NEC_PRACTICE NEC 2023

NEC 2023 Code Questions Practice Test 3

Free NEC 2023 practice test with 30 questions covering AFCI protection in hotel and motel guest rooms, overhead conductor clearances near pools, service overcurrent protection, the small conductor rule, and single-point grounding connections. Full NEC 2023 code references.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

How to Use This Practice Test

This NEC 2023 Code Questions Practice Test 3 has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Mixed-format test — questions jump between topics just like the real exam. Don't spend more than 90 seconds on any one question.

  • Topics covered: All NEC chapters — branch circuits, grounding, conductors, wiring methods, motors, and more.
  • Passing score: Aim for 80%+ consistently before scheduling your exam.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2023
NEC 2023 Code Questions Practice Test 3
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2023 Code Questions Practice Test 3 — Question List

Question 1: If the conduit is placed in hazardous locations , it must be made .................... to prevent sparking when fault current flow through it.

  • wrench tight
  • sealed
  • bonded
  • rugged plastic

NEC Reference: NEC 500.8(E)

Question 2: What are the maximum allowable service dis connectors consist for each service?

  • 4
  • 2
  • 6
  • 8

NEC Reference: NEC 230.71(A)

Question 3: What is the smallest rating plug fuse that is used for residential 120 volts branch circuit?

  • 15 amperes
  • 20 amperes
  • 12 amperes
  • 18 amperes

NEC Reference: NEC 240.6(A)

Question 4: What is the voltage drop of two 10 AWG THWN conductors that supply 16 amperes 115 volts load located 50 feet from the source?

  • 1.92 volts
  • 0.96 volts
  • 2.4 volts
  • 1.8 volts

Question 5: What is the minimum volt ampere rating of a 110,000 square foot school?

  • 330 KVA
  • 220 KVA
  • 165 KVA
  • 440 KVA

NEC Reference: NEC 220.12

Question 6: A disconnecting means should be visibly located from a motor not more than .............. distance.

  • 50 feet
  • 40 feet
  • 55 feet
  • 60 feet

Question 7: A 4800 watts electric motor is connected to 240 volts single phase supply, 2 wire circuit. what is the minimum size THW conductor that is required to supply the load?

  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG

NEC Reference: NEC 424.3(B)

Question 8: What is the minimum allowable 3 wire service entrance conductor rating for a single family dwelling unit?

  • 100 amperes
  • 125 amperes
  • 150 amperes
  • 75 amperes

NEC Reference: NEC 230.42(B)

Question 9: An electric heater with a resistance of 18 ohms draws a current of 7 amperes. what is the minimum wattage of electric heater?

  • 882 watts.
  • 764 watts
  • 126 watts
  • 922 watts

Question 10: what is the maximum over current device rating that is allowed to placed  to protect panel board instrumentation circuit?

  • 30 amperes
  • 15 amperes
  • 20 amperes
  • 10 amperes

NEC Reference: NEC 408.52

Question 11: AFCI protection is required for 120 volt, 15 and 20 ampere branch circuits supplying outlets in which occupancy, in addition to dwelling units?

  • Hotel and motel guest rooms/suites
  • Industrial warehouses only
  • No other occupancy requires AFCI
  • Outdoor parking lots only

NEC Reference: NEC 210.12(C)

Question 12: Overhead conductors are subject to increased clearance requirements when installed near a swimming pool, to reduce the risk of contact by:

  • Pool equipment, ladders, and people at the pool
  • It has no relevance to swimming pools
  • Only lightning strikes
  • Only birds landing on the wire

NEC Reference: NEC 225.19(C)

Question 13: Each ungrounded service conductor must be protected by an overcurrent device with a rating or setting:

  • Not higher than the conductor ampacity (with a limited exception)
  • At least double the conductor ampacity
  • No overcurrent protection is required at services
  • Exactly half the conductor ampacity

NEC Reference: NEC 230.90(A)

Question 14: Under the small conductor rule, 14 AWG copper conductors are limited to a maximum standard overcurrent device rating of:

  • 15 amperes
  • 20 amperes
  • 25 amperes
  • 30 amperes

NEC Reference: NEC 240.4(D)(3)

Question 15: Where a service consists of multiple disconnects fed from one set of service-entrance conductors, the connection of the grounded conductor to the grounding electrode system must be made:

  • At only one point
  • At every disconnect separately
  • It does not matter how many points are used
  • No connection is ever made

NEC Reference: NEC 250.24(A)(4)

Question 16: In spaces used for environmental air (other than ducts and plenums specifically fabricated for that purpose), wiring methods are generally limited to:

  • Metal raceways or specific metal-clad cable types
  • Any type of nonmetallic cable, without restriction
  • Bare open conductors
  • No wiring is ever permitted in air handling spaces

NEC Reference: NEC 300.22(C)

Question 17: An ungrounded (hot) conductor must NOT be identified using which of the following colors, since they are reserved for grounded and grounding conductors?

