JOURNEYMAN NEC 2020

NEC 2020 Journeyman Practice Test 2

Free Online Journeyman Electrician Practice Test — NEC 2020 Edition 2This free 30-question practice test covers branch-circuit rules, overcurrent protection, GFCI and AFCI requirements, and basic load-calculation concepts. All questions and explanations are based on the 2020 NEC.

TOPICS COVERED
journeyman electrician

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account required. All questions include detailed explanations and NEC references.

Most state Journeyman exams have 80–100 questions covering NEC code, wiring methods, branch circuits, motor controls, and load calculations.

Most states require a 70–75% passing score. This practice test uses the same 70% pass threshold so you know where you stand.

Questions are written to the 2020 NEC. Check your state licensing board to confirm which edition your state has adopted.

How to Use This Practice Test

This NEC 2020 Journeyman Practice Test 2 has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: This is an open-book exam — tab your NEC index and Articles 210, 250, and 430 before you start.

  • Topics covered: Branch circuits, grounding, wiring methods, load calculations, and motors.
  • Passing score: 70–75% (most states). Aim for 80% on practice tests so the real exam feels easy.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

JOURNEYMAN · NEC 2020
NEC 2020 Journeyman Practice Test 2
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2020 Journeyman Practice Test 2 — Question List

Question 1: Per NEC Article 100, an "outlet" is defined as a point on the wiring system at which current is taken to supply what?

  • Utilization equipment
  • The utility transformer
  • The grounding electrode
  • The service point only

NEC Reference: NEC Article 100

Question 2: Per NEC Article 100, a "device" is defined as a unit of an electrical system that carries or controls electric energy as its principal function, but does NOT do what?

  • Consume (utilize) the energy
  • Carry current at all
  • Mount in a box
  • Have a rated voltage

NEC Reference: NEC Article 100

Question 3: Per NEC 110.3(B), listed or labeled equipment must be installed and used in accordance with:

  • Any instructions included in the listing or labeling
  • Whatever the installer personally prefers
  • The lowest-cost method available
  • No documentation is ever required

NEC Reference: NEC 110.3(B)

Question 4: Where branch circuits of more than one voltage system share the same raceway, box, or enclosure, per NEC 210.5(C), the ungrounded conductors of each system must be:

  • Left unmarked, since electricians should already know the systems
  • Identified by system at each termination/connection point
  • Run in entirely separate buildings only
  • Always the same color for every system

NEC Reference: NEC 210.5(C)

Question 5: Per NEC 210.11(A), the minimum number of branch circuits required for an installation is determined from:

  • The total computed load, per Article 220, and the rating of the circuits used
  • A random guess by the installer
  • The number of rooms in the building only
  • The building's square footage alone, with no other factor

NEC Reference: NEC 210.11(A)

Question 6: A branch circuit supplies both continuous and noncontinuous loads. Per NEC 210.20(A), the overcurrent device rating must be not less than what, without applying any adjustment or correction factors?

  • The noncontinuous load plus 125% of the continuous load
  • 100% of both loads combined, with no adjustment
  • 125% of the noncontinuous load only
  • 50% of the total connected load

NEC Reference: NEC 210.20(A)

Question 7: Per NEC 210.23(A)(1), a single receptacle installed on an individual branch circuit must have an ampere rating of:

  • Not less than the branch-circuit rating
  • Always exactly 15 amperes
  • Half the branch-circuit rating
  • There is no requirement at all

NEC Reference: NEC 210.23(A)(1)

Question 8: Per NEC 225.18, overhead branch-circuit and feeder conductors of 0-150 volts to ground, over an area subject only to pedestrian traffic, must maintain a minimum vertical clearance from final grade of:

  • 8 feet
  • 10 feet
  • 12 feet
  • 18 feet

NEC Reference: NEC 225.18

Question 9: Besides the common ratings listed in NEC 240.6(A), NEC 240.6(B) recognizes additional standard ampere ratings for fuses, including which of the following small sizes?

  • 1, 3, 6, and 10 amperes
  • 11, 13, 17, and 19 amperes
  • 2, 4, 8, and 16 amperes
  • There are no additional standard fuse ratings

NEC Reference: NEC 240.6(B)

Question 10: A calculated conductor ampacity does not correspond to a standard overcurrent device size. Per NEC 240.4(B), rounding up to the next higher standard rating is generally permitted, provided the device is rated no more than what maximum ampere value, among other conditions?

  • 400 amperes
  • 800 amperes
  • 1200 amperes
  • There is no maximum

NEC Reference: NEC 240.4(B)

Question 11: Per NEC 240.5, flexible cords and fixture wires must generally be protected against overcurrent based on what?

  • Their own ampacity, per Table 240.5
  • The main service rating only
  • Nothing — they never need overcurrent protection
  • The largest breaker available in the panel

NEC Reference: NEC 240.5

Question 12: Per NEC 240.15(A), an overcurrent device must generally be installed in series with:

  • Each ungrounded conductor
  • The grounded (neutral) conductor only
  • The equipment grounding conductor only
  • No conductor — it is optional

NEC Reference: NEC 240.15(A)

Question 13: Per NEC 250.20(B), a 120/240-volt, single-phase, 3-wire alternating-current system supplying the premises wiring of a dwelling must generally be:

  • Grounded
  • Ungrounded, by default
  • Isolated from earth entirely
  • Grounded only if the owner requests it

NEC Reference: NEC 250.20(B)

Question 14: Per NEC 300.5(D)(4), direct-buried conductors or cables emerging from the ground must be protected by an enclosure or raceway, from the required burial depth up to a point at least how high above finished grade?

