JOURNEYMAN NEC 2020

NEC 2020 Journeyman Practice Test 6

Free Online Journeyman Electrician Practice Test — NEC 2020 Edition 6This free 30-question practice test covers grounding electrodes and the grounding electrode system, bonding jumpers, overcurrent protection rules, and conductor ampacity under Table 310.15(B)(16). All questions and explanations are based on the 2020 NEC.

TOPICS COVERED
journeyman electrician

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account required. All questions include detailed explanations and NEC references.

Most state Journeyman exams have 80–100 questions covering NEC code, wiring methods, branch circuits, motor controls, and load calculations.

Most states require a 70–75% passing score. This practice test uses the same 70% pass threshold so you know where you stand.

Questions are written to the 2020 NEC. Check your state licensing board to confirm which edition your state has adopted.

How to Use This Practice Test

This NEC 2020 Journeyman Practice Test 6 has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: This is an open-book exam — tab your NEC index and Articles 210, 250, and 430 before you start.

  • Topics covered: Branch circuits, grounding, wiring methods, load calculations, and motors.
  • Passing score: 70–75% (most states). Aim for 80% on practice tests so the real exam feels easy.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

JOURNEYMAN · NEC 2020
NEC 2020 Journeyman Practice Test 6
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2020 Journeyman Practice Test 6 — Question List

Question 1: At service equipment, the main bonding jumper connects the grounded (neutral) conductor to which of the following?

  • A driven ground rod only
  • The service equipment enclosure
  • The utility transformer neutral only
  • Nothing — the neutral must stay isolated at the service

NEC Reference: NEC 250.28

Question 2: Which of the following is specifically prohibited from being used as a grounding electrode?

  • Metal underground gas piping system
  • Metal frame of the building
  • Concrete-encased electrode (Ufer ground)
  • Ground ring

NEC Reference: NEC 250.52(B)(1)

Question 3: Per NEC Table 250.66, for a service with copper ungrounded conductors of 2 AWG or smaller, what is the minimum size copper grounding electrode conductor (GEC)?

  • 6 AWG copper
  • 8 AWG copper
  • 4 AWG copper
  • 10 AWG copper

NEC Reference: NEC Table 250.66

Question 4: Per NEC 250.53(A)(2), a single rod, pipe, or plate electrode with a resistance to earth greater than _____ ohms must be supplemented with an additional electrode.

  • 10 ohms
  • 25 ohms
  • 15 ohms
  • 50 ohms

NEC Reference: NEC 250.53(A)(2)

Question 5: A concrete-encased electrode (Ufer ground) using bare copper conductor must be at least how long to qualify as a grounding electrode?

  • 10 feet
  • 20 feet
  • 6 feet
  • 8 feet

NEC Reference: NEC 250.52(A)(3)

Question 6: A ground ring grounding electrode must consist of at least 20 feet of bare copper conductor not smaller than _____ encircling the building.

  • 2 AWG
  • 4 AWG
  • 6 AWG
  • 8 AWG

NEC Reference: NEC 250.52(A)(4)

Question 7: A driven ground rod electrode must have a minimum length of at least how many feet in contact with the soil?

  • 5 feet
  • 8 feet
  • 10 feet
  • 6 feet

NEC Reference: NEC 250.52(A)(5)

Question 8: Per NEC 250.53(A)(3), when two rod electrodes are used, they must be spaced not less than _____ apart to be effective.

  • 3 feet
  • 6 feet
  • 10 feet
  • 12 feet

NEC Reference: NEC 250.53(A)(3)

Question 9: Per NEC Table 250.122, what is the minimum size copper equipment grounding conductor (EGC) required for a circuit protected by a 20 ampere overcurrent device?

  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG

NEC Reference: NEC Table 250.122

Question 10: A feeder is protected by a 100 ampere circuit breaker. Per NEC Table 250.122, what is the minimum size copper equipment grounding conductor required?

  • 10 AWG
  • 8 AWG
  • 6 AWG
  • 4 AWG

NEC Reference: NEC Table 250.122

Question 11: Downstream of the service disconnecting means, which of the following is generally NOT a recognized equipment grounding conductor?

  • Rigid metal conduit
  • Electrical metallic tubing
  • The grounded (neutral) conductor
  • A bare copper conductor

NEC Reference: NEC 250.118

Question 12: Per NEC 250.104(B), metal piping systems (such as gas piping) that may become energized must be bonded to which of the following?

  • The service equipment enclosure, grounded conductor, GEC, or a grounding electrode
  • Nothing — bonding of gas piping is prohibited
  • Only a dedicated ground rod driven at the meter
  • Only the nearest metal water pipe

NEC Reference: NEC 250.104(B)

Question 13: For a separately derived system, such as a dry-type transformer secondary, where may the required system bonding jumper be installed per NEC 250.30(A)(1)?

  • At every panelboard fed from the transformer
  • At a single point — the source or the first disconnecting means, not both
  • At the nearest metal water pipe only
  • At any convenient junction box downstream

NEC Reference: NEC 250.30(A)(1)

Question 14: A feeder supplies a disconnecting means at a separate structure on the same property. Per NEC 250.32(B)(1), what is required at the structure regarding grounding?

