Panelboards and Switchboards (NEC 408) — NEC 2023 Edition

Free NEC 2023 practice test on panelboards and switchboards. Covers overcurrent protection, wet-location clearances, neutral terminal rules, high-leg (wild leg) marking, and transformer-fed panelboard protection. Simple English, full explanations.

Share this test
TOPICS COVERED
NEC Questions NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Panelboards and Switchboards (NEC 408) — NEC 2023 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2023
Panelboards and Switchboards (NEC 408) — NEC 2023 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Panelboards and Switchboards (NEC 408) — NEC 2023 Edition — Question List

Question 1: In a panelboard, may two grounded (neutral) conductors be connected under one terminal?

  • Yes, always
  • Yes, if the panel is in a dwelling
  • No, unless the terminal is identified for more than one conductor
  • Yes, if both are the same size

NEC Reference: NEC 408.41

Question 2: When a panelboard enclosure is mounted in a wet location, how much air space is generally required between the enclosure and the mounting surface?

  • 1/4 inch
  • 1/2 inch
  • 3/4 inch
  • 1 inch

NEC Reference: NEC 312.2(A)

Question 3: When a panelboard is supplied by a transformer, the panelboard's overcurrent protection must generally be placed on which side of the transformer?

  • Primary
  • Secondary
  • Neither side
  • Both sides equally required

NEC Reference: NEC 408.36(B)

Question 4: The rating of the overcurrent protective device supplying a panelboard should generally be what, compared to the panelboard's own rating?

  • Not be greater than the panelboard rating
  • Be 125% of the panelboard rating
  • Be greater than the panelboard rating
  • Be 115% of the panelboard rating

NEC Reference: NEC 408.36

Question 5: On a 3-phase, 4-wire delta system with a high-leg (wild leg) conductor, that high-leg conductor must terminate on which phase (bus position) of the panelboard or switchboard?

  • A, or first phase
  • B, or center phase
  • C, or third phase
  • Any phase, no restriction

NEC Reference: NEC 408.3(E)

Question 6: Where accessible, the high-leg (wild leg) conductor of a 4-wire delta system must be identified by what color?

  • Orange
  • Green
  • Blue
  • White

NEC Reference: NEC 110.15

Question 7: For a switchboard rated 0-150 volts to ground under Condition 1, what is the minimum required clear working space depth?

  • 3 feet
  • 1 foot
  • 6 feet
  • 10 feet

NEC Reference: NEC Table 110.26(A)(1)

Question 8: Where must a panelboard circuit directory be located?

  • Only on the as-built drawings
  • On the face, inside the door, or in an approved location next to the panelboard
  • On the utility meter enclosure
  • In the building maintenance office

NEC Reference: NEC 408.4(A)

Question 9: What limits the number of overcurrent devices that may be installed in a panelboard?

  • The number of spaces the electrician can fit
  • A fixed maximum of 42 devices
  • The number for which the panelboard is designed, rated and listed
  • A fixed maximum of 30 devices

NEC Reference: NEC 408.54

Question 10: What must the rating of a panelboard be at least?

  • The minimum feeder capacity for the load calculated under Article 220
  • The sum of all its breaker ratings
  • Twice the connected load
  • The rating of the service

NEC Reference: NEC 408.30

Question 11: How must panelboards be enclosed?

  • In a nonmetallic box only
  • In any metal box with exposed bus
  • In an open frame with a guard rail
  • In cabinets or cutout boxes, and of dead-front construction

NEC Reference: NEC 408.38

Question 12: A panelboard is installed in a wet location. What rule applies to its enclosure?

  • It must be raised 3 ft above the floor
  • It needs only a gasketed front cover
  • 312.2: weatherproof and installed to prevent moisture from accumulating
  • No special rule applies indoors

NEC Reference: NEC 408.37

Question 13: A panelboard is supplied through nonmetallic raceway. What must be provided inside the cabinet for the equipment grounding conductors?

  • A splice box outside the panel
  • A terminal bar bonded to the cabinet
  • A separate ground rod
  • Nothing; the neutral bar is used

NEC Reference: NEC 408.40

Question 14: A switchboard rated 1,200 A is more than 6 ft wide. What does 110.26(C)(2) require for its working space?