  • 4 feet
  • 6 feet
  • 8 feet
  • 10 feet

NEC Reference: NEC 300.5(D)(4)

Question 15: A cable is installed running parallel to a wood framing member. Per NEC 300.4(D), the cable must be kept at least how far from the nearest edge of the framing member, unless protected by a steel plate?

  • 1/2 inch
  • 1 1/4 inch
  • 2 1/2 inch
  • 6 inches

NEC Reference: NEC 300.4(D)

Question 16: Per NEC 400.12, flexible cords and cables are generally NOT permitted to be used as a substitute for what?

  • The fixed wiring of a structure
  • A portable lamp cord
  • An extension cord used temporarily outdoors
  • A cord supplying a listed appliance

NEC Reference: NEC 400.12

Question 17: Per NEC 400.10, which of the following is a use generally permitted for flexible cords and cables?

  • Connecting a portable lamp or appliance
  • Permanent wiring of a finished wall
  • Wiring embedded in poured concrete
  • Replacing service-entrance conductors

NEC Reference: NEC 400.10

Question 18: Per NEC 404.2(B), a grounded (neutral) conductor must generally be provided at which of the following?

  • Most switch locations controlling lighting loads
  • Only three-way switches
  • Only switches located outdoors
  • Nowhere — a neutral is never needed at a switch

NEC Reference: NEC 404.2(B)

Question 19: An existing outlet box has no equipment grounding conductor. Per NEC 406.4(D), which replacement option is generally permitted, marked "No Equipment Ground"?

  • A GFCI-type receptacle marked "No Equipment Ground"
  • A standard grounding-type receptacle with no other change
  • Nothing may ever be installed at that outlet again
  • A receptacle with the grounding pin removed

NEC Reference: NEC 406.4(D)

Question 20: Per NEC 408.36, a panelboard must generally be protected by an overcurrent device having a rating not greater than:

  • The rating of the panelboard
  • Twice the rating of the panelboard
  • There is no rating relationship required
  • Half the rating of the panelboard, always

NEC Reference: NEC 408.36

Question 21: Per NEC 408.4(A), every circuit and circuit modification must be legibly identified as to its clear, evident, and specific purpose on:

  • A circuit directory at the panelboard
  • A note left with the homeowner only, not at the panel
  • Nothing — labeling is optional
  • The electrician's personal notebook only

NEC Reference: NEC 408.4(A)

Question 22: Per NEC 404.9(B), a snap switch with a metal mounting yoke installed in a grounded metal box must generally be:

  • Left ungrounded, since switches carry little current
  • Effectively grounded
  • Insulated from the box entirely
  • Bonded to the water pipe directly, bypassing the box

NEC Reference: NEC 404.9(B)

Question 23: A two-family dwelling has a 240-volt outdoor receptacle for a portable generator connection. Per the 2020 NEC, does NEC 210.8(A)(3) require GFCI protection for this specific receptacle?

  • No, not under the 2020 scope, which covers only 125-volt outdoor receptacles
  • Yes, all outdoor receptacles of any voltage were already covered in 2020
  • Only if the generator is gasoline powered
  • GFCI protection has never applied to outdoor receptacles

NEC Reference: NEC 210.8(A)(3)

Question 24: In a dwelling unit, per NEC 220.14(J), general-use 15- and 20-ampere receptacle outlets are generally accounted for by which load in a service or feeder calculation?

  • The general lighting load (3 VA per square foot)
  • A separate 1500 VA load per receptacle
  • A separate 180 VA load per receptacle, as in commercial buildings
  • They are never counted in any calculation

NEC Reference: NEC 220.14(J)

Question 25: Per NEC 225.30, a building or structure supplied by feeders or branch circuits from another building or structure on the same property is generally supplied by how many such feeders or branch circuits, absent a listed exception?

  • One
  • Exactly three, always
  • As many as convenient, with no limit
  • Zero — a separate structure cannot be fed by a feeder

NEC Reference: NEC 225.30

Question 26: Per NEC 250.86, metal enclosures and raceways installed for conductors other than service conductors must generally be:

  • Grounded
  • Left ungrounded in all cases
  • Painted rather than grounded
  • Insulated from earth intentionally

NEC Reference: NEC 250.86

Question 27: Per NEC 210.8(A)(1), all 125-volt, 15- and 20-ampere receptacles installed in dwelling unit bathrooms must have what type of protection?

  • GFCI protection
  • AFCI protection only
  • No protection is required
  • A dedicated 50-ampere circuit

NEC Reference: NEC 210.8(A)(1)

Question 28: Per NEC 210.12(A), 120-volt, 15- and 20-ampere branch circuits supplying outlets in dwelling unit kitchens and laundry areas generally require what protection?

  • AFCI protection
  • No protection is required
  • GFCI protection only, never AFCI
  • A padlock on the panel door

NEC Reference: NEC 210.12(A)

Question 29: Per NEC 210.12(B), when a receptacle outlet is replaced or a branch circuit is extended in an area of an existing dwelling that would otherwise require AFCI protection under 210.12(A), what must generally be done?

  • AFCI protection must generally be provided
  • Nothing — existing circuits are always exempt
  • The circuit must be entirely abandoned
  • GFCI protection is substituted automatically, with no other option

NEC Reference: NEC 210.12(B)

Question 30: Per NEC 220.52(A), each 20-ampere small-appliance branch circuit in a dwelling unit is counted at how many volt-amperes for feeder and service load calculation purposes?

  • 1,500 VA
  • 1,000 VA
  • 3,000 VA
  • 750 VA

NEC Reference: NEC 220.52(A)

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
EXAM CARD JOURNEYMAN
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)