JOURNEYMAN NEC 2026

NEC 2026 Journeyman Practice Test 5

Free Online Journeyman Electrician Practice Test — NEC 2026 Edition 5This free 25-question practice test covers wiring methods such as NM cable, EMT, and flexible conduit, key NEC Article 100 definitions, working space clearances, and several detailed 2026 NEC emergency disconnect (230.85) scenarios. Based on the 2026 National Electrical Code.

TOPICS COVERED
journeyman electrician

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 38 min for 25 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account required. All questions include detailed explanations and NEC references.

Most state Journeyman exams have 80–100 questions covering NEC code, wiring methods, branch circuits, motor controls, and load calculations.

Most states require a 70–75% passing score. This practice test uses the same 70% pass threshold so you know where you stand.

Questions are written to the 2026 NEC. Check your state licensing board to confirm which edition your state has adopted.

How to Use This Practice Test

This NEC 2026 Journeyman Practice Test 5 has 25 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: This is an open-book exam — tab your NEC index and Articles 210, 250, and 430 before you start.

  • Topics covered: Branch circuits, grounding, wiring methods, load calculations, and motors.
  • Passing score: 70–75% (most states). Aim for 80% on practice tests so the real exam feels easy.
  • Questions: 25 multiple-choice, one correct answer each
25
Questions
38 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

JOURNEYMAN · NEC 2026
NEC 2026 Journeyman Practice Test 5
Q1 / 25
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2026 Journeyman Practice Test 5 — Question List

Question 1: A cable is run through bored holes in roof rafters. Per NEC 300.4(A)(1), where the edge of the bored hole is less than 1-1/4 inches from the nearest edge of the rafter, the cable must be protected by:

  • A steel plate or bushing not less than 1/16 inch thick
  • Additional cable ties only
  • A larger-diameter hole
  • Nothing — rafters are exempt from this rule

NEC Reference: NEC 300.4(A)(1)

Question 2: Per NEC 300.4(D), where a cable or raceway is installed parallel to framing members such as studs, joists, or rafters, it must be installed so that it is not less than what distance from the nearest edge of the framing member, or otherwise protected?

  • 3/4 inch
  • 1 inch
  • 1-1/4 inches
  • 2 inches

NEC Reference: NEC 300.4(D)

Question 3: Per NEC Table 300.5, a UF cable installed under a one-family dwelling's residential driveway, supplying a 120V, 20A circuit protected by GFCI, generally requires a minimum burial depth of:

  • 6 inches
  • 12 inches
  • 18 inches
  • 24 inches

NEC Reference: NEC Table 300.5

Question 4: Per NEC 300.11(A), raceways and cables must be securely fastened in place and are NOT permitted to be supported by:

  • Independent support wires installed specifically for that purpose
  • A fire-rated ceiling's support wires used solely for that purpose
  • Ceiling grid or ceiling support wires of a suspended ceiling not installed for that purpose
  • Structural building members

NEC Reference: NEC 300.11(A)

Question 5: Per NEC 334.80, even though NM cable conductors may be rated 90 degrees C, the ampacity of NM cable must be determined using the:

  • 90°C column of Table 310.16
  • 75°C column of Table 310.16
  • 60°C column of Table 310.16
  • Average of the 60°C and 90°C columns

NEC Reference: NEC 334.80

Question 6: Per NEC Article 336, Type TC (power and control tray cable) is permitted to be installed in cable trays, in raceways, and, where specifically listed for the purpose,:

  • Directly buried, if identified for that use
  • Only in dry indoor locations
  • Never outdoors
  • Only in residential dwellings

NEC Reference: NEC 336.10

Question 7: Per NEC 358.12, electrical metallic tubing (EMT) is not permitted to be installed:

  • In cinder concrete or cinder fill subject to permanent moisture, unless protected
  • In any concrete slab, under any condition
  • Above a suspended ceiling
  • In dry locations

NEC Reference: NEC 358.12

Question 8: Per NEC 350.60, liquidtight flexible metal conduit (LFMC) is permitted to serve as the equipment grounding conductor only where the total length in any ground-fault current path does not exceed:

  • 3 feet
  • 6 feet
  • 10 feet
  • 25 feet

NEC Reference: NEC 350.60

Question 9: Per NEC 110.14(C)(1)(a), for equipment rated 100 amperes or less, conductor ampacity used for termination purposes must generally be based on the:

  • 90°C column, regardless of equipment listing
  • 75°C column, always
  • 60°C column, unless the equipment is listed and marked for a higher temperature
  • The conductor's actual insulation rating, with no adjustment

NEC Reference: NEC 110.14(C)(1)(a)

Question 10: Per NEC Table 110.26(A)(1), for equipment operating at 0-150 volts to ground under Condition 2 (exposed live parts on one side, grounded parts on the other), the minimum working space depth is:

  • 2 feet 6 inches
  • 3 feet
  • 3 feet 6 inches
  • 4 feet

NEC Reference: NEC Table 110.26(A)(1)

Question 11: Per NEC 110.3(B), listed or labeled equipment must be:

  • Installed and used per any instructions included in the listing or labeling
  • Installed however the electrician judges best, ignoring manufacturer instructions
  • Re-inspected annually regardless of use
  • Exempt from all other NEC requirements

NEC Reference: NEC 110.3(B)

Question 12: Per NEC Article 100, a "Dwelling Unit" is defined as a single unit providing complete, independent living facilities, including permanent provisions for:

