JOURNEYMAN NEC 2026

NEC 2026 Journeyman Practice Test 2

Free Online Journeyman Electrician Practice Test — NEC 2026 Edition 2This free 25-question practice test covers grounding electrode systems, bonding jumpers, grounding electrode and equipment grounding conductor sizing, and the 2026 NEC's emergency disconnect requirements for one- and two-family dwellings under 230.85. Based on the 2026 National Electrical Code.

TOPICS COVERED
journeyman electrician

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 38 min for 25 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account required. All questions include detailed explanations and NEC references.

Most state Journeyman exams have 80–100 questions covering NEC code, wiring methods, branch circuits, motor controls, and load calculations.

Most states require a 70–75% passing score. This practice test uses the same 70% pass threshold so you know where you stand.

Questions are written to the 2026 NEC. Check your state licensing board to confirm which edition your state has adopted.

How to Use This Practice Test

This NEC 2026 Journeyman Practice Test 2 has 25 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: This is an open-book exam — tab your NEC index and Articles 210, 250, and 430 before you start.

  • Topics covered: Branch circuits, grounding, wiring methods, load calculations, and motors.
  • Passing score: 70–75% (most states). Aim for 80% on practice tests so the real exam feels easy.
  • Questions: 25 multiple-choice, one correct answer each
25
Questions
38 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

JOURNEYMAN · NEC 2026
NEC 2026 Journeyman Practice Test 2
Q1 / 25
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Journeyman Practice Test 2 — Question List

Question 1: Per NEC 250.24(A), the service grounded (neutral) conductor must be connected to the grounding electrode system at:

  • Each panelboard throughout the building
  • The service disconnecting means, or ahead of it
  • Only at the meter base
  • Only at the utility transformer

NEC Reference: NEC 250.24(A)(1)

Question 2: A dry-type transformer creates a separately derived system inside a commercial building. Per NEC 250.30, this system requires its own:

  • System bonding jumper and grounding electrode connection
  • Connection to the building's water meter only
  • No additional grounding — it uses the service ground
  • A dedicated lightning arrestor only

NEC Reference: NEC 250.30(A)

Question 3: Per NEC 250.50, where multiple grounding electrodes described in 250.52(A) are present at a building — for example, a metal underground water pipe and a concrete-encased electrode — the NEC requires they be:

  • Bonded together to form the grounding electrode system
  • Kept electrically isolated from each other
  • Used one at a time, at the installer's discretion
  • Removed except for the one closest to the panel

NEC Reference: NEC 250.50

Question 4: Per NEC 250.52(A)(3), a concrete-encased electrode ("Ufer ground") qualifies as a grounding electrode when it includes at least 20 feet of bare copper conductor not smaller than:

  • 8 AWG
  • 6 AWG
  • 4 AWG
  • 2 AWG

NEC Reference: NEC 250.52(A)(3)

Question 5: A single ground rod electrode is installed and measures 40 ohms of resistance to earth. Per NEC 250.53(A)(2), what must the installer do?

  • Nothing — 40 ohms is acceptable
  • Install a second rod at least 6 feet away
  • Replace the rod with a larger-diameter rod
  • Add a lightning arrestor

NEC Reference: NEC 250.53(A)(2)

Question 6: Per NEC 250.66(B), where the grounding electrode conductor connects only to a concrete-encased electrode, the GEC is not required to be larger than:

  • 8 AWG copper
  • 6 AWG copper
  • 4 AWG copper
  • 2 AWG copper

NEC Reference: NEC 250.66(B)

Question 7: Per NEC Table 250.66, for service-entrance conductors of 2/0 AWG copper, the minimum grounding electrode conductor size is:

  • 8 AWG copper
  • 6 AWG copper
  • 4 AWG copper
  • 2 AWG copper

NEC Reference: NEC Table 250.66

Question 8: Per NEC Table 250.122, a branch circuit protected by a 100-ampere overcurrent device requires a copper equipment grounding conductor no smaller than:

  • 10 AWG
  • 8 AWG
  • 6 AWG
  • 4 AWG

NEC Reference: NEC Table 250.122

Question 9: Per NEC 250.28, the main bonding jumper connecting the service equipment enclosure to the grounded (neutral) conductor must be sized:

  • Per Table 250.102(C)(1), based on the largest ungrounded service conductor
  • Always 6 AWG copper regardless of service size
  • Half the size of the largest ungrounded conductor
  • Per the panel manufacturer's label only

NEC Reference: NEC 250.28(D)

Question 10: A detached workshop is supplied by a feeder from the main dwelling's panel, and an equipment grounding conductor is run with the feeder. Per NEC 250.32(B)(1), at the workshop's disconnecting means, the grounded (neutral) conductor:

  • Must be bonded to the EGC and grounding electrode, same as the main service
  • Must remain isolated from the equipment grounding conductor
  • Is not required at all in the feeder
  • May be bonded only if the structure has metal siding

NEC Reference: NEC 250.32(B)(1)

Question 11: Per NEC 250.4(A)(5), the effective ground-fault current path must be:

  • Permanent, low-impedance, and capable of safely carrying the maximum likely fault current
  • Sized only for normal operating current
  • Optional if the equipment is double-insulated
  • Routed through the earth as the primary path

NEC Reference: NEC 250.4(A)(5)

Question 12: Per NEC 250.90, bonding is required to ensure:

  • Electrical continuity and the capacity to safely conduct any likely fault current
  • A neat and orderly panel appearance
  • Reduced conductor size requirements
  • Compliance only for services over 400A

NEC Reference: NEC 250.90

Question 13: Per NEC 250.118, which of the following is recognized as a type of equipment grounding conductor?

