Flexible Cords and Fixture Wires (NEC 400/402) — NEC 2023 Edition

Free NEC 2023 practice test on flexible cords and fixture wires. Covers permitted and prohibited uses of flexible cords, ampacity adjustment for grouped conductors, overcurrent protection, and fixture wire sizing. Simple English, full explanations.

Share this test
TOPICS COVERED
NEC Questions NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Flexible Cords and Fixture Wires (NEC 400/402) — NEC 2023 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2023
Flexible Cords and Fixture Wires (NEC 400/402) — NEC 2023 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Flexible Cords and Fixture Wires (NEC 400/402) — NEC 2023 Edition — Question List

Question 1: Flexible cord may NOT be used as a substitute for what?

  • The wiring of a crane or hoist
  • The fixed wiring of a structure
  • A pendant for a luminaire
  • A cord for a portable appliance

NEC Reference: NEC 400.12

Question 2: Eight 16-ampere current-carrying conductors are grouped together in a flexible cord. What is the allowable ampacity of each conductor after adjustment?

  • 11.2 amperes
  • 16 amperes
  • 12.8 amperes
  • 14.4 amperes

NEC Reference: NEC Table 400.5(A)(3)

Question 3: In which of the following situations is a flexible cord generally NOT permitted to be used?

  • Wiring of cranes and hoists
  • Connection of moving parts
  • Elevator cables
  • Attached to building surfaces

NEC Reference: NEC 400.12

Question 4: Flexible cord is protected against overcurrent in accordance with its ampacity from which table?

  • Table 310.16
  • Table 400.4
  • Table 402.5
  • Table 400.5(A)(1) and Table 400.5(A)(2)

NEC Reference: NEC 240.5(A)

Question 5: What is the minimum size fixture wire generally permitted for wiring control circuits?

  • 18 AWG
  • 16 AWG
  • 10 AWG
  • 12 AWG

NEC Reference: NEC 402.6

Question 6: What is the allowable ampacity of a 10 AWG fixture wire?

  • 28
  • 23
  • 17
  • 32

NEC Reference: NEC Table 402.5

Question 7: Unless specifically permitted, fixture wires cannot generally be used for which type of wiring?

  • Branch circuit wiring
  • Elevator and escalator control circuits
  • To connect luminaires
  • Fire alarm circuits

NEC Reference: NEC 402.11

Question 8: When 5 current-carrying conductors are grouped together in a flexible cord, what percent of the rated ampacity is allowed for each conductor?

  • 80
  • 60
  • 70
  • 90

NEC Reference: NEC Table 400.5(A)(3)

Question 9: Which of the following IS a permitted use of flexible cord, per NEC 400.10?

  • Pendant luminaires
  • Fixed permanent wiring in walls
  • Underground burial
  • Concealed within concrete

NEC Reference: NEC 400.10(A)

Question 10: What information must be marked on flexible cords (by tag, or on the surface of types such as S, SO and ST)?

  • Type designation, size and number of conductors
  • The ampacity at 30 °C and length
  • Only the manufacturer's name
  • The installation date and circuit number

NEC Reference: NEC 400.6

Question 11: Flexible cord installed in an application permitted by 400.10(A) must generally be installed how?

  • In continuous lengths without splice or tap
  • With splices allowed in any size of cord
  • With splices made only with tape
  • With taps every 10 ft

NEC Reference: NEC 400.13

Question 12: Where flexible cord passes through a hole in an outlet box cover or similar enclosure, how must it be protected?

  • With a larger hole only
  • With a cord grip on the outside only
  • With bushings or fittings
  • With electrical tape wrapped around the cord

NEC Reference: NEC 400.17

Question 13: A flexible cord has three current-carrying conductors. What ampacity adjustment factor from Table 400.5(A)(3) applies?

  • 70%
  • 80%
  • 50%
  • None (100%), since the table starts at 4 conductors

NEC Reference: NEC 400.5(A)

Question 14: Besides the insulation type, what key characteristic does Table 402.3 list for each fixture wire type?

  • Maximum length of run
  • Maximum operating temperature
  • Number of strands
  • Ampacity at 60 °C

NEC Reference: NEC Table 402.3

Question 15: In a flexible cord, the grounded (neutral) conductor is generally identified by what color or marking?

