NEC CODE NEC 2023

Cabinets, Enclosures & Cutout Boxes (NEC 312/314) — NEC 2023 Edition

Free NEC 2023 practice test on cabinets, enclosures, and boxes. Covers box fill volume calculations, splices and taps in enclosures, and which items count toward box fill. Simple English, full explanations.

TOPICS COVERED
NEC Questions NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 29 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Cabinets, Enclosures & Cutout Boxes (NEC 312/314) — NEC 2023 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
29
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2023
Cabinets, Enclosures & Cutout Boxes (NEC 312/314) — NEC 2023 Edition
Q1 / 29
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Cabinets, Enclosures & Cutout Boxes (NEC 312/314) — NEC 2023 Edition — Question List

Question 1: What is the minimum box fill volume allowance required for each 16 AWG conductor?

  • 1.75 cubic inches
  • 2.0 cubic inches
  • 2.25 cubic inches
  • 2.5 cubic inches

NEC Reference: NEC Table 314.16(B)

Question 2: True or false: a cabinet or enclosure can never be used as a raceway for conductors passing through it.

  • True
  • False
  • Only for metal enclosures
  • Only underground

NEC Reference: NEC 312.8

Question 3: Splices and taps can be installed in a cabinet or enclosure used as a raceway if they do not fill more than what percent of the cross-sectional area at that point?

  • 75
  • 70
  • 60
  • 80

NEC Reference: NEC 312.8

Question 4: True or false: locknuts, bushings, AND internal cable clamps are all excluded from box fill volume calculations.

  • True
  • False
  • Only for plastic boxes
  • Only for metal boxes

NEC Reference: NEC 314.16(B)

Question 5: Which of the following conductors is NOT counted for box fill calculations?

  • Conductors that originate and terminate entirely within the box
  • A conductor loop less than 12 inches long that enters the box
  • A conductor that terminates in the box
  • A conductor that passes through the box

NEC Reference: NEC 314.16(B)(1)

Question 6: A junction box contains two receptacles, four 12 AWG circuit conductors, and two 12 AWG equipment grounding conductors. What is the total required box fill volume?

  • 20.25 cu in
  • 22.50 cu in
  • 18 cu in
  • 24.75 cu in

NEC Reference: NEC 314.16 / Table 314.16(B)

Question 7: A box has 14.40 cubic inches of remaining volume after devices are accounted for. How many additional 14 AWG conductors can be added?

  • 4
  • 5
  • 6
  • 7

NEC Reference: NEC Table 314.16(B)

Question 8: How many 10 AWG conductors can be spliced within an 11 cubic inch conduit body?

  • 2
  • 3
  • 4
  • 5

NEC Reference: NEC Table 314.16(B)

Question 9: A box is generally required at each termination point for which type of wiring?

  • Power and lighting systems
  • Communication systems
  • Control conductors only
  • Signaling conductors only

NEC Reference: NEC 300.15

Question 10: A 3-wire, single-phase, 120/240-volt circuit supplies a 1,000 W, 120-volt electric heater and a 600 W, 120-volt electric dryer on the opposite leg. What is the operating voltage of the heater?

  • 90 volts
  • 100 volts
  • 120 volts
  • 110 volts

NEC Reference: General electrical theory (series circuit with two different loads)

Question 11: For box fill calculations, a single device (like a switch or receptacle) mounted on one strap counts as how many conductor-equivalents?

  • Two
  • Zero
  • One
  • Three

NEC Reference: NEC 314.16(B)(4)

Question 12: When one or more equipment grounding conductors enter a box, how many conductor-equivalents are counted for box fill?

  • One, for the whole group
  • One for each equipment grounding conductor
  • Zero -- they are never counted
  • Two for each conductor

NEC Reference: NEC 314.16(B)(5)

Question 13: What is the box fill volume allowance required for each 8 AWG conductor?

  • 3.00 cubic inches
  • 2.50 cubic inches
  • 2.00 cubic inches
  • 3.50 cubic inches

NEC Reference: NEC Table 314.16(B)

Question 14: What is the box fill volume allowance required for each 18 AWG conductor?