  • A fire-rated door only
  • One entrance at the center only
  • No special entrance rules
  • An entrance at each end of the working space

NEC Reference: NEC 110.26(C)(2)

Question 15: At the service, which component connects the equipment grounding conductors to the grounded (neutral) conductor?

  • The main bonding jumper
  • An equipment bonding jumper at each subpanel
  • The system bonding jumper of a transformer
  • The grounding electrode conductor

NEC Reference: NEC 250.28

Question 16: In a subpanel fed by a feeder from the service, how are the grounded (neutral) and equipment grounding conductors terminated?

  • On the same bar, bonded together
  • On separate, isolated bars
  • Either way is permitted
  • Neutrals to the enclosure, grounds to a rod

NEC Reference: NEC 250.142(B)

Question 17: Service equipment in a building other than a dwelling unit must be field marked with what?

  • The utility transformer size only
  • The arc-flash PPE category
  • The maximum available fault current and the date of the calculation
  • The installer's license number

NEC Reference: NEC 110.24(A)

Question 18: How must unused breaker openings in a panelboard be closed?

  • With identified closures or equal protection
  • With the removed knockout taped back in place
  • They may be left open in dwelling units
  • With a blank breaker of any brand

NEC Reference: NEC 408.7

Question 19: A switchboard that is not totally enclosed is installed under a combustible ceiling. What minimum space is required above it?

  • 6 ft
  • 18 in.
  • 1 ft
  • 3 ft

NEC Reference: NEC 408.18(A)

Question 20: Minimum wire-bending space at terminals in cabinets and cutout boxes is found in which tables?

  • Table 314.16(A)
  • Table 310.16
  • Chapter 9, Table 1
  • Tables 312.6(A) and 312.6(B)

NEC Reference: NEC 312.6

Question 21: Barriers are required in service switchboards and panelboards so that what is not exposed while load terminations are serviced?

  • Uninsulated, ungrounded service busbars and terminals
  • The equipment grounding bar
  • The neutral bar
  • The branch-circuit breakers

NEC Reference: NEC 408.3(A)(2)

Question 22: A back-fed circuit breaker supplies power into a panelboard (other than as permitted for listed interactive inverters). How must it be secured?

  • With a handle tie only
  • It needs no special securing
  • With electrical tape over the handle
  • With an additional fastener that requires other than a pull to release

NEC Reference: NEC 408.36(D)

Question 23: What is the minimum height of the working space in front of a panelboard (unless the equipment is taller)?

  • 6 ft
  • 6½ ft
  • 7 ft
  • 8 ft

NEC Reference: NEC 110.26(A)(3)

Question 24: What does the NEC require for indoor working spaces around service equipment, switchboards and panelboards?

  • A dedicated HVAC supply
  • A floor drain
  • Illumination
  • A fire extinguisher

NEC Reference: NEC 110.26(D)

Question 25: Where multiple service disconnects are grouped at a single switchboard location, per NEC 230.71, what is the maximum number generally allowed for most occupancies?

  • 6
  • 2
  • 10
  • There is no limit

NEC Reference: NEC 230.71(B)

Question 26: In other than one- and two-family dwellings, a panelboard supplied by a feeder must be marked with what?

  • The building square footage
  • Where its power supply originates
  • The date of installation
  • The name of the electrician

NEC Reference: NEC 408.4(B)

Question 27: On a 3-phase panelboard or switchboard bus, what is the required phase arrangement?

  • C, B, A from left to right
  • A, B, C from front to back, top to bottom, or left to right
  • B phase always on the left
  • Any order, if marked

NEC Reference: NEC 408.3(E)(1)

Question 28: Which circuit directory description is NOT acceptable under 408.4(A)?

  • "Bob's office"
  • "Kitchen counter receptacles, north wall"
  • "Furnace - basement"
  • "Exterior lights - front entry"

NEC Reference: NEC 408.4(A)

Question 29: A feeder from the main building supplies a separate detached building. What is required for that building?

  • A second service drop
  • A separate utility meter
  • A disconnecting means for the conductors supplying it
  • Nothing beyond the feeder breaker in the main building

NEC Reference: NEC 225.31

Question 30: Equipment protected by a tested series combination rating must be field marked to show what?

  • The name of the testing laboratory
  • The available fault current only
  • The installation date only
  • That it is series rated and identified replacement components are required

NEC Reference: NEC 110.22(C)

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)