NEC CODE NEC 2023

Voltage Drop Calculations (NEC Chapter 9) — NEC 2023 Edition

Free NEC 2023 practice test on voltage drop: recommended 3%/5% limits, worked single-phase and three-phase voltage drop calculations, conductor sizing to limit voltage drop, and maximum circuit length. Simple English, full explanations.

TOPICS COVERED
NEC Questions NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 15 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Voltage Drop Calculations (NEC Chapter 9) — NEC 2023 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
15 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2023
Voltage Drop Calculations (NEC Chapter 9) — NEC 2023 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Voltage Drop Calculations (NEC Chapter 9) — NEC 2023 Edition — Question List

Question 1: What is the minimum NEC recommended voltage for a 230 volt load connected to 240 v source?

  • 230 V
  • 228 V
  • 232 V
  • 225 V

Question 2: If a 115 volt load is connected to 120 V source. What is minimum voltage that is supplied to the load as recommended by NEC?

  • 114 V.
  • 115 V
  • 120 V
  • 117 V

Question 3: What is the voltage drop of two 10 AWH THHN conductors that supply 16 A, 115 V load located 50 ft from the source?

  • 1.92 V
  • 0,96
  • 2.4 V
  • 1.8 V

Question 4: Two 12 AWG THHN conductors are placed to connect 8A, 120 V load to the source which is 100 ft distance. What is maximum voltage drop in conductor?

  • 3.2 Volts
  • 6.4 Volts
  • 1.92 Volts
  • 2.4 Volts

NEC Reference: NEC Chapter 9, Table 8 / Informational Note to 215.2(A)

Question 5: A 3 phase 18 KVA, 208 volts load is connected to panel board with 100 ft length of 2AWG THHN copper conductor. What is the approximate voltage drop in the conductor?

  • 1.68 volts
  • 3.2 Volts
  • 2.4 volts
  • 3.8 volts

NEC Reference: NEC Chapter 9, Table 8 / Informational Note to 215.2(A)

Question 6: A 12 KVA , 3 phase 480 Volts load should be connected to panel board with a distance of 220 ft. What size conductor is required to prevent the voltage drop from exceeding 3 %?

  • 12 AWG
  • 10 AWG
  • 8 AWG
  • 14 AWG

NEC Reference: NEC Chapter 9, Table 8 / Informational Note to 215.2(A)

Question 7: A 4 AWG THHN is used to connect a 480 V 3 phase 35 kVA transformer to panel board. what is the maximum length of conductor that can be used in which the voltage drop doesn't cross 3% ?

  • 640 ft
  • 320 ft
  • 720 ft
  • 540 ft

NEC Reference: NEC 14.4

Question 8: What is the maximum voltage drop that is recommended by NEC for both branch and feeder conductors?

  • 3 %
  • 4 %
  • 5 %
  • 6 %

NEC Reference: NEC Chapter 9, Table 8 / Informational Note to 215.2(A)

Question 9: What is 3 phase load that can be connected to a 220 ft, 8 THHN, 480 V conductor with out exceeding the NEC recommended voltage drop?

  • 40 KVA
  • 42 KVA
  • 48 KVA
  • 53 KVA

NEC Reference: NEC 12.9

Question 10: What is maximum voltage drop in percentage recommended by NEC for branch circuit conductors?

  • 3 %
  • 5 %
  • 2 %
  • 4 %

Question 11: The NEC's 3% and 5% voltage drop recommendations are found in Informational Notes. What does that generally mean about their enforceability?

  • They are recommendations, not mandatory requirements
  • They are mandatory and always enforced
  • They apply only to service conductors
  • They were removed from the NEC entirely

NEC Reference: NEC Informational Note to 210.19(A) / 215.2(A)

Question 12: Two 8 AWG THHN copper conductors supply a 20 A, 120 V load located 75 ft from the source. Using R = 0.78 ohm/1000 ft for 8 AWG, what is the approximate voltage drop?

  • 2.34 volts
  • 1.56 volts
  • 3.12 volts
  • 4.68 volts

NEC Reference: NEC Chapter 9, Table 8

Question 13: A calculated voltage drop of 2.34 volts on a 120-volt circuit represents approximately what percentage voltage drop?

  • About 1.95%
  • About 5%
  • About 10%
  • About 0.5%

NEC Reference: NEC Informational Note to 210.19(A)

Question 14: What is "voltage drop," in the context of conductor sizing?

  • Loss of voltage along a conductor due to its resistance
  • A type of overcurrent protection device
  • A required grounding method
  • A conduit fill calculation

NEC Reference: NEC Chapter 9

Question 15: Which of the following generally INCREASES voltage drop on a circuit, all else being equal?

