NEC CODE NEC 2020

Motor Circuit Calculations 3 (NEC 430/440) — NEC 2020 Edition

Free NEC 2020 practice test on motor and motor-compressor circuit calculations. Covers hermetic refrigerant motor-compressor branch-circuit and short-circuit protection (Article 440), controllers, and disconnecting means (Article 430). Simple English, full explanations.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Motor Circuit Calculations 3 (NEC 430/440) — NEC 2020 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2020
Motor Circuit Calculations 3 (NEC 430/440) — NEC 2020 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Motor Circuit Calculations 3 (NEC 430/440) — NEC 2020 Edition — Question List

Question 1: What is the maximum rating, as a percent of motor-compressor rated-load current, for the short-circuit and ground-fault protective device of a single motor-compressor?

  • 225 %
  • 175 %
  • 200 %
  • 150 %

NEC Reference: NEC 440.22(A)

Question 2: Per the exception in NEC 440.22(A), what is the minimum ampere rating allowed for a motor-compressor short-circuit and ground-fault protective device, even if the calculated value is lower?

  • 10 A
  • 15 A
  • 20 A
  • 25 A

NEC Reference: NEC 440.22(A) Exception

Question 3: What size branch-circuit conductor is required for an 18-ampere motor-compressor connected to a 240-volt circuit, with terminals rated at 75 C?

  • 12 AWG
  • 10 AWG
  • 14 AWG
  • 8 AWG

NEC Reference: NEC 440.32 / Table 310.16

Question 4: What size branch-circuit protection is required for a 20-ampere motor-compressor connected to a 240-volt circuit?

  • 35 A
  • 40 A
  • 45 A
  • 50 A

NEC Reference: NEC 440.22(A)

Question 5: What size branch-circuit conductor is suitable for a 5 HP, 208-volt three-phase motor, with terminals rated 75 C?

  • 12 AWG
  • 10 AWG
  • 8 AWG
  • 14 AWG

NEC Reference: NEC Table 430.250 / Table 310.16

Question 6: A single-pole, general-use snap switch is only permitted to control (start and stop) a stationary motor rated up to what horsepower?

  • 1/2 HP
  • 1/4 HP
  • 3/4 HP
  • 1 HP

NEC Reference: NEC 430.83(C)

Question 7: The branch-circuit overcurrent device of a stationary motor rated below what horsepower may also serve as the motor's controller?

  • 5 HP
  • 3 HP
  • 1 HP
  • 1/8 HP

NEC Reference: NEC 430.81(A)

Question 8: A disconnecting means for motor circuits over 1000 volts must be capable of being locked in which position?

  • Closed position
  • Open position
  • On position
  • Both open and closed

NEC Reference: NEC 430.109

Question 9: Overload protection is generally required for a motor rated above what horsepower?

  • 1/8 HP
  • 1/4 HP
  • 1/2 HP
  • 1 HP

NEC Reference: NEC 430.32(A)

Question 10: A motor disconnecting means located "within sight" of the motor must be visible and not more than what distance away?

  • 25 feet
  • 50 feet
  • 70 feet
  • 90 feet

NEC Reference: NEC Article 100

Question 11: For a hermetic refrigerant motor-compressor, overload protection is generally based on which current value?

  • The rated-load or branch-circuit selection current
  • A random guess
  • The building service size
  • The compressor's weight

NEC Reference: NEC 440.52

Question 12: Per NEC 440.12(A), a disconnecting means for a hermetic motor-compressor is generally sized based on what percent of the compressor rated-load current, if not horsepower-rated?

  • 115%
  • 125%
  • 100%
  • 175%

NEC Reference: NEC 440.12(A)

Question 13: A cord-and-plug-connected room air conditioner rated 250 volts or less generally must not draw more than what percent of the branch-circuit rating?

  • 80%
  • 100%
  • 125%
  • 50%

NEC Reference: NEC 440.62(B)

Question 14: Per NEC 440.4(A), hermetic refrigerant motor-compressor equipment must be marked with which of the following, in addition to other data?

  • Rated-load current
  • The installer's name
  • Nothing is required
  • Only the paint color

NEC Reference: NEC 440.4(A)

Question 15: A motor controller (other than certain inverse-time breakers) must generally have a horsepower rating not lower than what?

  • The horsepower rating of the motor
  • Half the motor horsepower
  • Any rating at all
  • Twice the motor horsepower, always

NEC Reference: NEC 430.83

Question 16: A manually resettable overload relay that could restart a motor unexpectedly, creating a hazard, must generally be reset from where?

