Overcurrent Protection Practice Test 2 (NEC 240) — NEC 2020 Edition

Free NEC 2020 practice test on overcurrent protection. Covers conductor protection limits, standard fuse/breaker sizing, next-size-up rounding, branch-circuit device location, multiwire circuits, and special equipment protection (welders, transformers). Simple English, full explanations.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Overcurrent Protection Practice Test 2 (NEC 240) — NEC 2020 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2020
Overcurrent Protection Practice Test 2 (NEC 240) — NEC 2020 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Overcurrent Protection Practice Test 2 (NEC 240) — NEC 2020 Edition — Question List

Question 1: What is the maximum standard overcurrent device size generally allowed to protect a 12 AWG copper conductor?

  • 20 amperes
  • 15 amperes
  • 25 amperes
  • 30 amperes

NEC Reference: NEC 240.4(D)(5)

Question 2: On a residential electric service, which conductors generally require overcurrent protection?

  • Ungrounded conductors
  • Grounded conductors
  • Neutral conductors
  • Equipment grounding conductors

NEC Reference: NEC 240.21

Question 3: Three single-phase motors, with full-load currents of 20, 25, and 30 amperes, are connected to a 240-volt circuit. What dual-element fuse size can be used for the group?

  • 110 amperes
  • 150 amperes
  • 200 amperes
  • 175 amperes

NEC Reference: NEC Table 430.52

Question 4: When a fuse or circuit breaker is used as an overcurrent protective device, how must it be connected in the circuit?

  • In series
  • In parallel
  • Both series and parallel
  • It does not matter

NEC Reference: NEC Article 240

Question 5: Where must the branch-circuit overcurrent protective device generally be located in relation to the branch circuit it protects?

  • At the panelboard where it receives power
  • At the equipment ground location
  • At the end of the branch circuit
  • At the power outlet where power is consumed

NEC Reference: NEC 240.21

Question 6: A multiwire branch circuit that is protected by fuses may supply only what type of loads?

  • Line-to-neutral loads
  • Line-to-line loads
  • Receptacle loads only
  • Service loads

NEC Reference: NEC 210.4(C)

Question 7: For a resistance welder, the maximum overcurrent device rating is generally what percent of the welder's rated primary current?

  • Not over 300%
  • Not over 100%
  • Not over 200%
  • Not over 400%

NEC Reference: NEC 630.12

Question 8: What is the maximum overcurrent device rating required for an autotransformer with a full-load input current of 50 amperes?

  • 75 amperes
  • 50 amperes
  • 80 amperes
  • 65 amperes

NEC Reference: NEC 450.4(A)

Question 9: A busway or conductor has an allowable ampacity of 48 amperes, which is not a standard overcurrent device rating. What is the maximum standard overcurrent device rating that may protect it?

  • 50 amperes
  • 40 amperes
  • 60 amperes
  • 70 amperes

NEC Reference: NEC 240.4(B)

Question 10: Per the NEC standard ampere ratings, what is generally the smallest standard fuse or breaker rating commonly used for a 120-volt residential branch circuit?

  • 15 amperes
  • 20 amperes
  • 12 amperes
  • 18 amperes

NEC Reference: NEC 240.6(A)

Question 11: What is the maximum standard overcurrent device size generally allowed to protect a 14 AWG copper conductor?

  • 15 amperes
  • 20 amperes
  • 25 amperes
  • 30 amperes

NEC Reference: NEC 240.4(D)(3)

Question 12: What is the maximum standard overcurrent device size generally allowed to protect a 10 AWG copper conductor?

  • 30 amperes
  • 25 amperes
  • 35 amperes
  • 40 amperes

NEC Reference: NEC 240.4(D)(7)

Question 13: Which of the following is a standard ampere rating listed in NEC 240.6(A)?

  • 40 amperes
  • 37 amperes
  • 42 amperes
  • 33 amperes

NEC Reference: NEC 240.6(A)

Question 14: Supplementary overcurrent protective devices, as described in NEC 240.10, are used to protect what?

  • Individual pieces of equipment
  • The entire building service
  • Nothing at all
  • Utility company transformers

NEC Reference: NEC 240.10

Question 15: Per NEC 240.24(A), the center of the grip of a circuit breaker handle, in its highest position, must generally not be higher than what height above the floor?