  • Increasing conductor length
  • Increasing conductor size (larger CM area)
  • Decreasing load current
  • None of these affect voltage drop

NEC Reference: NEC Chapter 9

Question 16: Increasing the conductor size (using a larger AWG/kcmil conductor than the minimum required for ampacity) generally has what effect on voltage drop?

  • It decreases voltage drop
  • It increases voltage drop
  • It has no effect at all
  • It always doubles the voltage drop

NEC Reference: NEC Chapter 9

Question 17: What is a common practical consequence of excessive voltage drop on a branch circuit supplying a motor load?

  • The motor runs hot, inefficiently, with reduced starting torque
  • The motor becomes more efficient
  • There is no practical consequence
  • The circuit breaker size must be reduced

NEC Reference: NEC Chapter 9 (general design consideration)

Question 18: In the three-phase voltage drop formula VD = 1.732 x K x I x D / CM, what does the constant 1.732 represent?

  • The square root of 3, for balanced three-phase systems
  • The number of conductors in the circuit
  • The power factor of the load
  • A safety margin with no mathematical basis

NEC Reference: NEC Chapter 9, Table 8

Question 19: In a single-phase voltage drop calculation using conductor resistance from Table 9, why is the one-way distance generally doubled (multiplied by 2)?

  • The circuit includes both the outgoing and returning conductor
  • It is just an arbitrary safety factor
  • It accounts for three-phase power only
  • It has nothing to do with circuit length

NEC Reference: NEC Chapter 9, Table 9

Question 20: In the voltage drop formula, the resistivity constant K is approximately 12.9 for copper. Is the K value for aluminum higher or lower?

  • Higher (aluminum has more resistance)
  • Lower
  • Exactly the same
  • Aluminum has no K value

NEC Reference: NEC Chapter 9, Table 8

Question 21: Two 6 AWG THHN copper conductors supply a 30 A, 240 V load located 150 ft from the source. Using R = 0.49 ohm/1000 ft for 6 AWG, what is the approximate voltage drop?

  • 4.41 volts
  • 2.94 volts
  • 5.88 volts
  • 3.5 volts

NEC Reference: NEC Chapter 9, Table 8

Question 22: A three-phase, 480V circuit has a calculated voltage drop of 9.6 volts. What percentage voltage drop does this represent?

  • 2%
  • 5%
  • 10%
  • 0.2%

NEC Reference: NEC Informational Note to 215.2(A)

Question 23: If a feeder has a 2% voltage drop, what is generally the maximum recommended voltage drop remaining for the branch circuit, to stay within the combined 5% NEC recommendation?

  • 3%
  • 5%
  • 1%
  • 8%

NEC Reference: NEC Informational Note to 210.19(A)

Question 24: In the voltage drop formula VD = 1.732 x K x I x D / CM, what does "CM" represent?

  • The conductor's circular mil area
  • The conduit fill percentage
  • The number of current-carrying conductors
  • The ambient temperature

NEC Reference: NEC Chapter 9, Table 8

Question 25: True or false: voltage drop calculations become more important as the distance between the source and the load increases.

  • True
  • False
  • Only for three-phase circuits
  • Distance has no effect on voltage drop

NEC Reference: NEC Chapter 9

Question 26: A calculated voltage drop of 6 volts on a 120-volt circuit exceeds the 3% branch-circuit recommendation. What is the generally recommended remedy?

  • Use a larger conductor to reduce resistance
  • Use a smaller conductor
  • Increase the circuit breaker size
  • Nothing can be done

NEC Reference: NEC Chapter 9 / Informational Note to 210.19(A)

Question 27: A three-phase, 24 kVA load operates at 208 volts. What is the approximate load current?

  • About 66.6 amperes
  • About 115 amperes
  • About 40 amperes
  • About 24 amperes

NEC Reference: NEC Chapter 9 (three-phase power formula)

Question 28: For circuits supplying sensitive electronic equipment, why might a design engineer choose to target voltage drop well BELOW the NEC's 3%/5% recommendations?

  • Sensitive equipment can be more susceptible to voltage variation
  • The NEC requires a stricter limit for electronics
  • It has no practical benefit
  • It is required only for motors, not electronics

NEC Reference: NEC Informational Note to 210.19(A)

Question 29: True or false: a conductor sized correctly for ampacity is automatically guaranteed to meet the NEC's recommended voltage drop limits.

  • False -- they are separate checks
  • True -- ampacity sizing always covers voltage drop
  • Voltage drop is not a real concern
  • Ampacity and voltage drop are the same calculation

NEC Reference: NEC Chapter 9 / 310.14

Question 30: A single-phase, 120V, 12A load is supplied by two 10 AWG THHN conductors (R = 1.2 ohm/1000 ft). What is the maximum one-way distance to keep voltage drop at or under 3% (3.6 volts)?

  • 125 ft
  • 250 ft
  • 62.5 ft
  • 100 ft

NEC Reference: NEC Chapter 9, Table 9

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit15 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)