NEC CODE NEC 2020

Service Entrance, Branch Circuits & Feeder Conductors 2 — NEC 2020 Edition

Free NEC 2020 practice test on service entrance, feeders, and branch circuits. Covers feeder ampacity sizing, dwelling and commercial lighting load demand, receptacle load calculations, service disconnect rules, and unbalanced load. Simple English, full explanations.

Share this test
TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Service Entrance, Branch Circuits & Feeder Conductors 2 — NEC 2020 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2020
Service Entrance, Branch Circuits & Feeder Conductors 2 — NEC 2020 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Service Entrance, Branch Circuits & Feeder Conductors 2 — NEC 2020 Edition — Question List

Question 1: A feeder supplies 60 A of continuous load and 30 A of noncontinuous load. What is the minimum standard overcurrent device rating?

  • 90 A
  • 100 A
  • 110 A
  • 125 A

NEC Reference: NEC 215.3

Question 2: A dwelling unit has a general lighting connected load of 4,000 VA. What is the total demand load after applying the lighting demand factor?

  • 3,350 VA
  • 4,000 VA
  • 3,200 VA
  • 3,600 VA

NEC Reference: NEC Table 220.42

Question 3: What is the branch-circuit load calculated for a show window that is 10 feet wide?

  • 2,000 VA
  • 1,800 VA
  • 1,600 VA
  • 2,200 VA

NEC Reference: NEC 220.14(G)

Question 4: How many 15-ampere, 14 AWG branch circuits are minimally required to supply the general lighting load for a 2,000 sq ft dwelling unit at 120 volts?

  • 3
  • 4
  • 5
  • 6

NEC Reference: NEC 220.14(J) / 210.11(A)

Question 5: A retail shop has 20 duplex receptacles, each on its own yoke. What is the calculated load for these receptacles?

  • 300 volt-amperes
  • 3,600 volt-amperes
  • 1,800 volt-amperes
  • 36,000 volt-amperes

NEC Reference: NEC 220.14(I)

Question 6: In a shopping complex, what is the maximum number of receptacles generally permitted on a 20-ampere, 120-volt breaker, using the standard 180 VA per receptacle?

  • 13
  • 10
  • 18
  • 11

NEC Reference: NEC 220.14(I)

Question 7: A single piece of equipment has five receptacles built into it. What is the total calculated load for these receptacles?

  • 450 volt-amperes
  • 900 volt-amperes
  • 600 volt-amperes
  • 800 volt-amperes

NEC Reference: NEC 220.14(I)

Question 8: A 1,200 sq ft dwelling unit is supplied at 120/240 V. What is the minimum number of 15-ampere, 2-wire general lighting branch circuits?

  • 1
  • 2
  • 3
  • 4

NEC Reference: NEC 220.14(J) / 210.11(A)

Question 9: What is the minimum laundry circuit load that must be considered for each 2-wire laundry branch circuit in a dwelling unit?

  • 1,500 Volt-Amperes
  • 1,200 Volt-Amperes
  • 1,000 Volt-Amperes
  • 800 Volt-Amperes

NEC Reference: NEC 220.52(B)

Question 10: For sizing a feeder or service neutral, how is the maximum unbalanced load defined?

  • The largest single appliance load
  • The difference between the largest and smallest loads
  • The total load of all phases added together
  • The maximum net calculated load between the neutral and any one ungrounded conductor

NEC Reference: NEC 220.61(A)

Question 11: What is the maximum number of service disconnecting means permitted for one service, grouped at one location?

  • 6
  • 2
  • 10
  • There is no limit

NEC Reference: NEC 230.71(B)

Question 12: For a one-family dwelling, what is the minimum rating required for the service disconnecting means?

  • 100 amperes
  • 60 amperes
  • 125 amperes
  • 200 amperes

NEC Reference: NEC 230.79(C)

Question 13: What is the general minimum vertical clearance of overhead service conductors above a roof surface?

  • 3 ft
  • 8 ft
  • 8 ft 6 in.
  • 10 ft

NEC Reference: NEC 230.24(A)

Question 14: A service mast supports the service-drop conductors. What must it be?

  • Of adequate strength, or supported by braces or guys
  • Any listed raceway, regardless of strength
  • Made only of PVC conduit
  • Shorter than 3 ft above the roof

NEC Reference: NEC 230.28

Question 15: What is the general minimum size of underground service-lateral conductors?

