Test 6 has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Mixed-format test — questions jump between topics just like the real exam. Don't spend more than 90 seconds on any one question.

  • Topics covered: All NEC chapters — branch circuits, grounding, conductors, wiring methods, motors, and more.
  • Passing score: Aim for 80%+ consistently before scheduling your exam.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2023
NEC 2023 Code Questions Practice Test 6
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2023 Code Questions Practice Test 6 — Question List

Question 1: What is the minimum working space that should be provided for switch boards and panel boards?

  • 6 1/2 feet
  • 8 1/2 feet
  • 4 1/2 feet
  • 2 1/2 feet

NEC Reference: NEC 110.26(A)(3)

Question 2: Which of the following equation is suitable to find the voltage drop in the circuit?

  • VD = IR
  • VD = I / R
  • VD = P / I
  • VD = I <sup>2</sup> R

Question 3: What is the wattage of the 120 volts single phase motor with a resistance of 20 ohms?

  • 720 Watts
  • 520 Watts
  • 2400 watts
  • 6 watts

Question 4: Over current devices must not be located on ..............

  • Over the steps of stairway
  • Above the panel board
  • Bath Rooms
  • Wet areas

Question 5: The primary current rating of a motor generator arc welder is 30 A with a duty cycle of 30 %? what is the minimum size branch circuit conductor for welder?

  • 12 AWG
  • 10 AWG
  • 14 AWG
  • 8 AWG

NEC Reference: NEC 630.11

Question 6: The maximum over current protection used for resistance type heating elements in electric space-heating equipment?

  • 60 amperes
  • 40 amperes
  • 70 amperes
  • 20 amperes

NEC Reference: NEC 424.22(B)

Question 7: For a single family dwelling unit , what is the minimum allowable rating of a 3 wire service entrance conductors?

  • 100 amperes
  • 150 amperes
  • 200 amperes
  • 180 amperes

NEC Reference: NEC 230.42(B)

Question 8: An electric heater with a resistance of 18 ohms which draws a current of 7 amps. what is the minimum wattage of electric heater?

  • 882 watts.
  • 126 watts
  • 723 watts
  • 184 watts

Question 9: What is the maximum branch circuit load for a 10 kW single electric range in a dwelling unit?

  • 8 kW
  • 10 KW
  • 7 KW
  • 6 KW

NEC Reference: NEC Table 220.55

Question 10: Which of the following must be provided near electronic equipment which are exposed to physical damage?

  • warning signs
  • working space
  • enclosures or gaurds
  • sufficient head room

NEC Reference: NEC 110.27(B)

Question 11: Along a kitchen countertop wall space, receptacle outlets must be installed so that no point along the countertop is more than how far from a receptacle outlet?

  • 24 inches
  • 6 feet
  • 12 inches
  • 10 feet

NEC Reference: NEC 210.52(C)(1)

Question 12: A building is permitted to have more than one service where special conditions apply. Which of the following is a recognized exception to the general one-service rule?

  • A fire pump
  • A ceiling fan
  • A general-purpose lighting circuit
  • A toaster

NEC Reference: NEC 230.2(A)

Question 13: A cartridge fuse must be plainly marked, either by printing on the fuse barrel or by a label, showing the ampere rating and:

  • Voltage rating and interrupting rating
  • The installer's birthday
  • No marking is required at all
  • Only the color of the fuse

NEC Reference: NEC 240.60(D)

Question 14: For a new feeder installed to a separate building or structure, an equipment grounding conductor must be:

  • Run with the feeder conductors
  • Omitted entirely for new installations
  • Replaced with a garden hose bib connection
  • Never required under any condition

NEC Reference: NEC 250.32(B)

Question 15: An equipment grounding conductor must not be used as a grounding electrode conductor, except where it:

  • Meets the requirements of both conductor types where specifically permitted
  • This is always permitted with no restriction
  • It is never permitted under any circumstance
  • It has no relationship to grounding electrode conductors

NEC Reference: NEC 250.121

Question 16: Where a single conductor carrying AC current passes through a ferrous metal enclosure, wall, or barrier by itself (without the other conductors of the circuit), the induced currents can cause:

  • Excessive heating of the ferrous metal
  • No effect at all
  • A decrease in temperature
  • Increased conductor ampacity

