Motor Circuit Calculations 2 (NEC 430) — NEC 2020 Edition

Free NEC 2020 practice test on motor circuit calculations. Covers branch-circuit and feeder conductor sizing, overload fuse selection, inverse-time breaker sizing, and feeder protection for grouped motors. Simple English, full explanations.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Motor Circuit Calculations 2 (NEC 430) — NEC 2020 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2020
Motor Circuit Calculations 2 (NEC 430) — NEC 2020 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Motor Circuit Calculations 2 (NEC 430) — NEC 2020 Edition — Question List

Question 1: A 5 HP single-phase motor is connected to a 240-volt supply. What is the minimum size branch-circuit conductor required?

  • No. 8 THWN
  • No. 6 THWN
  • No. 4 THWN
  • No. 10 THWN

NEC Reference: NEC Table 430.248 / 430.22(A)

Question 2: A 4 HP, 230V single-phase motor has a marked service factor of 1.15 and a nameplate current of 25 A. What standard dual-element fuse size can be used to protect the motor from overload, short circuit, and ground faults?

  • 25 A
  • 30 A
  • 28 A
  • 35 A

NEC Reference: NEC 430.32(A)(1)

Question 3: What size branch-circuit conductor can be used for a 5 HP, 230-volt three-phase motor, with terminals rated at 75 C?

  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG

NEC Reference: NEC Table 430.250 / Table 310.16

Question 4: What size inverse-time circuit breaker is required for a 10 HP, 230-volt three-phase motor?

  • 70 A
  • 56 A
  • 40 A
  • 30 A

NEC Reference: NEC Table 430.52 / Table 430.250

Question 5: A feeder supplies two three-phase motors: a 10 HP and a 15 HP, both 230 volts. What is the maximum feeder protection rating allowed?

  • 175 A
  • 105 A
  • 125 A
  • 200 A

NEC Reference: NEC 430.62(A)

Question 6: A feeder supplies a 15 HP and a 10 HP three-phase motor, both 460 volts, with terminals rated at 75 C. What minimum size feeder conductor is required?

  • 8 AWG
  • 6 AWG
  • 10 AWG
  • 12 AWG

NEC Reference: NEC 430.24 / Table 310.16

Question 7: Which of the following motors has the highest full-load current (FLC)?

  • 3 HP, 208 volts three-phase
  • 10 HP, 230 volts three-phase
  • 10 HP, 460 volts three-phase
  • 3 HP, 115 volts single-phase

NEC Reference: NEC Table 430.248 / Table 430.250

Question 8: What size branch-circuit conductor can supply a 3 HP, 115-volt single-phase motor with terminals rated at 60 C?

  • 8 AWG
  • 10 AWG
  • 12 AWG
  • 14 AWG

NEC Reference: NEC Table 430.248 / Table 310.16

Question 9: A 5 HP three-phase motor with a nameplate FLA of 25 A is used for intermittent, 5-minute-rated duty. What size branch-circuit conductor can be used, with terminals rated 75 C?

  • 12 AWG
  • 8 AWG
  • 10 AWG
  • 14 AWG

NEC Reference: NEC Table 430.22(E) / Table 310.16

Question 10: Can the motor branch-circuit short-circuit and ground-fault protective device also fully protect the motor against overload?

  • True
  • False -- a separate overload device is needed
  • Only for single-phase motors
  • Only for motors under 1 HP

NEC Reference: NEC 430.51

Question 11: Per NEC Table 430.250, what is the full-load current of a 20 HP, 230-volt three-phase motor?

  • 54 amperes
  • 68 amperes
  • 28 amperes
  • 96 amperes

NEC Reference: NEC Table 430.250

Question 12: Per NEC Table 430.52, what is the maximum rating, as a percent of motor FLC, for a non-time-delay fuse (most common motor types)?

  • 300%
  • 175%
  • 250%
  • 125%

NEC Reference: NEC Table 430.52

Question 13: For a feeder supplying a single motor plus other loads (not just motors), how is the feeder protection generally determined?

  • Motor branch protection plus rating for other loads
  • Only the motor rating, ignoring other loads
  • Only the other loads, ignoring the motor
  • A flat 100 amperes regardless of load

NEC Reference: NEC 430.63

Question 14: Two or more motors, each rated 1 HP or less and drawing not more than 6 amperes, can be grouped on a single branch circuit protected at what maximum standard rating?

