Overcurrent Protection Practice Test 1 (NEC 240) — NEC 2020 Edition

Free online NEC Article 240 overcurrent protection practice test. Covers conductor ampacity limits (14/12/10 AWG), standard OCPD ratings, the 10-foot and 25-foot tap rules, plug and cartridge fuse requirements, circuit breaker installation rules, and supplementary overcurrent protection. NEC 2020 edition — ideal for journeyman and master electrician exam preparation.

Share this test
TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Overcurrent Protection Practice Test 1 (NEC 240) — NEC 2020 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2020
Overcurrent Protection Practice Test 1 (NEC 240) — NEC 2020 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Overcurrent Protection Practice Test 1 (NEC 240) — NEC 2020 Edition — Question List

Question 1: Under the 10-foot feeder tap rule, the tap conductors must have an ampacity not less than what?

  • The feeder conductor ampacity
  • The calculated load and the rating of the device they terminate in
  • 125% of the feeder overcurrent device rating
  • One-third of the feeder overcurrent device rating

NEC Reference: NEC 240.21(B)(1)

Question 2: Tap conductors that leave an enclosure or vault must generally have an ampacity of not less than what fraction of the overcurrent device rating protecting the feeder conductors?

  • 1/5
  • 1/10
  • 1/12
  • 1/8

NEC Reference: NEC 240.21(B)(1)(4)

Question 3: A branch-circuit-rated circuit breaker marked for use with 18 AWG copper supplies a continuous load of 5.6 A. What overcurrent protection rating may be used?

  • 7 amperes
  • 10 amperes
  • 15 amperes
  • 20 amperes

NEC Reference: NEC 240.4(D)(1)

Question 4: How must an overcurrent device be connected to the ungrounded conductor it protects?

  • In series with the conductor
  • In parallel with the conductor
  • In the grounded conductor only
  • Across the conductor and ground

NEC Reference: NEC 240.15(A)

Question 5: In which location are overcurrent devices NOT permitted in dwelling units?

  • Basements
  • Bathrooms
  • Garages
  • Laundry rooms

NEC Reference: NEC 240.24(E)

Question 6: What is the maximum voltage between conductors for which plug fuses may generally be used as overcurrent protection?

  • 150 volts
  • 120 volts
  • 240 volts
  • 480 volts

NEC Reference: NEC 240.50(A)

Question 7: Which of these is NOT a standard ampere rating for fuses and inverse-time circuit breakers in 240.6(A)?

  • 25 A
  • 35 A
  • 45 A
  • 55 A

NEC Reference: NEC 240.6(A)

Question 8: A circuit changes from a larger conductor to a smaller conductor with no overcurrent device at the change. The overcurrent device must protect which conductor?

  • The smallest conductor
  • The largest conductor
  • Only the conductor at the panel
  • The average of the two

NEC Reference: NEC 240.4

Question 9: Under the 25-foot feeder tap rule, how must the tap conductors be protected from physical damage?

  • Only by a sign at the tap point
  • They need no protection if they are 25 ft or less
  • By an approved raceway or other approved means
  • By a fuse at each end

NEC Reference: NEC 240.21(B)(2)

Question 10: Per NEC 240.4(D), what is the maximum overcurrent protection permitted for 14 AWG copper conductors in a branch circuit?

  • 10 A
  • 15 A
  • 20 A
  • 25 A

NEC Reference: NEC 240.4(D)(3)

Question 11: Per NEC 240.4(D), what is the maximum overcurrent protection permitted for 12 AWG copper conductors?

  • 15 A
  • 20 A
  • 25 A
  • 30 A

NEC Reference: NEC 240.4(D)(5)

Question 12: Conductors are protected by a 1,200 A overcurrent device. What is their minimum ampacity?

  • 1,000 A
  • 1,100 A
  • 1,200 A
  • 960 A

NEC Reference: NEC 240.4(C)

Question 13: A 25-foot tap conductor runs from a feeder to a subpanel. Per NEC 240.21(B)(2), the tap conductors must terminate in a single circuit breaker or set of fuses rated at no more than what?

  • The rating of the upstream feeder OCPD
  • The ampacity of the tap conductors
  • 125% of the continuous load
  • 1/3 of the feeder OCPD rating

NEC Reference: NEC 240.21(B)(2)(3)

Question 14: Per NEC 240.21(B)(2), for the 25-foot tap rule to apply, the tap conductor ampacity must be not less than what fraction of the upstream feeder overcurrent device rating?

  • 1/10
  • 1/4
  • 1/3
  • 1/2

NEC Reference: NEC 240.21(B)(2)(1)

Question 15: Per NEC 240.6(A), which of the following is NOT a standard ampere rating for fuses and fixed-trip circuit breakers?