NEC Reference: NEC 300.20

Question 17: A pull box or junction box installed with a plaster or drywall finish must have its cover installed so that it is:

  • Flush with, or set back no more than 1/4 inch
  • Buried inside the wall permanently
  • Sealed shut with no access at all
  • It does not matter

NEC Reference: NEC 314.28(E)

Question 18: The ampacity of Type MC cable conductors is determined using the same ampacity tables as:

  • Conductors in a raceway
  • No table applies to MC cable
  • It is a fixed 15 amperes regardless of size
  • Fixture wire only

NEC Reference: NEC 330.80

Question 19: Auxiliary gutters are used to supplement wiring space at meter centers, distribution centers, panelboards, and similar equipment, but must not extend a distance greater than:

  • 30 feet
  • 5 feet
  • 100 feet
  • There is no limit

NEC Reference: NEC 366.12

Question 20: The minimum wire-bending space at panelboard terminals and clearance between bus bars must be determined in accordance with:

  • NEC Table 312.6(A) and 312.6(B)
  • No table applies to bus clearance
  • The installer's personal preference
  • NEC Table 220.12

NEC Reference: NEC 408.18

Question 21: A recessed incandescent luminaire must have thermal protection to reduce the risk of fire due to excessive temperature, integral to:

  • The luminaire itself
  • A separate device installed a year later
  • No thermal protection is ever required
  • The branch-circuit breaker only

NEC Reference: NEC 410.130(E)

Question 22: A cord-and-plug connection is generally permitted in lieu of a direct connection for an appliance where the appliance is:

  • Identified for flexible cord connection, or to facilitate service
  • Never permitted for any appliance
  • Only for appliances rated over 50 kW
  • It has no bearing on cord-and-plug use

NEC Reference: NEC 422.16(A)

Question 23: Per NEC Article 100, a "branch circuit" is defined as the circuit conductors between the final overcurrent device protecting the circuit and:

  • The outlet(s)
  • The utility transformer
  • Another overcurrent device only
  • The grounding electrode

NEC Reference: NEC Article 100

Question 24: An automatic restarting of a motor after shutdown by an overload protective device is:

  • Generally prohibited, unless listed for that use
  • Always required for every motor
  • Never addressed by the NEC
  • Required only for motors under 1 hp

NEC Reference: NEC 430.43

Question 25: When a hermetic motor-compressor is marked with both a rated-load current and a branch-circuit selection current, which value must be used for branch-circuit conductor sizing?

  • Whichever value is greater
  • Whichever value is smaller, always
  • Neither value is used
  • The average of the two

NEC Reference: NEC 440.6(A)

Question 26: Article 500 references other NFPA documents for the classification of specific hazardous locations, such as the classification of flammable liquid storage facilities. This kind of cross-referencing is addressed in:

  • NEC 500.4
  • NEC 90.1
  • NEC 300.1
  • No such reference exists

NEC Reference: NEC 500.4

Question 27: In a Class I hazardous location, where a flexible connection is used, the equipment bonding jumper must not rely solely on:

  • The threaded connection points of the flexible fitting
  • This is not a concern in hazardous locations
  • A bonding jumper is never used in Class I locations
  • Duct tape wrapped around the fitting

NEC Reference: NEC 501.30(B)

Question 28: Luminaires in a Class I, Division 2 location that are subject to physical damage must be protected by a suitable guard, or by:

  • Location that protects it from damage
  • No protection is ever provided
  • Wrapping the fixture in plastic
  • Painting it a bright color only

NEC Reference: NEC 501.130(B)

Question 29: The mobile home service equipment or main circuit breaker/fuses (disconnecting means) must have a minimum rating of:

  • 100 amperes
  • 30 amperes
  • 50 amperes
  • 15 amperes

NEC Reference: NEC 550.32(A)

Question 30: Feeder and service loads for marinas and boatyards are calculated using demand factors from NEC Table 555.12, which generally decrease as:

  • The number of berths/receptacles increases
  • The number of berths decreases
  • Demand factors are always 100%, with no variation
  • It has no relationship to berth count

NEC Reference: NEC Table 555.12

EXAM CARD NEC_PRACTICE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)