  • Intentional manual action only
  • It resets itself automatically, always
  • A random timer
  • It never needs resetting

NEC Reference: NEC 430.43

Question 17: If the motor disconnecting means is not within sight of the controller location, what does NEC 430.102(B) generally require?

  • The disconnect must be lockable in the open position
  • Nothing extra is required
  • A sign is enough, no lock needed
  • The controller must be moved instead

NEC Reference: NEC 430.102(B)

Question 18: Tap conductors supplying an individual motor from a branch circuit generally must have an ampacity of not less than what fraction of the branch-circuit conductor ampacity, when very short?

  • One-third the branch-circuit conductor ampacity
  • Exactly the same size, always
  • One-tenth the branch-circuit conductor ampacity
  • No tap is ever permitted

NEC Reference: NEC 430.28

Question 19: For air-conditioning or refrigerating equipment with multiple motors and loads on a single nameplate, what value is generally used to size the equipment's branch-circuit protection?

  • The nameplate maximum overcurrent protection rating
  • A random guess
  • Always 15 amperes
  • The building main breaker size

NEC Reference: NEC 440.22(B)

Question 20: What is the "branch-circuit selection current" for a hermetic refrigerant motor-compressor?

  • A nameplate value used for sizing when larger than rated-load current
  • A random constant
  • Always equal to the branch breaker size
  • The compressor's weight in pounds

NEC Reference: NEC Article 440

Question 21: Can a single motor be supplied from a feeder that also supplies other loads, without a separate feeder just for that motor?

  • Yes, if properly sized
  • No, every motor needs a dedicated feeder
  • Only for motors under 1 HP
  • Only for single-phase motors

NEC Reference: NEC 430.24 / 430.63

Question 22: Exposed non-current-carrying metal parts of a motor-compressor unit must generally be what, similar to standard motor frames?

  • Grounded
  • Insulated from ground
  • Painted only
  • Left ungrounded

NEC Reference: NEC 440.61

Question 23: For air-conditioning or refrigeration equipment, the disconnecting means must generally be readily accessible and located within sight of what?

  • The equipment it serves
  • A neighboring building
  • Nowhere specific
  • Only the main panel, regardless of distance

NEC Reference: NEC 440.14

Question 24: On HVAC equipment nameplates, what do the abbreviations MCA and MOCP generally stand for?

  • Minimum circuit ampacity and maximum overcurrent protection
  • Motor control assembly and motor overcurrent panel
  • Nothing standard -- they vary by installer
  • Maximum current allowed and minimum operating cost

NEC Reference: NEC Article 440

Question 25: Can the same disconnecting means serve both the required motor disconnect and a required equipment disconnect for air-conditioning/refrigeration equipment, when they are the same device?

  • Yes, if it meets both articles' requirements
  • No, two separate devices are always required
  • Only for motors under 1 HP
  • Only for single-phase equipment

NEC Reference: NEC 440.14 / 430.109

Question 26: Can a thermal protector built into a hermetic motor-compressor serve as the required overload protection?

  • Yes, if suitable for the application
  • No, a separate device is always required
  • Only for motors over 50 HP
  • Only for three-phase compressors

NEC Reference: NEC 440.52(A)(1)

Question 27: Under NEC 440.22(A), when the calculated motor-compressor short-circuit protective device rating does not correspond to a standard fuse or breaker size, what should be done?

  • Use the next higher standard rating, within the cap
  • Leave the equipment unprotected
  • Always round down, no matter what
  • Double the value automatically

NEC Reference: NEC 440.22(A)

Question 28: When two or more motor-compressors, or a motor-compressor plus other loads, are supplied by a single branch circuit, how is the branch-circuit conductor generally sized?

  • 125% of the largest, plus the sum of the rest
  • 100% of all loads added together, no multiplier
  • Only the largest single load, ignoring the rest
  • A flat 20 amperes regardless of load

NEC Reference: NEC 440.33

Question 29: Is it good practice, though not always mandatory, to locate the motor disconnecting means near the controller?

  • Yes, for convenience and safety
  • No, they must always be in separate buildings
  • It is against code to place them near each other
  • It makes no practical difference

NEC Reference: NEC 430.102

Question 30: When a motor overload relay is in a different ambient temperature than the motor itself, what type of overload relay should generally be selected?

  • An ambient-compensated overload relay
  • Any relay at all, it does not matter
  • A relay with no thermal sensing
  • A relay sized for double the FLC

NEC Reference: NEC 430.32(C)

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)