  • 20 amperes
  • 15 amperes
  • 30 amperes
  • 40 amperes

NEC Reference: NEC 430.53(A)

Question 15: Per NEC 430.53(B), several motors of any rating can be grouped on one branch circuit if each motor has its own what?

  • Its own overload protective device
  • A separate building
  • A dedicated generator
  • Nothing extra is required

NEC Reference: NEC 430.53(B)

Question 16: Per NEC Table 430.250, what is the full-load current of a 5 HP, 460-volt three-phase motor?

  • 7.6 amperes
  • 15.2 amperes
  • 28 amperes
  • 3.8 amperes

NEC Reference: NEC Table 430.250

Question 17: When the calculated motor branch-circuit protective device rating does not match a standard size, and the next size down is insufficient, what does NEC 430.52(C)(1) allow?

  • Using the next higher standard rating
  • Leaving the motor unprotected
  • Using a rating with no standard basis
  • Doubling the calculated value automatically

NEC Reference: NEC 430.52(C)(1)

Question 18: When sizing a feeder that supplies several motors, which single motor's FLC gets the 125% multiplier?

  • The highest-rated motor
  • The lowest-rated motor
  • All motors equally
  • None of the motors

NEC Reference: NEC 430.24

Question 19: Per NEC Table 430.250, what is the full-load current of a 75 HP, 460-volt three-phase motor?

  • 96 amperes
  • 124 amperes
  • 80 amperes
  • 156 amperes

NEC Reference: NEC Table 430.250

Question 20: When selecting a conductor ampacity from NEC Table 310.16, which temperature column should be used?

  • The lowest-rated termination temperature
  • Always the 90 C column
  • Always the 60 C column
  • Whichever column gives the smallest wire

NEC Reference: NEC 110.14(C)

Question 21: A motor has a marked service factor of exactly 1.15. Per NEC 430.32(A)(1), what overload percentage applies?

  • 125%
  • 115%
  • 100%
  • 150%

NEC Reference: NEC 430.32(A)(1)

Question 22: When a capacitor is connected on the load side of a motor overload device, what must the motor disconnecting means do?

  • Disconnect the motor and capacitor together
  • Disconnect only the capacitor
  • Disconnect only the motor
  • Nothing special is required

NEC Reference: NEC 430.113

Question 23: Per NEC Table 430.250, what is the full-load current of a 30 HP, 230-volt three-phase motor?

  • 80 amperes
  • 68 amperes
  • 104 amperes
  • 54 amperes

NEC Reference: NEC Table 430.250

Question 24: Where a motor has a wiring space or terminal housing, what must the space provide for the conductors entering it?

  • Sufficient space for connections and bending
  • No space is required
  • Space only for a padlock
  • Space only for paint

NEC Reference: NEC 430.12

Question 25: For a motor supplied through an adjustable-speed drive (power conversion equipment), what current value is used for conductor sizing between the drive and the motor?

  • The drive's rated output current
  • Only the motor nameplate current
  • A random estimate
  • The building service size

NEC Reference: NEC 430.122(A)

Question 26: Per NEC Table 430.250, what is the full-load current of a 1 HP, 230-volt three-phase motor?

  • 3.6 amperes
  • 7.2 amperes
  • 1.8 amperes
  • 14 amperes

NEC Reference: NEC Table 430.250

Question 27: Where must the motor branch-circuit short-circuit and ground-fault protective device generally be located relative to the motor controller?

  • Ahead of (supply side of) the controller
  • After the motor windings
  • Anywhere at all
  • Inside the motor frame only

NEC Reference: NEC 430.52

Question 28: Per NEC Table 430.250, what is the full-load current of a 30 HP, 460-volt three-phase motor?

  • 40 amperes
  • 80 amperes
  • 20 amperes
  • 65 amperes

NEC Reference: NEC Table 430.250

Question 29: When selecting a thermal overload relay heater element for a motor starter, which current value should generally guide the selection?

  • The motor nameplate current
  • The NEC table value only
  • A random guess
  • The panel bus rating

NEC Reference: NEC 430.6(A)(2)

Question 30: When Article 430's motor-specific sizing rules conflict with the general conductor and overcurrent rules elsewhere in the NEC, which rules apply?

  • The specific motor rules in Article 430
  • The general rules always win
  • Neither rule applies
  • Whichever the installer prefers

NEC Reference: NEC 90.3 / Article 430

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)