  • 4 AWG copper or 2 AWG aluminum
  • 8 AWG copper or 6 AWG aluminum
  • 6 AWG copper or 4 AWG aluminum
  • 1/0 AWG copper or 2/0 AWG aluminum

NEC Reference: NEC 230.31(B)

Question 16: Per the NEC informational note, what is the recommended maximum COMBINED voltage drop for a feeder plus branch circuit together?

  • 5%
  • 3%
  • 10%
  • 1%

NEC Reference: NEC 215.2(A) Informational Note

Question 17: Service-entrance cable is subject to physical damage. Which method may protect it?

  • Schedule 80 PVC conduit
  • Flexible metal conduit
  • Schedule 40 PVC conduit
  • A wrap of vinyl tape

NEC Reference: NEC 230.50(A)

Question 18: How must each service disconnecting means be marked?

  • With the electrician's license number
  • With the date of installation
  • With the utility meter number
  • Permanently marked to identify it as a service disconnect

NEC Reference: NEC 230.70(B)

Question 19: Where must the service disconnecting means be installed?

  • Anywhere in the building
  • At a readily accessible location nearest the point of entrance of the service conductors
  • In a locked closet with the key kept by the utility
  • In an attic above the service entrance

NEC Reference: NEC 230.70(A)(1)

Question 20: For a grounded service, where may the grounding electrode conductor connect to the grounded service conductor?

  • Only at the first branch-circuit panelboard
  • At any accessible point from the service drop or lateral to the service disconnect neutral terminal
  • Only at the utility transformer
  • At any subpanel on the premises

NEC Reference: NEC 250.24(A)(1)

Question 21: Under the 10-foot feeder tap rule, tap conductors not over 10 feet long must have an ampacity of not less than what?

  • The load served or terminating device rating
  • Any size at all
  • Half the feeder size
  • A fixed 15 amperes

NEC Reference: NEC 240.21(B)(1)

Question 22: In a multiple-occupancy building, what access must each occupant have to service disconnecting means?

  • Access to the disconnect(s) serving that occupancy, unless the building has continuous management supervision
  • No access; only the utility may operate them
  • Access to every disconnect in the building
  • Access only through the building owner by appointment

NEC Reference: NEC 230.72(C)

Question 23: Ungrounded service-entrance conductors must have an ampacity not less than what?

  • Half the rating of the service disconnect
  • The utility transformer rating
  • The rating of the service disconnecting means
  • Twice the rating of the service disconnect

NEC Reference: NEC 230.42(B)

Question 24: Where must a service head be located?

  • Inside the attic
  • At least 10 ft from the point of attachment
  • Below the point of attachment, for drainage
  • Above the point of attachment of the service-drop conductors

NEC Reference: NEC 230.54(C)

Question 25: For service equipment rated 0-150 volts to ground under Condition 1, what is the minimum required clear working space depth?

  • 3 feet
  • 1 foot
  • 6 feet
  • 10 feet

NEC Reference: NEC Table 110.26(A)(1)

Question 26: For a single dwelling unit, the "optional" feeder or service load calculation method can be used instead of the standard method under which condition?

  • Single 120/240V or 208Y/120V service, 100A or more
  • Only for buildings with 3-phase power
  • Only for services under 60 amperes
  • It can never be used for dwellings

NEC Reference: NEC 220.82

Question 27: An underground service raceway enters a building. What does 230.8 require?

  • A drip loop at the entry
  • Sealing or plugging the raceway at either or both ends
  • Leaving the raceway open to drain
  • Filling the raceway with sand

NEC Reference: NEC 230.8

Question 28: What must the rating of the service disconnecting means be at least?

  • The calculated load to be carried, determined per Article 220
  • The utility transformer rating
  • The size of the meter base
  • The rating of the largest branch circuit

NEC Reference: NEC 230.79

Question 29: A two-family dwelling has an individually metered feeder to each unit. On what load is each unit's feeder sized?

  • Half of the whole building load
  • The service rating of the building
  • That unit's own calculated load
  • The largest appliance in the building

NEC Reference: NEC 220.40

Question 30: How must listed service equipment be installed?

  • In any way that fits the space
  • With extra fasteners only
  • As the inspector decides on site
  • In accordance with its listing and labeling instructions

NEC Reference: NEC 110.3(B)

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)