  • 6 feet 7 inches
  • 5 feet
  • 8 feet
  • 10 feet

NEC Reference: NEC 240.24(A)

Question 16: Overcurrent devices must generally not be located in which of the following rooms?

  • Bathrooms
  • Garages
  • Basements
  • Kitchens

NEC Reference: NEC 240.24(E)

Question 17: Under the 10-foot tap rule, a feeder tap conductor not over 10 feet long generally must have an ampacity of not less than what?

  • The load served, and the terminating device rating
  • Any size at all
  • Half the feeder conductor size
  • A fixed 15 amperes always

NEC Reference: NEC 240.21(B)(1)

Question 18: Under the 25-foot tap rule, feeder tap conductors must have an ampacity of not less than what fraction of the ampacity of the feeder overcurrent device?

  • One-third
  • One-half
  • Two-thirds
  • The full ampacity

NEC Reference: NEC 240.21(B)(2)

Question 19: Series-rated overcurrent device combinations must be selected and marked according to what requirement?

  • Their listing and field marking
  • The installer's preference
  • No rule applies
  • The panel color

NEC Reference: NEC 240.86

Question 20: A Type S fuse and its adapter are designed to be what, once installed?

  • Non-removable and non-interchangeable
  • Removable and interchangeable with any fuse
  • Not evaluated for safety at all
  • Made only of glass

NEC Reference: NEC 240.54(B)

Question 21: A cartridge fuse must have a voltage rating that is what, compared to the circuit voltage?

  • Not less than the circuit voltage
  • Always exactly equal
  • Lower than the circuit voltage
  • Voltage rating does not matter

NEC Reference: NEC 240.60(A)

Question 22: A circuit breaker used regularly to switch a circuit on and off must be marked how?

  • "SWD" or "HID" as applicable
  • No special marking is required
  • Only a red sticker
  • The manufacturer's logo only

NEC Reference: NEC 240.83(D)

Question 23: An overcurrent device's interrupting rating must be sufficient for what?

  • The available fault current at that point
  • The device's physical size
  • The room temperature
  • Nothing -- interrupting rating is not regulated

NEC Reference: NEC 110.9

Question 24: A lighting and appliance branch-circuit panelboard must generally be protected by an overcurrent device rated no more than what, relative to the panelboard?

  • Not more than the panelboard rating
  • 150% of the panelboard rating
  • Any rating at all
  • Half the panelboard rating

NEC Reference: NEC 408.36

Question 25: Transformer secondary conductors installed under the 25-foot tap rule for transformers must be protected from physical damage and generally must terminate in what?

  • A single overcurrent device
  • No overcurrent device at all
  • Two separate services
  • A grounding rod only

NEC Reference: NEC 240.21(C)(6)

Question 26: Conductors with a 90 C insulation rating may use the 90 C ampacity column of NEC Table 310.16 for what specific purpose, even if terminations are only rated for 60 C or 75 C?

  • Applying ampacity adjustment/correction factors
  • Ignoring termination ratings completely
  • Nothing -- it is never permitted
  • Doubling the conductor's final rating

NEC Reference: NEC 110.14(C)

Question 27: Feeder conductors must generally be protected against overcurrent in accordance with their what?

  • Ampacity
  • Color
  • Length only
  • Manufacturer preference

NEC Reference: NEC 215.3

Question 28: Can an overcurrent device ever be permitted to open the grounded (neutral) conductor of a circuit?

  • Only if it opens all conductors together
  • Yes, always freely
  • Never under any condition
  • Only on weekends

NEC Reference: NEC 240.22

Question 29: Does the "next size up" rounding rule of NEC 240.4(B) apply to sizing overcurrent protection for transformer secondary conductors under 240.21(C)?

  • True -- it does not apply there
  • False -- it always applies everywhere
  • Only for three-phase transformers
  • Only for autotransformers

NEC Reference: NEC 240.4(B) / 240.21(C)

Question 30: Which of the following is a standard ampere rating listed in NEC 240.6(A), commonly used for larger residential feeders?

  • 60 amperes
  • 55 amperes
  • 65 amperes
  • 58 amperes

NEC Reference: NEC 240.6(A)

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026