Free Online Journeyman Electrician Practice Test — NEC 2026 Edition 6This free 25-question practice test covers conductors and ampacity: reading Table 310.16, ambient temperature correction, adjustment for more than three current-carrying conductors, termination temperature limits, conductor identification and voltage drop math.

Share this test
Want the real exam format? Take a free full-length exam for your state
TOPICS COVERED
journeyman electrician

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 38 min for 25 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account required. All questions include detailed explanations and NEC references.

Most state Journeyman exams have 80–100 questions covering NEC code, wiring methods, branch circuits, motor controls, and load calculations.

Most states require a 70–75% passing score. This practice test uses the same 70% pass threshold so you know where you stand.

Questions are written to the 2026 NEC. Check your state licensing board to confirm which edition your state has adopted.

Before You Start

  • 25 questions, multiple choice
  • 37½ minutes, pass mark 70% (18 correct)
  • Keep Table 310.16, the ambient correction table and Table 310.15(C)(1) open
25
Questions
38 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

JOURNEYMAN · NEC 2026
NEC 2026 Journeyman Practice Test 6
Q1 / 25
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
Rate it and add a quick comment. No sign-up.
Tap one to send it now:
Share your score
Share it and get the Journeyman Electrician Cheat Sheet — NEC 2026 free, right now.
Unlocked — thanks for sharing! 🎉
Get the Journeyman Electrician Cheat Sheet — NEC 2026
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Journeyman Practice Test 6 — Question List

Question 1: Per NEC Table 310.16, what is the 75°C ampacity of 1/0 AWG copper?

  • 170 amperes
  • 150 amperes
  • 125 amperes
  • 145 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 2: Per NEC Table 310.16, what is the 75°C ampacity of 2 AWG aluminum?

  • 75 amperes
  • 100 amperes
  • 90 amperes
  • 115 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 3: Per NEC Table 310.16, what is the 90°C ampacity of 4 AWG THHN copper?

  • 70 amperes
  • 100 amperes
  • 95 amperes
  • 85 amperes

NEC Reference: NEC 2026 — Table 310.16

Question 4: A 50-ampere circuit breaker rated 75°C supplies a load. Which is the smallest THWN copper conductor that can be used, based on the 75°C column?

  • 8 AWG
  • 10 AWG
  • 4 AWG
  • 6 AWG

NEC Reference: NEC 2026 — Table 310.16 and 110.14(C)

Question 5: Four current-carrying 8 AWG THHN copper conductors are in one raceway at 30°C ambient. Using the 90°C ampacity (55 A), what is the adjusted ampacity?

  • 50 amperes
  • 38.5 amperes
  • 55 amperes
  • 44 amperes

NEC Reference: NEC 2026 — Table 310.15(C)(1)

Question 6: Three 6 AWG THHN copper conductors run through an attic at 45°C (113°F). Using the 90°C ampacity (75 A) and a correction factor of 0.87, what is the corrected ampacity?

  • 65.25 amperes
  • 75 amperes
  • 56.5 amperes
  • 61.5 amperes

NEC Reference: NEC 2026 — Table 310.15(B)(1)(1)

Question 7: Twelve current-carrying 12 AWG THHN copper conductors share a raceway. Using the 90°C ampacity of 30 A, what is the adjusted ampacity?

  • 15 amperes
  • 18 amperes
  • 24 amperes
  • 21 amperes

NEC Reference: NEC 2026 — Table 310.15(C)(1)

Question 8: Per NEC 110.14(C)(1)(a), a 90°C THHN conductor connected to a 30-ampere breaker with no termination marking must have its ampacity taken from which column?

  • 60°C
  • Any column
  • 75°C
  • 90°C

NEC Reference: NEC 2026 — 110.14(C)(1)(a)

Question 9: Per NEC 110.14(A), terminals for more than one conductor and terminals used for aluminum conductors must be:

  • Made of brass only
  • Painted
  • Identified for that use
  • Larger than 1/0

NEC Reference: NEC 2026 — 110.14(A)

Question 10: Per NEC 110.14(D), where a tightening torque is indicated as a numeric value on equipment or in the installation instructions:

  • An impact driver set to maximum must be used
  • A calibrated torque tool must be used to achieve the indicated value
  • Hand tightening is acceptable
  • The value is only a suggestion

NEC Reference: NEC 2026 — 110.14(D)

Question 11: The voltage drop formula for a single-phase circuit is VD = (2 × K × I × L) ÷ CM. What does "L" represent?

  • The load in kVA
  • The total length of both conductors
  • The one-way length of the circuit in feet
  • The number of conductors

NEC Reference: NEC 2026 — 210.19(A) Informational Note (voltage drop)

Question 12: Using VD = (2 × K × I × L) ÷ CM with K = 12.9 (copper), I = 20 A, L = 100 ft and 12 AWG (6530 cmil), what is the voltage drop?

