NEC CODE NEC 2020

Overcurrent Protection Practice Test 1 (NEC 240) — NEC 2020 Edition

Free online NEC Article 240 overcurrent protection practice test. Covers conductor ampacity limits (14/12/10 AWG), standard OCPD ratings, the 10-foot and 25-foot tap rules, plug and cartridge fuse requirements, circuit breaker installation rules, and supplementary overcurrent protection. NEC 2020 edition — ideal for journeyman and master electrician exam preparation.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Overcurrent Protection Practice Test 1 (NEC 240) — NEC 2020 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2020
Overcurrent Protection Practice Test 1 (NEC 240) — NEC 2020 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Overcurrent Protection Practice Test 1 (NEC 240) — NEC 2020 Edition — Question List

Question 1: True or false: under the 10-foot tap rule, the ampacity of a feeder tap conductor not over 10 feet long must be not less than the rating of the overcurrent device where it terminates.

  • True
  • False
  • Only for 3-phase circuits
  • Only for residential circuits

NEC Reference: NEC 240.21(B)(1)

Question 2: Tap conductors that leave an enclosure or vault must generally have an ampacity of not less than what fraction of the overcurrent device rating protecting the feeder conductors?

  • 1/5
  • 1/10
  • 1/12
  • 1/8

NEC Reference: NEC 240.21(B)(1)(4)

Question 3: A branch-circuit rated circuit breaker is marked for use with 18 AWG conductors, supplying a continuous load of 5.6 amperes. What overcurrent protection amperage can be used?

  • 7 amperes
  • 10 amperes
  • 15 amperes
  • 20 amperes

NEC Reference: NEC 240.4(D)(1)

Question 4: True or false: the overcurrent device should be connected in parallel with each ungrounded conductor.

  • True
  • False
  • Only for 3-phase circuits
  • Only for grounded conductors

NEC Reference: NEC 240.20(A)

Question 5: True or false: overcurrent devices are normally located at the point where the conductors deliver energy to the load.

  • True
  • False
  • Only for feeders
  • Only for services

NEC Reference: NEC 240.21

Question 6: What is the maximum voltage between conductors for which plug fuses may generally be used as overcurrent protection?

  • 150 volts
  • 120 volts
  • 240 volts
  • 480 volts

NEC Reference: NEC 240.50(A)

Question 7: Which of the following is NOT a standard ampere rating for a fuse or circuit breaker?

  • 35
  • 45
  • 55
  • 25

NEC Reference: NEC 240.6(A)

Question 8: When two different sizes of wire are connected in series, the overcurrent device rating must protect which wire?

  • The smallest wire
  • The largest wire
  • Both wires equally
  • Neither wire

NEC Reference: NEC 240.4

Question 9: True or false: overcurrent protection is completely eliminated for tap conductors whose length does not exceed 25 feet.

  • True
  • False
  • Only for residential circuits
  • Only for 3-phase circuits

NEC Reference: NEC 240.21(B)(2)

Question 10: Per NEC 240.4(D), what is the maximum overcurrent protection permitted for 14 AWG copper conductors in a branch circuit?

  • 10 A
  • 15 A
  • 20 A
  • 25 A

NEC Reference: NEC 240.4(D)(3)

Question 11: Per NEC 240.4(D), what is the maximum overcurrent protection permitted for 12 AWG copper conductors?

  • 15 A
  • 20 A
  • 25 A
  • 30 A

NEC Reference: NEC 240.4(D)(5)

Question 12: Per NEC 240.4(D), what is the maximum overcurrent protection permitted for 10 AWG copper conductors?

  • 20 A
  • 25 A
  • 30 A
  • 40 A

NEC Reference: NEC 240.4(D)(7)

Question 13: A 25-foot tap conductor runs from a feeder to a subpanel. Per NEC 240.21(B)(2), the tap conductors must terminate in a single circuit breaker or set of fuses rated at no more than what?

  • The rating of the upstream feeder OCPD
  • The ampacity of the tap conductors
  • 125% of the continuous load
  • 1/3 of the feeder OCPD rating

NEC Reference: NEC 240.21(B)(2)(3)

Question 14: Per NEC 240.21(B)(2), for the 25-foot tap rule to apply, the tap conductor ampacity must be not less than what fraction of the upstream feeder overcurrent device rating?

  • 1/10
  • 1/4
  • 1/3
  • 1/2

NEC Reference: NEC 240.21(B)(2)(1)

Question 15: Per NEC 240.6(A), which of the following is NOT a standard ampere rating for fuses and fixed-trip circuit breakers?

