NEC CODE NEC 2023

Flexible Cords and Fixture Wires (NEC 400/402) — NEC 2023 Edition

Free NEC 2023 practice test on flexible cords and fixture wires. Covers permitted and prohibited uses of flexible cords, ampacity adjustment for grouped conductors, overcurrent protection, and fixture wire sizing. Simple English, full explanations.

TOPICS COVERED
NEC Questions NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Flexible Cords and Fixture Wires (NEC 400/402) — NEC 2023 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2023
Flexible Cords and Fixture Wires (NEC 400/402) — NEC 2023 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Flexible Cords and Fixture Wires (NEC 400/402) — NEC 2023 Edition — Question List

Question 1: True or false: flexible cord or cable generally cannot be used as a substitute for the fixed (permanent) wiring of a structure.

  • True
  • False
  • Only in commercial buildings
  • Only for cords over 50 feet

NEC Reference: NEC 400.12

Question 2: Eight 16-ampere current-carrying conductors are grouped together in a flexible cord. What is the allowable ampacity of each conductor after adjustment?

  • 11.2 amperes
  • 16 amperes
  • 12.8 amperes
  • 14.4 amperes

NEC Reference: NEC Table 400.5(A)(3)

Question 3: In which of the following situations is a flexible cord generally NOT permitted to be used?

  • Wiring of cranes and hoists
  • Connection of moving parts
  • Elevator cables
  • Attached to building surfaces

NEC Reference: NEC 400.12

Question 4: The overcurrent device protecting a flexible cord or cable must not be rated how, relative to the cord's ampacity?

  • Higher than the cord's ampacity
  • Lower than the cord's ampacity
  • 125% lower than the cord's ampacity
  • 125% higher than the cord's ampacity

NEC Reference: NEC 400.13 / 240.5

Question 5: What is the minimum size fixture wire generally permitted for wiring control circuits?

  • 18 AWG
  • 16 AWG
  • 10 AWG
  • 12 AWG

NEC Reference: NEC 402.6

Question 6: What is the allowable ampacity of a 10 AWG fixture wire?

  • 28
  • 23
  • 17
  • 32

NEC Reference: NEC Table 402.5

Question 7: Unless specifically permitted, fixture wires cannot generally be used for which type of wiring?

  • Branch circuit wiring
  • Elevator and escalator control circuits
  • To connect luminaires
  • Fire alarm circuits

NEC Reference: NEC 402.10

Question 8: When 5 current-carrying conductors are grouped together in a flexible cord, what percent of the rated ampacity is allowed for each conductor?

  • 80
  • 60
  • 70
  • 90

NEC Reference: NEC Table 400.5(A)(3)

Question 9: Which of the following IS a permitted use of flexible cord, per NEC 400.10?

  • Pendant luminaires
  • Fixed permanent wiring in walls
  • Underground burial
  • Concealed within concrete

NEC Reference: NEC 400.10(A)

Question 10: Flexible cords must generally be marked, at intervals, with what information?

  • Type, size, and number of conductors
  • Nothing is required
  • Only the manufacturer's logo
  • Only the purchase date

NEC Reference: NEC 400.6

Question 11: True or false: flexible cords generally must not contain splices or taps.

  • True
  • False
  • Only for indoor cords
  • Only for cords under 6 feet

NEC Reference: NEC 400.9

Question 12: Flexible cords must generally be protected from what, wherever passing through a wall, floor, or other surface?

  • Physical damage from sharp edges
  • Nothing -- no protection is needed
  • Only sunlight
  • Only rodents

NEC Reference: NEC 400.14

Question 13: Per NEC Table 400.5(A)(3), what adjustment factor applies for 2-3 current-carrying conductors bundled together?

  • It depends on the exact conductor count per the table
  • Always exactly 50%, no matter what
  • Always exactly 25%, no matter what
  • There is never any adjustment

NEC Reference: NEC Table 400.5(A)(3)

Question 14: Fixture wires are generally selected based on their insulation type and what other key characteristic, listed in NEC Table 402.3?

