NEC 2020 Code Questions Practice Test 16

Free NEC 2020 practice test with 30 questions on conductor sizing, feeder taps, cable types, and motor circuits. Plain-English questions with full explanations.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

How to Use This Practice Test

This NEC 2020 Code Questions Practice Test 16 has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Mixed-format test — questions jump between topics just like the real exam. Don't spend more than 90 seconds on any one question.

  • Topics covered: All NEC chapters — branch circuits, grounding, conductors, wiring methods, motors, and more.
  • Passing score: Aim for 80%+ consistently before scheduling your exam.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2020
NEC 2020 Code Questions Practice Test 16
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2020 Code Questions Practice Test 16 — Question List

Question 1: Where the grounding electrode conductor connects only to a concrete-encased electrode, it need not be larger than:

  • 4 AWG copper
  • 2/0 AWG copper
  • 14 AWG copper
  • There is no maximum

NEC Reference: NEC 250.66(B)

Question 2: Where the grounding electrode conductor connects only to a rod electrode, it need not be larger than:

  • 6 AWG copper
  • 2 AWG copper
  • 14 AWG copper
  • There is no maximum

NEC Reference: NEC 250.66(A)

Question 3: What is the maximum standard overcurrent device rating for a 12 AWG copper conductor?

  • 15 amperes
  • 20 amperes
  • 25 amperes
  • 30 amperes

NEC Reference: NEC 240.4(D)(5)

Question 4: What is the maximum standard overcurrent device rating for a 10 AWG copper conductor?

  • 20 amperes
  • 25 amperes
  • 30 amperes
  • 40 amperes

NEC Reference: NEC 240.4(D)(7)

Question 5: What is the maximum standard overcurrent device rating for a 16 AWG copper fixture wire?

  • 7 amperes
  • 10 amperes
  • 15 amperes
  • 20 amperes

NEC Reference: NEC 240.4(D)(2)

Question 6: Under the 25-foot tap rule, the tap conductor ampacity must be at least what fraction of the feeder overcurrent device rating?

  • One-tenth
  • One-third
  • One-half
  • Full rating

NEC Reference: NEC 240.21(B)(2)

Question 7: Under the 10-foot tap rule, tap conductors can skip overcurrent protection at the tap point if they are not longer than:

  • 10 feet
  • 25 feet
  • 50 feet
  • 100 feet

NEC Reference: NEC 240.21(B)(1)

Question 8: As a general rule, overcurrent protection is placed at the point where a conductor:

  • Receives its supply
  • Ends at the last outlet
  • Crosses a property line
  • There is no general rule

NEC Reference: NEC 240.21

Question 9: Which of the following is a standard fuse and breaker rating?

  • 45 amperes
  • 48 amperes
  • 52 amperes
  • 58 amperes

NEC Reference: NEC 240.6(A)

Question 10: A panelboard circuit directory must be:

  • Legible and clear
  • Handwritten in pencil only
  • Not required
  • Written in a foreign language only

NEC Reference: NEC 408.4(A)

Question 11: A 4 inch round box, 1 1/2 inches deep, has a listed volume of:

  • 12.5 cubic inches
  • 15.5 cubic inches
  • 18 cubic inches
  • 21 cubic inches

NEC Reference: NEC Table 314.16(A)

Question 12: NM cable (Romex) is not permitted to be:

  • Embedded in poured concrete
  • Used in a wall cavity
  • Fished through a finished wall
  • Run in an attic

NEC Reference: NEC 334.12

Question 13: Type AC cable has an internal bonding strip in contact with the armor. This strip is used to:

  • Give a backup grounding path
  • Add insulation only
  • Improve color coding
  • It has no purpose

NEC Reference: NEC 320.108

Question 14: Type SE (service entrance) cable ampacity is based on the:

  • 60 C column
  • 90 C column
  • It has no ampacity
  • 30 C column

NEC Reference: NEC 338.10

Question 15: For sizing motor conductors, the full-load current value used should come from:

  • The NEC full-load current tables
  • The nameplate current, always
  • A guess
  • The panel rating

NEC Reference: NEC 430.6(A)(1)

Question 16: A motor has a full-load current of 12 amperes. What is the minimum branch-circuit conductor ampacity?

  • 12 amperes
  • 15 amperes
  • 18 amperes
  • 24 amperes

NEC Reference: NEC 430.22(A)

Question 17: A 3/4 horsepower motor normally runs unattended and is not readily accessible. What can serve as its overload protection?

  • The branch-circuit overcurrent device
  • Nothing, protection is skipped
  • A padlock
  • A separate 400% fuse only

NEC Reference: NEC 430.32(B)

Question 18: Under the 25-foot transformer secondary tap rule, the tap conductors must be protected from physical damage and be no longer than:

  • 10 feet
  • 25 feet
  • 50 feet
  • 100 feet

NEC Reference: NEC 240.21(C)(6)

Question 19: An autotransformer supplying a branch circuit needs overcurrent protection set at not more than what percent of the rated input current?

  • 125 %
  • 250 %
  • 400 %
  • No protection is needed

NEC Reference: NEC 450.4

Question 20: Dry-type transformer vent openings must not be blocked by:

  • Walls or other obstructions
  • Nothing, blocking is fine
  • Paint only
  • It does not matter

NEC Reference: NEC 450.9

Question 21: A receptacle for servicing HVAC equipment must be within what distance of the equipment?

  • 10 feet
  • 25 feet
  • 50 feet
  • 100 feet

NEC Reference: NEC 210.63

Question 22: NEC 210.8 is split into two parts. What do these two parts cover?

  • Dwelling units and other than dwelling units
  • Only dwelling units
  • Only commercial buildings
  • Nothing, both parts are the same

NEC Reference: NEC 210.8

Question 23: AFCI protection also applies to guest rooms in:

  • Hotels and motels
  • Warehouses only
  • No other occupancy
  • Parking lots only

NEC Reference: NEC 210.12(C)

Question 24: Which of these is an accepted reason for a building to have more than one service?

  • A fire pump
  • A ceiling fan
  • A toaster
  • A lamp

NEC Reference: NEC 230.2(A)

Question 25: Which of these can be connected ahead of (supply side of) the service disconnect?

  • A listed surge-protective device
  • A lighting panel
  • A branch-circuit receptacle
  • A motor circuit

NEC Reference: NEC 230.82

Question 26: For a grounded conductor larger than 6 AWG, identification is permitted at the time of installation by:

  • White tape or paint at each end
  • No marking at all
  • A red marking only
  • A metal tag with no color

NEC Reference: NEC 200.6(B)

Question 27: A service raceway has 2/0 AWG copper conductors. What size copper supply-side bonding jumper is needed?

  • 8 AWG
  • 4 AWG
  • 1/0 AWG
  • 3/0 AWG

NEC Reference: NEC 250.102(C)

Question 28: Where several service disconnects are used, the grounding electrode conductor can be run as one common conductor with:

  • Taps run to each disconnect
  • No taps at all, ever
  • A separate rod for each disconnect only
  • It is never permitted

NEC Reference: NEC 250.64(D)

Question 29: The size of the supply-side bonding jumper is generally based on the size of the:

  • Largest ungrounded service conductor
  • Building square footage
  • Number of light fixtures
  • Roof height

NEC Reference: NEC 250.102(C)

Question 30: Why must the grounded (neutral) conductor be run to each service disconnecting means?

  • It is part of the ground-fault current path
  • It has no real purpose
  • To save on copper
  • For looks only

NEC Reference: NEC 250.24(C)