  • 60 A
  • 65 A
  • 70 A
  • 80 A

NEC Reference: NEC 240.6(A)

Question 16: Per NEC 240.24(A), the center of the grip of a circuit breaker's handle, in its highest position, shall not be more than what height above the floor or working platform?

  • 5 ft 6 in
  • 6 ft 0 in
  • 6 ft 7 in
  • 7 ft 0 in

NEC Reference: NEC 240.24(A)(1)

Question 17: A cartridge fuse has flat knife-blade contacts at each end, rather than cylindrical ferrule contacts. Per NEC 240.60(B), what does this indicate about the fuse's rating?

  • 30 A or less
  • Exactly 60 A
  • 60 A or less
  • Over 60 A

NEC Reference: NEC 240.60(B)

Question 18: Per NEC 240.22, overcurrent devices shall generally NOT be placed in series with which type of conductor?

  • Ungrounded (hot) conductors
  • Equipment grounding conductors
  • Grounded (neutral) conductors
  • All conductors equally

NEC Reference: NEC 240.22

Question 19: Per NEC 240.24(D), overcurrent devices shall not be located in the vicinity of easily ignitable material. Which specific example does the NEC give?

  • Attached garages
  • Clothes closets
  • Kitchen pantries
  • Utility rooms

NEC Reference: NEC 240.24(D)

Question 20: A circuit breaker has the marking "SWD" on its face plate. Per NEC 240.83(C), this breaker is listed and suitable for use as a switch on which type of circuit?

  • Motor circuits rated 1 HP or less
  • Fluorescent lighting circuits at 120V or 277V
  • Electric resistance heating circuits
  • HVAC compressor circuits

NEC Reference: NEC 240.83(D)

Question 21: Per NEC 240.10, supplementary overcurrent protection found inside luminaires or appliances does what?

  • May substitute for the branch-circuit device
  • Shall not substitute for branch-circuit protection
  • Must equal the branch-circuit device rating
  • Requires a separate disconnect per Article 430

NEC Reference: NEC 240.10

Question 22: Per NEC 240.4(B), when a conductor's ampacity does not correspond to a standard OCPD rating, the next higher standard device rating is permitted only if that next higher rating does not exceed what value?

  • 400 A
  • 600 A
  • 800 A
  • 1,000 A

NEC Reference: NEC 240.4(B)

Question 23: Per NEC 240.80, circuit breakers shall be what?

  • Operable by automatic means only
  • Capable of being opened and closed manually
  • Equipped with a key-operated interlock
  • Rated at a minimum of 30 A

NEC Reference: NEC 240.80

Question 24: Per NEC 240.51(B), Edison-base plug fuses shall be used only in what situation?

  • In all new residential installations
  • As replacements with no evidence of tampering/overfusing
  • In circuits up to 240 V
  • In motor circuits up to 2 HP

NEC Reference: NEC 240.51(B)

Question 25: Per NEC 240.54(C), once a Type S fuse adapter is installed in a fuseholder, what happens?

  • Removable with a screwdriver for changes
  • Non-removable, accepts only that ampere class
  • Accepts any ampere rating of Type S fuse
  • Removed before each replacement fuse

NEC Reference: NEC 240.54(C)

Question 26: What is a current-limiting overcurrent protective device?

  • A breaker with an adjustable long-time setting
  • A fuse that opens only after a 10-second delay
  • A device that limits normal load current to its rating
  • A device that, in its current-limiting range, cuts the fault current to well below the available value

NEC Reference: NEC 240.2

Question 27: Per NEC 240.4(G), overcurrent protection for conductors supplying motor loads is provided according to which NEC article?

  • Article 210
  • Article 220
  • Article 430
  • Article 440

NEC Reference: NEC 240.4(G)

Question 28: Per NEC 240.85, a circuit breaker with a slash voltage rating of "120/240V" may generally be applied on what type of system?

  • Ungrounded delta systems only
  • Corner-grounded delta systems only
  • Solidly grounded systems, voltage to ground under 120V
  • Any system under 240V line-to-line

NEC Reference: NEC 240.85

Question 29: Per the general rule in NEC 240.21(A), overcurrent protection must generally be provided for conductors where?

  • Where they terminate at the load
  • Where they receive their supply
  • At the midpoint of the run
  • Only at the main service disconnect

NEC Reference: NEC 240.21(A)

Question 30: Per NEC 240.4(D), what is the maximum overcurrent protection permitted for 12 AWG aluminum or copper-clad aluminum conductors?

  • 15 A
  • 20 A
  • 25 A
  • 30 A

NEC Reference: NEC 240.4(D)(4)

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020