  • Maximum operating temperature rating
  • The manufacturer's logo
  • The wire's color only
  • Nothing else matters

NEC Reference: NEC Table 402.3

Question 15: In a flexible cord, the grounded (neutral) conductor is generally identified by what color or marking?

  • White, gray, or another approved marking
  • Always bright orange
  • No marking is ever used
  • Always black

NEC Reference: NEC 400.22

Question 16: Extension cords used on a construction site are generally covered under which special NEC article, in addition to Article 400?

  • Article 590 (temporary wiring)
  • Article 250 only
  • Article 90 only
  • No article covers this

NEC Reference: NEC Article 590

Question 17: Fixture wires generally range in size from 18 AWG up to what maximum size, per NEC Article 402?

  • 10 AWG
  • 6 AWG
  • 2 AWG
  • 1/0 AWG

NEC Reference: NEC Article 402

Question 18: Flexible cords are classified by service conditions such as "hard usage" and "extra-hard usage." What does this classification generally indicate?

  • The cord's durability for different physical conditions
  • The cord's color only
  • Nothing meaningful
  • Only the price category

NEC Reference: NEC Table 400.4

Question 19: The ampacity of flexible cords and cables, per NEC Table 400.5(A)(1) and (A)(2), depends on the conductor size and what other factor?

  • The number of current-carrying conductors
  • The cord's brand name
  • The room temperature only
  • Nothing else matters

NEC Reference: NEC Table 400.5(A)(1)

Question 20: Can fixture wire generally be used as service-entrance conductors for a building?

  • No, it is not suitable for that use
  • Yes, always freely permitted
  • Only for very small services
  • Only in dwelling units

NEC Reference: NEC Article 402 / 230.41

Question 21: Is flexible cord permitted for connecting portable lamps and appliances?

  • Yes
  • No, never
  • Only outdoors
  • Only in industrial buildings

NEC Reference: NEC 400.10(A)

Question 22: Is a flexible cord generally permitted to run through a doorway, window, or similar opening as a permanent installation?

  • No, this is generally prohibited
  • Yes, always permitted
  • Only for cords under 3 feet
  • Only in garages

NEC Reference: NEC 400.12

Question 23: What is the allowable ampacity of a 12 AWG fixture wire, per NEC Table 402.5?

  • 25 amperes
  • 20 amperes
  • 30 amperes
  • 15 amperes

NEC Reference: NEC Table 402.5

Question 24: True or false: flexible cord is generally not permitted to be run through holes in walls, structural ceilings, or floors, as a fixed installation.

  • True
  • False
  • Only for cords rated over 300V
  • Only outdoors

NEC Reference: NEC 400.12

Question 25: What is generally the smallest conductor size permitted for a general-purpose flexible cord, per NEC Table 400.4?

  • 18 AWG
  • 14 AWG
  • 12 AWG
  • 10 AWG

NEC Reference: NEC Table 400.4

Question 26: A flexible cord supplying a grounding-type appliance must generally include what additional conductor?

  • An equipment grounding conductor
  • A telephone wire
  • Nothing extra is needed
  • A second neutral only

NEC Reference: NEC 400.23

Question 27: An attachment plug on a flexible cord must generally maintain proper what, matching the conductor identification within the cord?

  • Polarity
  • Color only, with no electrical significance
  • Nothing -- wiring order does not matter
  • Weight balance only

NEC Reference: NEC 400.23 / general wiring rules

Question 28: True or false: flexible cords are generally permitted to be concealed behind building walls, ceilings, or floors as a permanent wiring method.

  • True
  • False
  • Only for cords under 25 feet
  • Only in commercial buildings

NEC Reference: NEC 400.12

Question 29: NEC Table 402.3 lists various fixture wire types by their insulation and temperature rating. Why does this matter for luminaire installations?

  • It must withstand the heat inside the fixture
  • It has no practical significance
  • Only the wire color matters
  • Temperature rating is irrelevant to fixture wire

NEC Reference: NEC Table 402.3

Question 30: Is flexible cord a permitted method for connecting portable power tools to a branch circuit?

  • Yes
  • No, never permitted
  • Only outdoors
  • Only for tools under 1 amp

NEC Reference: NEC 400.10(A)

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)