JOURNEYMAN NEC 2026

NEC 2026 Journeyman Practice Test 8

Free Online Journeyman Electrician Practice Test — NEC 2026 Edition 8This free 25-question practice test covers special locations: Article 680 swimming pools, spas, hot tubs and hydromassage tubs, Article 590 temporary wiring on job sites, repair garages and fuel dispensing, and the basics of hazardous (classified) locations.

Share this test
Want the real exam format? Take a free full-length exam for your state
TOPICS COVERED
journeyman electrician

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 38 min for 25 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account required. All questions include detailed explanations and NEC references.

Most state Journeyman exams have 80–100 questions covering NEC code, wiring methods, branch circuits, motor controls, and load calculations.

Most states require a 70–75% passing score. This practice test uses the same 70% pass threshold so you know where you stand.

Questions are written to the 2026 NEC. Check your state licensing board to confirm which edition your state has adopted.

Before You Start

  • 25 questions, multiple choice
  • 37½ minutes, pass mark 70%
  • Main articles: 500, 511, 514, 590 and 680
25
Questions
38 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

JOURNEYMAN · NEC 2026
NEC 2026 Journeyman Practice Test 8
Q1 / 25
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
Rate it and add a quick comment. No sign-up.
Tap one to send it now:
Share your score
Share it and get the Journeyman Electrician Cheat Sheet — NEC 2026 free, right now.
Unlocked — thanks for sharing! 🎉
Get the Journeyman Electrician Cheat Sheet — NEC 2026
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Journeyman Practice Test 8 — Question List

Question 1: Per NEC 680.22(A)(3), receptacles not used for pool equipment must be located at least how far from the inside walls of a pool?

  • 10 feet
  • 20 feet
  • 3 feet
  • 6 feet

NEC Reference: NEC 2026 — 680.22(A)(3)

Question 2: Per NEC 680.22(B)(4), existing luminaires within 5 feet horizontally of the inside walls of a pool must be at least how high above the maximum water level (and be rigidly attached and GFCI protected)?

  • 5 feet
  • 12 feet
  • 7½ feet
  • 8 feet

NEC Reference: NEC 2026 — 680.22(B)(4)

Question 3: Per NEC 680.23(A)(5), a wet-niche underwater pool luminaire must be installed so the top of the lens is at least how far below the normal water level (unless listed for less depth)?

  • 18 inches
  • 6 inches
  • 24 inches
  • 12 inches

NEC Reference: NEC 2026 — 680.23(A)(5)

Question 4: Per NEC 680.23(A)(3), branch circuits for underwater pool luminaires operating at more than the low-voltage contact limit must have:

  • No special protection
  • AFCI protection
  • GFCI protection
  • A 50-ampere breaker

NEC Reference: NEC 2026 — 680.23(A)(3)

Question 5: Per NEC 680.26(C), the pool water must be bonded by a conductive surface in contact with the water having an area of at least:

  • 4 square inches
  • 12 square inches
  • 1 square foot
  • 9 square inches

NEC Reference: NEC 2026 — 680.26(C)

Question 6: Per NEC 680.26(B)(6), which pool items must be bonded to the equipotential bonding grid?

  • Pump motors and other fixed electrical equipment associated with the pool water circulating system
  • Metal parts of the homeowner's car parked near the pool
  • Plastic pool chairs and loungers placed on the pool deck
  • Wooden decking boards that are within 3 feet of the pool

NEC Reference: NEC 2026 — 680.26(B)(6)

Question 7: Per NEC 680.21(C), outlets supplying pool pump motors on branch circuits rated 150 volts or less to ground and 60 amperes or less (single- or 3-phase) must have:

  • No protection if hard-wired
  • AFCI protection
  • A surge protector
  • GFCI protection

NEC Reference: NEC 2026 — 680.21(C)

Question 8: Per NEC 680.11, underground wiring that is not associated with the pool must not be installed within how far horizontally of the inside wall of the pool, unless necessary for pool equipment?

  • 3 feet
  • 5 feet
  • 20 feet
  • 10 feet

NEC Reference: NEC 2026 — 680.11

Question 9: Per NEC 680.43(A)(1), at an indoor spa or hot tub, receptacles must be located at least how far from the inside walls of the spa?

  • 10 feet
  • 5 feet
  • 3 feet
  • 6 feet

NEC Reference: NEC 2026 — 680.43(A)(1)

Question 10: Per NEC 680.43(A)(2), receptacles within how far of the inside walls of an indoor spa or hot tub must be GFCI protected?

  • 10 feet
  • 20 feet
  • 6 feet
  • 5 feet

NEC Reference: NEC 2026 — 680.43(A)(2)

Question 11: Per NEC 680.44, the outlet(s) supplying a self-contained spa or hot tub, or a packaged equipment assembly, must have:

  • Overload protection only
  • A twist-lock receptacle
  • GFCI protection
  • AFCI protection only

NEC Reference: NEC 2026 — 680.44

Question 12: Per NEC 680.71, receptacles within how far of the inside walls of a hydromassage bathtub must be GFCI protected?