  • Living, sleeping, cooking, and sanitation
  • Cooking only
  • Sleeping only
  • Parking and storage only

NEC Reference: NEC Article 100

Question 13: Per NEC Article 100, a "Qualified Person" is one who has skills and knowledge related to the construction and operation of the electrical equipment and installations, and who has received:

  • Safety training to recognize and avoid the hazards involved
  • A four-year engineering degree only
  • No specific training — job title alone qualifies them
  • Only a general contractor's license

NEC Reference: NEC Article 100

Question 14: Per NEC Article 100, a "Branch Circuit" is defined as the circuit conductors between the final overcurrent device protecting the circuit and the:

  • Outlet(s)
  • Service equipment
  • Utility transformer
  • Grounding electrode

NEC Reference: NEC Article 100

Question 15: Per NEC 400.12, flexible cords and cables are NOT permitted to be used as a substitute for:

  • The fixed wiring of a structure
  • Pendant connections to luminaires
  • Connection of portable appliances
  • Elevator cables

NEC Reference: NEC 400.12(1)

Question 16: Per NEC 410.16(B), a surface-mounted incandescent or LED luminaire installed in a clothes closet, without a completely enclosed light source, must maintain a minimum clearance from the nearest point of a storage space of:

  • 6 inches
  • 12 inches
  • 18 inches
  • 24 inches

NEC Reference: NEC 410.16(B)

Question 17: Per NEC Article 725, a Class 2 power-limited circuit is characterized by its power source being limited such that, under both normal and fault conditions, it:

  • Does not require the level of overcurrent protection or wiring methods required for electric light and power circuits
  • Requires the same overcurrent protection as a 120V branch circuit
  • May never be run in the same raceway as any other circuit
  • Must always use 12 AWG minimum conductors

NEC Reference: NEC Article 725

Question 18: Per NEC 344.10(D) and 342.10, rigid metal conduit (RMC) and intermediate metal conduit (IMC) installed in a corrosive environment must be protected by:

  • A corrosion-resistant material, such as PVC coating, or an approved method for the environment
  • No additional protection is ever required
  • A layer of tape only
  • Painting with any exterior paint

NEC Reference: NEC 344.10(D) / 342.10

Question 19: Per the 2026 NEC 230.85(A)(2), which of the following satisfies the emergency disconnect requirement for a one-family dwelling?

  • A meter disconnect installed per 230.82(3) and marked as the emergency disconnect
  • The main breaker of an interior subpanel
  • Any feeder disconnect downstream of the service
  • A 200A indoor panel in the laundry room

NEC Reference: NEC 2026 — 230.85(A)(1)-(3)

Question 20: A one-family dwelling has an existing 150A indoor service installed under an older NEC edition. The homeowner is only replacing the roof, with no electrical work performed. Per the 2026 NEC, must an emergency disconnect be added because of this reroofing project?

  • Yes, any 2026-permitted project on the property triggers 230.85
  • No, the existing service is not retroactively required to comply absent service alteration
  • Only if the roofer is also a licensed electrician
  • Only if the service is over 100A

NEC Reference: NEC 2026 — 230.85, scope

Question 21: Where two through six service disconnects are grouped at a dwelling to satisfy 230.71, per the 2026 NEC 230.85(D), each disconnect used to satisfy the emergency disconnect requirement must be:

  • Ganged together and operated by a single handle
  • Individually marked and may be operated independently
  • Limited to a maximum of two disconnects
  • Exempt from any emergency disconnect marking

NEC Reference: NEC 2026 — 230.85(D)

Question 22: A one-family dwelling uses a meter-combination enclosure that includes the service disconnect inside the same enclosure as the meter. Per the 2026 NEC 230.85(A)(1), may this equipment serve as the emergency disconnect?

  • Yes, provided it is marked "EMERGENCY DISCONNECT, SERVICE DISCONNECT"
  • No, meter-combination enclosures are excluded from 230.85
  • Only if a second, separate device is also installed
  • Only in rural jurisdictions

NEC Reference: NEC 2026 — 230.85(A)(1)

Question 23: Where the emergency disconnect is a stand-alone device installed ahead of the service equipment, per the 2026 NEC 230.85(C), the conductors between that disconnect and the service equipment are considered:

  • Feeder conductors
  • Service conductors
  • Branch-circuit conductors
  • Tap conductors under 240.21(B)

NEC Reference: NEC 2026 — 230.85(C)

Question 24: A dwelling has a solar PV system interconnected at the load side of the service equipment, with its own rapid shutdown system per Article 690. Per the 2026 NEC, does the 230.85 emergency disconnect need to also disconnect the PV system?

  • Yes, 230.85 always includes PV systems
  • No, the PV system has its own disconnecting means and rapid shutdown under Article 690
  • Only if the PV system exceeds 30kW
  • Only if the PV uses string inverters

NEC Reference: NEC 2026 — 230.85 / 690.13

Question 25: A contractor is replacing a damaged service mast and meter base on an existing one-family dwelling, and the AHJ requires the work to comply with the 2026 NEC. Per 230.85, is an emergency disconnect generally required as part of this work?

  • No, existing services are always exempt regardless of the scope of work
  • Yes, when the service is materially altered, the AHJ generally requires 230.85 compliance as part of the work
  • Only if the amperage is increased
  • Only if the homeowner requests it

NEC Reference: NEC 2026 — 230.85, scope

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
EXAM CARD JOURNEYMAN
Questions25
Time limit38 min
Pass score70%
Code editionNEC 2026
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)