  • 1.50 cubic inches
  • 1.75 cubic inches
  • 2.00 cubic inches
  • 1.25 cubic inches

NEC Reference: NEC Table 314.16(B)

Question 15: Metal boxes must generally be durably and legibly marked with what, to help with box fill calculations?

  • Their cubic inch capacity
  • Nothing is required
  • Only the manufacturer's logo
  • Only the color

NEC Reference: NEC 314.16(A)(2)

Question 16: For a straight pull in a pull box, the box length must generally be at least what multiple of the largest raceway's trade diameter?

  • 8 times
  • 4 times
  • 6 times
  • 10 times

NEC Reference: NEC 314.28(A)(1)

Question 17: For an angle or U-pull in a pull box, the distance between raceway entries enclosing the same conductor must generally be at least what multiple of the raceway trade diameter?

  • 6 times
  • 8 times
  • 4 times
  • 10 times

NEC Reference: NEC 314.28(A)(2)

Question 18: Outlet, device, pull, and junction boxes must generally be installed so as to be what, after the building is finished?

  • Accessible without removing building finish
  • Permanently sealed behind drywall
  • Buried with no access at all
  • Removed after construction

NEC Reference: NEC 314.29

Question 19: A domed or raised box cover can generally add to the box's usable fill volume if what condition is met?

  • The cover is marked with its volume
  • Any cover always counts, marked or not
  • Covers never add volume
  • Only plastic covers count

NEC Reference: NEC 314.16(A)(2)

Question 20: Fittings used with cabinets and cutout boxes, such as connectors and locknuts, must generally be what?

  • Listed and used per their listing
  • Homemade only
  • Unlisted is preferred
  • Nothing is required

NEC Reference: NEC 110.3(B)

Question 21: What is the box fill volume allowance required for each 6 AWG conductor?

  • 5.00 cubic inches
  • 4.00 cubic inches
  • 3.50 cubic inches
  • 6.00 cubic inches

NEC Reference: NEC Table 314.16(B)

Question 22: A box contains 6 current-carrying 14 AWG conductors and one duplex receptacle (a single device). What is the total required box fill volume?

  • 16 cubic inches
  • 12 cubic inches
  • 14 cubic inches
  • 18 cubic inches

NEC Reference: NEC 314.16 / Table 314.16(B)

Question 23: For a nonmetallic box with integral (built-in) cable clamps, how are those clamps generally counted in box fill?

  • One conductor-equivalent for the whole box
  • One for each individual clamp
  • They are never counted
  • Two for each clamp

NEC Reference: NEC 314.16(B)(2)

Question 24: An outlet box used to support a ceiling-suspended paddle fan must generally be what?

  • Listed for fan support
  • Any general-purpose box
  • A cardboard box
  • Not required to hold any weight

NEC Reference: NEC 314.27(C)

Question 25: An outlet box used to support a luminaire weighing more than 50 pounds must generally be what?

  • Listed and marked for that weight
  • Made of plastic with no rating
  • Ignored, weight does not matter
  • Removed completely

NEC Reference: NEC 314.27(A)(2)

Question 26: Per NEC Article 100 definitions, what generally distinguishes a "cutout box" from a "cabinet"?

  • A cutout box is surface-mounted only
  • There is no difference at all
  • A cutout box is always underground
  • A cabinet is always outdoors

NEC Reference: NEC Article 100

Question 27: Support fittings, such as fixture studs or hickeys that take up space in a box, are generally treated in box fill calculations similar to what other item?

  • A cable clamp
  • A locknut
  • A bushing
  • Nothing -- it is never counted

NEC Reference: NEC 314.16(B)(3)

Question 28: A cabinet or cutout box installed outdoors or in a wet location must generally be what?

  • Weatherproof
  • Left uncovered
  • Made only of untreated wood
  • Nothing special is required

NEC Reference: NEC 312.2(A)

Question 29: A standard single-gang device box with 18 cubic inches of volume, containing one duplex receptacle and 3 current-carrying 12 AWG conductors, plus 1 equipment grounding conductor -- is this box fill compliant?

  • Yes, 13.5 cu in is required, which fits
  • No, it exceeds 18 cu in
  • It requires exactly 18 cu in, no margin
  • Box fill does not apply to device boxes

NEC Reference: NEC 314.16

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions29
Time limit45 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)