  • White, gray, or another approved marking
  • Always bright orange
  • No marking is ever used
  • Always black

NEC Reference: NEC 400.22

Question 16: Extension cords used on a construction site are generally covered under which special NEC article, in addition to Article 400?

  • Article 590 (temporary wiring)
  • Article 250 only
  • Article 90 only
  • No article covers this

NEC Reference: NEC Article 590

Question 17: Fixture wires generally range in size from 18 AWG up to what maximum size, per NEC Article 402?

  • 10 AWG
  • 6 AWG
  • 2 AWG
  • 1/0 AWG

NEC Reference: NEC Article 402

Question 18: What do service classifications such as "hard usage" and "extra-hard usage" in Table 400.4 tell you about a flexible cord?

  • Its maximum voltage only
  • Its color code
  • Its conductor material
  • How rugged it is for the physical conditions of use

NEC Reference: NEC Table 400.4

Question 19: The ampacity of a flexible cord in Table 400.5(A)(1) depends on its conductor size and what else?

  • The length of the cord
  • The color of the outer jacket
  • The number of current-carrying conductors (column A, B or C)
  • The brand of the cord

NEC Reference: NEC 400.5(A)

Question 20: How must a fixture wire used as a grounded conductor be identified?

  • By a red tracer
  • By one or more continuous white stripes or other means of 400.22
  • By green insulation
  • It needs no identification

NEC Reference: NEC 402.8

Question 21: Where flexible cord is used to connect portable equipment or to allow removal for maintenance, what must the cord be equipped with?

  • An attachment plug, energized from a receptacle or cord connector
  • A strain relief clamp only
  • A separate disconnect switch
  • A splice box at each end

NEC Reference: NEC 400.10(B)

Question 22: Flexible cords must be connected so that tension is not transmitted to joints or terminal screws. Which method is recognized?

  • Soldering the conductors to the terminals
  • Using a larger terminal screw
  • Leaving extra slack coiled inside the box
  • Knotting the cord, winding with tape, or fittings designed for the purpose

NEC Reference: NEC 400.14

Question 23: What is the allowable ampacity of a 12 AWG fixture wire according to Table 402.5?

  • 17 amperes
  • 20 amperes
  • 23 amperes
  • 25 amperes

NEC Reference: NEC Table 402.5

Question 24: Which of these flexible cord installations is prohibited by 400.12?

  • Connecting a portable appliance
  • Wiring a crane or hoist
  • Running the cord through a hole in the floor to a receptacle below
  • Supplying a pendant luminaire

NEC Reference: NEC 400.12

Question 25: Extension cords on a construction site are plugged into 125-volt, single-phase, 15-, 20- and 30-ampere receptacle outlets. What protection must those outlets have?

  • Surge protection only
  • GFCI protection for personnel
  • No protection beyond the breaker
  • AFCI protection

NEC Reference: NEC 590.6(A)(1)

Question 26: A cord-and-plug-connected appliance requires grounding. What must its flexible cord include?

  • An equipment grounding conductor
  • A shield drain wire
  • A second grounded conductor
  • A larger ungrounded conductor

NEC Reference: NEC 250.138(A)

Question 27: On a polarized attachment plug, the identified (grounded) conductor of the cord must connect to which terminal?

  • The green hex-head terminal
  • The terminal that is white or silver in color
  • The brass-colored terminal
  • The terminal with the largest screw

NEC Reference: NEC 200.10(B)

Question 28: May flexible cord be installed above a suspended (dropped) ceiling to reach a luminaire?

  • No, 400.12 prohibits cord located above suspended or dropped ceilings
  • Yes, if the cord is secured to the ceiling grid
  • Yes, if it is no longer than 6 ft
  • Yes, if the cord is plenum rated

NEC Reference: NEC 400.12

Question 29: Why must the fixture wire type selected from Table 402.3 suit the luminaire?

  • It must be solid, never stranded
  • It must be the same brand as the luminaire
  • It must withstand the operating temperature inside the luminaire
  • It must match the luminaire color

NEC Reference: NEC Table 402.3

Question 30: Which flexible cord type is classified for extra-hard usage in Table 400.4?

  • Type SPT-2
  • Type HPN
  • Type SJ
  • Type SO

NEC Reference: NEC Table 400.4

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.