  • Rigid metal conduit, installed and terminated per Code
  • Any bare copper wire, regardless of size
  • A telephone grounding block
  • A metal water pipe run alone with no other bonding

NEC Reference: NEC 250.118

Question 14: Per NEC 250.20(B), a 120/240-volt, single-phase, 3-wire AC system supplying a dwelling must be:

  • Grounded
  • Ungrounded
  • Grounded only if over 400A
  • Grounded only in wet locations

NEC Reference: NEC 250.20(B)

Question 15: Per NEC Article 100, a "Bonding Jumper" is defined as a reliable conductor that ensures the required electrical conductivity between:

  • Metal parts required to be electrically connected
  • Two separate services on the same property
  • The utility transformer and the meter only
  • Any two pieces of metal, regardless of function

NEC Reference: NEC Article 100

Question 16: Per NEC Article 100, the "Grounded Conductor" of a wiring system is the conductor that is intentionally:

  • Grounded (i.e., typically the neutral)
  • The equipment grounding conductor
  • Always colored green
  • Never connected to earth

NEC Reference: NEC Article 100

Question 17: Per NEC 250.64(A), the grounding electrode conductor, where exposed, must be:

  • Protected from physical damage, and generally spliced only by irreversible compression or exothermic welding
  • Spliced freely with wire nuts as needed
  • Installed only in nonmetallic conduit
  • Routed through a water meter without a bonding jumper

NEC Reference: NEC 250.64(A)

Question 18: Per NEC 250.104(A), interior metal water piping likely to become energized must be bonded to:

  • The service equipment enclosure, grounded conductor, GEC, or a grounding electrode
  • A dedicated ground rod separate from the electrode system
  • Nothing — metal water piping is self-grounding
  • Only the nearest branch-circuit EGC

NEC Reference: NEC 250.104(A)

Question 19: Per the 2026 NEC 230.85(A), the emergency disconnect for a one-family dwelling must be installed:

  • In a readily accessible outdoor location
  • Anywhere inside the dwelling
  • Only in an attached garage
  • In the crawl space near the meter

NEC Reference: NEC 2026 — 230.85(A)

Question 20: Per the 2026 NEC 230.85(E), the emergency disconnect for a dwelling must carry which base marking, along with a sub-label identifying its type?

  • "EMERGENCY DISCONNECT"
  • "MAIN SHUT-OFF"
  • "DANGER - HIGH VOLTAGE"
  • No marking is required beyond a red handle

NEC Reference: NEC 2026 — 230.85(E)

Question 21: Per the 2026 NEC 230.85, when a homeowner operates the emergency disconnect, which conductors are opened?

  • All ungrounded service conductors
  • All conductors, including the grounded (neutral) conductor
  • Only one of the two ungrounded conductors
  • Only the equipment grounding conductor

NEC Reference: NEC 2026 — 230.85

Question 22: A two-family dwelling has two separate 200-ampere services, each serving one unit. Per the 2026 NEC 230.85(A), how many emergency disconnects are required?

  • One shared disconnect for both units
  • Two — one per service
  • None — two-family dwellings are exempt
  • Four — two per service

NEC Reference: NEC 2026 — 230.85(A)

Question 23: Per the 2026 NEC, the emergency disconnect requirement in 230.85 applies to which occupancy type?

  • One-family and two-family dwelling units
  • All occupancies regardless of size
  • Commercial occupancies only
  • Multi-family dwellings of three units or more

NEC Reference: NEC 2026 — 230.85

Question 24: A stand-alone emergency disconnect is installed ahead of the service equipment and is not itself the service disconnect. Per the 2026 NEC 230.85(E)(3), what exact sub-label must accompany the "EMERGENCY DISCONNECT" marking?

  • "SERVICE DISCONNECT"
  • "NOT SERVICE EQUIPMENT"
  • "METER DISCONNECT"
  • "AUXILIARY DISCONNECT"

NEC Reference: NEC 2026 — 230.85(E)(3)

Question 25: Per the 2026 NEC 230.85(B), the emergency disconnect must be capable of being operated:

  • By hand, without specialized tools or equipment
  • Only remotely by the utility
  • Only with a proprietary key from the manufacturer
  • Only by a licensed electrician on site

NEC Reference: NEC 2026 — 230.85(B)

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
EXAM CARD JOURNEYMAN
Questions25
Time limit38 min
Pass score70%
Code editionNEC 2026
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)