  • 10 feet
  • 5 feet
  • 6 feet
  • 3 feet

NEC Reference: NEC 2026 — 680.71

Question 13: Per NEC 680.73, the hydromassage tub's electrical equipment (such as the pump motor) must be:

  • Sealed inside the tub apron with tile
  • Located in the attic
  • Accessible without damaging the building structure or finish
  • Installed outdoors

NEC Reference: NEC 2026 — 680.73

Question 14: Per NEC 680.8(A), a cord-and-plug-connected pool filter pump or other fixed equipment may have a flexible cord no longer than:

  • 10 feet
  • 15 feet
  • 6 feet
  • 3 feet

NEC Reference: NEC 2026 — 680.8(A)

Question 15: Per NEC 590.6(A)(1), on a construction site, which receptacles need GFCI protection for personnel?

  • Only outdoor receptacles
  • Only receptacles on generators larger than 15 kW
  • Only receptacles used for lighting
  • All 125-volt, single-phase, 15-, 20- and 30-ampere receptacles that are not part of the permanent wiring

NEC Reference: NEC 2026 — 590.6(A)(1)

Question 16: Per NEC 590.4(D), receptacles on construction sites must not be installed on branch circuits that:

  • Are protected by GFCI
  • Are installed in boxes
  • Supply temporary lighting
  • Are rated 20 amperes

NEC Reference: NEC 2026 — 590.4(D)

Question 17: Per NEC 590.3(A), temporary electric power and lighting installations are permitted during the period of:

  • Construction, remodeling, maintenance, repair, demolition or similar activities
  • Only 30 days, after which permanent wiring must be installed
  • Up to 5 years for any purpose, with AHJ approval
  • Only while the AHJ is present on the construction site

NEC Reference: NEC 2026 — 590.3(A)

Question 18: Per NEC 590.4(J), temporary cables and cords must be supported at intervals that protect them from damage, and:

  • They may be tied to tree branches
  • They may be laid on the ground in walkways
  • They may be nailed to the framing with bare nails
  • Vegetation (such as trees) must not be used to support overhead spans

NEC Reference: NEC 2026 — 590.4(J)

Question 19: Per NEC 500.5(B), a Class I, Division 2 location is one where ignitible gases or vapors are:

  • Present only as combustible dust in the air
  • Never present, even if equipment fails or leaks
  • Present under normal operating conditions most of the time
  • Normally confined in closed systems and escape only by accidental rupture or abnormal operation

NEC Reference: NEC 2026 — 500.5(B)

Question 20: Per NEC 501.10(A)(1), which wiring method is permitted in a Class I, Division 1 location?

  • Threaded rigid metal conduit or threaded steel IMC
  • Type NM cable
  • EMT with setscrew fittings
  • Flexible cord for all equipment

NEC Reference: NEC 2026 — 501.10(A)(1)

Question 21: Per NEC 511.12, in commercial garage areas where electrical diagnostic equipment, electrical hand tools or portable lighting equipment are used, 125-volt, single-phase, 15- and 20-ampere receptacles must have:

  • GFCI protection for personnel
  • AFCI protection
  • A twist-lock configuration only
  • Surge protection only

NEC Reference: NEC 2026 — 511.12

Question 22: Per NEC 514.11(A), each circuit leading to or through gasoline dispensing equipment must have a means that:

  • Simultaneously disconnects all ungrounded conductors and the grounded conductor (emergency electrical disconnect)
  • Disconnects only the neutral conductor at each dispenser
  • Is located inside each dispenser so it is easy to reach
  • Is a GFCI device that trips on ground faults only

NEC Reference: NEC 2026 — 514.11(A)

Question 23: Per NEC 514.9, a seal fitting is required in each conduit run entering or leaving a dispenser. The seal must be:

  • Installed only in the island junction box
  • Omitted for PVC conduit
  • Located 10 feet from the dispenser
  • The first fitting after the conduit emerges from the earth or concrete

NEC Reference: NEC 2026 — 514.9

Question 24: Per NEC 680.22(C), switching devices (switches, timers) for pool equipment must be located at least how far horizontally from the inside walls of the pool, unless separated by a solid fence, wall or other permanent barrier?

  • 20 feet
  • 10 feet
  • 3 feet
  • 5 feet

NEC Reference: NEC 2026 — 680.22(C)

Question 25: Per NEC 500.5(D), a Class III location is one that is hazardous because of:

  • Flammable gases or vapors released by fuel storage tanks
  • Easily ignitible fibers or flyings, such as in textile mills and woodworking plants
  • Explosive solids stored in magazines or bunkers
  • Combustible dust such as grain, flour or coal dust

NEC Reference: NEC 2026 — 500.5(D)

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
EXAM CARD JOURNEYMAN
Questions25
Time limit38 min
Pass score70%
Code editionNEC 2026
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)