  • White or gray
  • Black
  • Red
  • Blue

NEC Reference: NEC 200.6

Question 18: Boxes installed in wet locations must be listed for the purpose, and enclosures for switches or receptacles must additionally be:

  • Weatherproof so moisture does not enter or accumulate
  • Left open with no cover
  • Made only of untreated wood
  • It does not matter in wet locations

NEC Reference: NEC 314.15

Question 19: Intermediate metal conduit (IMC) must generally be supported at intervals not exceeding:

  • 5 feet
  • 10 feet
  • 15 feet
  • 20 feet

NEC Reference: NEC 342.30

Question 20: Liquidtight flexible metal conduit (LFMC) must generally be secured within 12 inches of every box or fitting and supported at intervals not exceeding:

  • 2 feet
  • 4 1/2 feet
  • 10 feet
  • 15 feet

NEC Reference: NEC 350.30

Question 21: An AC general-use snap switch controlling a tungsten-filament lamp load must be rated for tungsten-filament loads, or rated in amperes not less than:

  • T rated, or otherwise rated for tungsten-filament loads
  • Any standard switch works with no restriction
  • A switch is never permitted for this load
  • Only DC-rated switches are permitted

NEC Reference: NEC 404.14(A)

Question 22: A faceplate for a switch or receptacle installed in a damp or wet location must be installed so as to be:

  • Fitted closely against the mounting surface
  • Left with a large visible gap
  • Removed entirely for airflow
  • It does not matter in wet locations

NEC Reference: NEC 406.9

Question 23: A fluorescent luminaire supplied by a multiwire branch circuit and containing double-ended lamp ballast(s) must have a disconnecting means to disconnect:

  • All ungrounded conductors supplying the ballast(s)
  • Only the grounded (neutral) conductor
  • No disconnect is ever required for fluorescent fixtures
  • Only the equipment grounding conductor

NEC Reference: NEC 410.130(G)

Question 24: NEC 422.5(A) requires factory-installed GFCI protection for cord-and-plug-connected appliances used in damp or wet locations, including which of the following?

  • High-pressure spray washing machines
  • Table lamps
  • Standard desktop computers
  • Ceiling fans

NEC Reference: NEC 422.5(A)

Question 25: Embedded heating cables must not be spliced in the field except with:

  • Identified splicing devices or kits
  • Ordinary wire nuts
  • Electrical tape alone
  • Field splices are never permitted, even with a kit

NEC Reference: NEC 424.44(C)

Question 26: A motor circuit disconnecting means is generally permitted to be a motor-circuit switch rated in horsepower, a molded-case circuit breaker, a molded-case switch, or:

  • An instantaneous-trip circuit breaker in a listed combination controller
  • A standard wall light switch
  • No disconnect type is ever acceptable
  • A telephone jack

NEC Reference: NEC 430.109(A)

Question 27: When the maximum branch-circuit short-circuit and ground-fault protective device rating calculated for multimotor equipment does not correspond to a standard rating, which rating is permitted to be used?

  • The next lower standard rating
  • The next higher standard rating, always
  • No standard rating may ever be substituted
  • A rating of exactly 15 amperes, regardless of load

NEC Reference: NEC 440.22(C)

Question 28: An autotransformer supplying a branch circuit must be provided with individual overcurrent protection, generally set at not more than what percentage of the rated full-load input current?

  • 125 %
  • 250 %
  • 400 %
  • No protection is required

NEC Reference: NEC 450.4

Question 29: Equipment for use in a Class I hazardous location must be marked to show the operating temperature, or the identification number, in relation to the:

  • Ignition temperature of the specific gas or vapor present
  • The color of the equipment housing
  • The installer's preferred temperature
  • No temperature marking is ever required

NEC Reference: NEC 500.9

Question 30: Outlets used to supply power to boat hoists in a marina or boatyard must be protected by:

  • GFCI protection
  • No special protection
  • AFCI protection only
  • A surge arrestor only

NEC Reference: NEC 555.13

EXAM CARD NEC_PRACTICE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)