  • About 2.5 volts
  • About 7.9 volts
  • About 12 volts
  • About 3.9 volts

NEC Reference: NEC 2026 — Chapter 9, Table 8 (voltage drop)

Question 13: The NEC Informational Notes to 210.19 and 215.2 recommend a maximum combined voltage drop on feeders and branch circuits of:

  • 5%
  • 2%
  • 3%
  • 10%

NEC Reference: NEC 2026 — 210.19(A) and 215.2(A) Informational Notes

Question 14: For a three-phase circuit, the voltage drop formula uses which multiplier instead of 2?

  • 1.732 (the square root of 3)
  • 3
  • 1.414
  • 2.5

NEC Reference: NEC 2026 — 210.19(A) Informational Note (voltage drop)

Question 15: Per NEC 200.6(A), which is an acceptable way to identify a 10 AWG grounded (neutral) conductor?

  • Red insulation with a white label
  • Green insulation
  • Continuous white or gray insulation
  • Black insulation with white tape at the ends

NEC Reference: NEC 2026 — 200.6(A)

Question 16: Per NEC 250.119(A), an insulated conductor 4 AWG or larger may be permanently re-identified as an equipment grounding conductor at each end and accessible point by:

  • Writing the word "ground" on the insulation in pencil
  • Cutting a notch in the insulation near each termination
  • Stripping the insulation, coloring the insulation green, or marking it with green tape or labels
  • Wrapping white tape around the insulation at each end

NEC Reference: NEC 2026 — 250.119(A)

Question 17: Per NEC 310.10(C), conductors used in wet locations must be:

  • Rated 60°C only, so the ampacity stays low enough in water
  • Any THHN conductor, because the nylon jacket keeps water out
  • Bare copper only, since insulation breaks down when wet
  • Moisture-impervious metal-sheathed, or a type listed for wet locations (such as THWN-2 or XHHW-2)

NEC Reference: NEC 2026 — 310.10(C)

Question 18: Per NEC 300.9, the interior of raceways installed in wet locations above grade is considered:

  • A hazardous location
  • A dry location
  • A wet location
  • A damp location

NEC Reference: NEC 2026 — 300.9

Question 19: Per NEC 310.12, the dwelling service and feeder 83% rule applies to which systems?

  • Any three-phase service that supplies a single building
  • Branch circuits and feeders in multifamily dwellings only
  • Commercial single-phase services rated up to 400 amperes
  • 120/240-volt, 3-wire single-phase dwelling services and main power feeders

NEC Reference: NEC 2026 — 310.12

Question 20: Using NEC 310.12, what is the minimum aluminum service conductor (75°C) for a 150-ampere, 120/240-volt dwelling service?

  • 3/0 AWG aluminum
  • 4/0 AWG aluminum
  • 2/0 AWG aluminum
  • 1/0 AWG aluminum

NEC Reference: NEC 2026 — 310.12

Question 21: Per NEC 310.15(C)(1), how many current-carrying conductors are in a raceway holding a 3-phase, 4-wire wye circuit feeding mostly LED lighting drivers (nonlinear loads)?

  • 5
  • 4
  • 2
  • 3

NEC Reference: NEC 2026 — 310.15(C)(1)

Question 22: Per NEC 240.4(D), a 12 AWG copper conductor with an adjusted ampacity of 24 A may be protected by a breaker of at most:

  • 25 amperes
  • 20 amperes
  • 30 amperes
  • 15 amperes

NEC Reference: NEC 2026 — 240.4(D)

Question 23: Per NEC 310.14(A), ampacities for conductors are permitted to be determined by tables or by:

  • The conductor manufacturer's catalog only
  • Engineering supervision, using the formula in 310.14(B)
  • The electrician's experience
  • The utility company

NEC Reference: NEC 2026 — 310.14(A)

Question 24: Per NEC 110.5, conductors used to carry current are copper or copper-clad aluminum unless otherwise provided. Where the conductor material is not specified, the sizes given in the Code apply to:

  • Aluminum conductors
  • Either, with no difference
  • Copper conductors
  • Copper-clad aluminum only

NEC Reference: NEC 2026 — 110.5

Question 25: Per NEC 310.16, the ampacity of 12 AWG aluminum at 75°C is 20 A. What does NEC 240.4(D) limit its overcurrent protection to?

  • 25 amperes
  • 20 amperes
  • 10 amperes
  • 15 amperes

NEC Reference: NEC 2026 — 240.4(D)(4)

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
EXAM CARD JOURNEYMAN
Questions25
Time limit38 min
Pass score70%
Code editionNEC 2026
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)