  • 60 A
  • 65 A
  • 70 A
  • 80 A

NEC Reference: NEC 240.6(A)

Question 16: Per NEC 240.24(A), the center of the grip of a circuit breaker's handle, in its highest position, shall not be more than what height above the floor or working platform?

  • 5 ft 6 in
  • 6 ft 0 in
  • 6 ft 7 in
  • 7 ft 0 in

NEC Reference: NEC 240.24(A)(1)

Question 17: A cartridge fuse has flat knife-blade contacts at each end, rather than cylindrical ferrule contacts. Per NEC 240.60(B), what does this indicate about the fuse's rating?

  • 30 A or less
  • Exactly 60 A
  • 60 A or less
  • Over 60 A

NEC Reference: NEC 240.60(B)

Question 18: Per NEC 240.22, overcurrent devices shall generally NOT be placed in series with which type of conductor?

  • Ungrounded (hot) conductors
  • Equipment grounding conductors
  • Grounded (neutral) conductors
  • All conductors equally

NEC Reference: NEC 240.22

Question 19: Per NEC 240.24(D), overcurrent devices shall not be located in the vicinity of easily ignitable material. Which specific example does the NEC give?

  • Attached garages
  • Clothes closets
  • Kitchen pantries
  • Utility rooms

NEC Reference: NEC 240.24(D)

Question 20: A circuit breaker has the marking "SWD" on its face plate. Per NEC 240.83(C), this breaker is listed and suitable for use as a switch on which type of circuit?

  • Motor circuits rated 1 HP or less
  • Fluorescent lighting circuits at 120V or 277V
  • Electric resistance heating circuits
  • HVAC compressor circuits

NEC Reference: NEC 240.83(C)

Question 21: Per NEC 240.10, supplementary overcurrent protection found inside luminaires or appliances does what?

  • May substitute for the branch-circuit device
  • Shall not substitute for branch-circuit protection
  • Must equal the branch-circuit device rating
  • Requires a separate disconnect per Article 430

NEC Reference: NEC 240.10

Question 22: Per NEC 240.4(B), when a conductor's ampacity does not correspond to a standard OCPD rating, the next higher standard device rating is permitted only if that next higher rating does not exceed what value?

  • 400 A
  • 600 A
  • 800 A
  • 1,000 A

NEC Reference: NEC 240.4(B)

Question 23: Per NEC 240.80, circuit breakers shall be what?

  • Operable by automatic means only
  • Capable of being opened and closed manually
  • Equipped with a key-operated interlock
  • Rated at a minimum of 30 A

NEC Reference: NEC 240.80

Question 24: Per NEC 240.51(B), Edison-base plug fuses shall be used only in what situation?

  • In all new residential installations
  • As replacements with no evidence of tampering/overfusing
  • In circuits up to 240 V
  • In motor circuits up to 2 HP

NEC Reference: NEC 240.51(B)

Question 25: Per NEC 240.54(C), once a Type S fuse adapter is installed in a fuseholder, what happens?

  • Removable with a screwdriver for changes
  • Non-removable, accepts only that ampere class
  • Accepts any ampere rating of Type S fuse
  • Removed before each replacement fuse

NEC Reference: NEC 240.54(C)

Question 26: At a fault current of 10 times the rating of both a current-limiting fuse and a thermal-magnetic circuit breaker (both rated 100 A), which device generally clears the fault faster?

  • The current-limiting fuse
  • The thermal-magnetic circuit breaker
  • Both clear in the same time
  • Cannot be determined

NEC Reference: NEC 240.2

Question 27: Per NEC 240.4(G), overcurrent protection for conductors supplying motor loads is provided according to which NEC article?

  • Article 210
  • Article 220
  • Article 430
  • Article 440

NEC Reference: NEC 240.4(G)

Question 28: Per NEC 240.85, a circuit breaker with a slash voltage rating of "120/240V" may generally be applied on what type of system?

  • Ungrounded delta systems only
  • Corner-grounded delta systems only
  • Solidly grounded systems, voltage to ground under 120V
  • Any system under 240V line-to-line

NEC Reference: NEC 240.85

Question 29: Per the general rule in NEC 240.21(A), overcurrent protection must generally be provided for conductors where?

  • Where they terminate at the load
  • Where they receive their supply
  • At the midpoint of the run
  • Only at the main service disconnect

NEC Reference: NEC 240.21(A)

Question 30: Per NEC 240.4(D), what is the maximum overcurrent protection permitted for 12 AWG aluminum or copper-clad aluminum conductors?

  • 15 A
  • 20 A
  • 25 A
  • 30 A

NEC Reference: NEC 240.4(D)(4)

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)