  • An EGC must be run with the feeder; the neutral must stay isolated from the EGC and enclosure
  • The neutral must be bonded to the enclosure the same as at the service
  • No EGC is needed if a ground rod is driven at the structure
  • The neutral may be reduced to half the size of the ungrounded conductors

NEC Reference: NEC 250.32(B)(1)

Question 15: Grounding and bonding connections must be made in a way that does NOT create what condition, per NEC 250.6(A)?

  • Objectionable current over grounding conductors or paths
  • Excess voltage drop on branch circuits
  • Overloaded neutral conductors only
  • Corrosion of buried conduit

NEC Reference: NEC 250.6(A)

Question 16: Unless a specific exception applies, what is the maximum standard overcurrent protection permitted for a 12 AWG copper conductor?

  • 15 amperes
  • 20 amperes
  • 25 amperes
  • 30 amperes

NEC Reference: NEC 240.4(D)(5)

Question 17: Unless a specific exception applies, what is the maximum standard overcurrent protection permitted for a 10 AWG copper conductor?

  • 20 amperes
  • 25 amperes
  • 30 amperes
  • 40 amperes

NEC Reference: NEC 240.4(D)(7)

Question 18: A continuous load calculation results in a required conductor ampacity of 34 amperes, which is not a standard overcurrent device size. Per NEC 240.4(B) and 240.6(A), what should be done?

  • Round down to 30 amperes
  • Round up to the next standard size, 35 amperes
  • Use a non-standard 34 ampere breaker
  • The circuit cannot be installed

NEC Reference: NEC 240.4(B)

Question 19: Under the 10-foot tap rule of NEC 240.21(B)(1), which of the following is a required condition?

  • Tap conductors up to 10 feet long, sized to the load and terminating device, enclosed in raceway if leaving the enclosure
  • Tap conductors up to 50 feet long with no ampacity requirement
  • Tap conductors may be any length if run overhead
  • Tap conductors need no overcurrent protection at all

NEC Reference: NEC 240.21(B)(1)

Question 20: Under the 25-foot tap rule of NEC 240.21(B)(2), the tap conductors must have an ampacity of at least what fraction of the rating of the overcurrent device from which they are tapped?

  • One-half
  • One-third
  • One-fourth
  • Two-thirds

NEC Reference: NEC 240.21(B)(2)

Question 21: True or false: NEC 240.24(E) prohibits installing overcurrent devices, such as panelboards, in the bathrooms of dwelling units.

  • True
  • False
  • Only in commercial bathrooms
  • Only for fuses, not breakers

NEC Reference: NEC 240.24(E)

Question 22: Per the 2020 NEC Table 310.15(B)(16), what is the allowable ampacity of an 8 AWG copper conductor with 90°C insulation (such as THHN), in a raceway with no more than 3 current-carrying conductors at 30°C ambient?

  • 50 amperes
  • 55 amperes
  • 60 amperes
  • 65 amperes

NEC Reference: NEC Table 310.15(B)(16)

Question 23: Per the 2020 NEC Table 310.15(B)(16), what is the allowable ampacity of a 6 AWG copper conductor with 90°C insulation, in a raceway with no more than 3 current-carrying conductors at 30°C ambient?

  • 65 amperes
  • 70 amperes
  • 75 amperes
  • 80 amperes

NEC Reference: NEC Table 310.15(B)(16)

Question 24: A branch circuit uses 10 AWG copper THHN conductors. Table 310.15(B)(16) lists a 90°C ampacity of 40 amperes for this conductor, but what is the maximum standard breaker size actually permitted to protect it?

  • 40 amperes
  • 35 amperes
  • 30 amperes
  • 45 amperes

NEC Reference: NEC 240.4(D)(7)

Question 25: Per NEC 310.15(B)(3)(a), when a raceway or cable contains 4 through 6 current-carrying conductors, the table ampacity of each conductor must be adjusted to what percentage?

  • 90 percent
  • 80 percent
  • 70 percent
  • 50 percent

NEC Reference: NEC 310.15(B)(3)(a)

Question 26: Per NEC 250.24(A)(5), on the load side of the service disconnecting means, the grounded (neutral) conductor must:

  • Remain isolated from equipment grounding conductors and the enclosure
  • Be bonded again at every panel for extra safety
  • Be removed entirely
  • Be connected to the ground bar only in metal buildings

NEC Reference: NEC 250.24(A)(5)

Question 27: Per NEC 250.50, if a metal underground water pipe, a concrete-encased electrode, and a ground ring are all present at a building, what must be done?

  • All of them must be bonded together into one grounding electrode system
  • Only the water pipe may be used; the others may be ignored
  • Only one electrode of the installer's choosing needs to be connected
  • Each electrode must serve a separate, unconnected system

NEC Reference: NEC 250.50

Question 28: Per NEC Table 250.66, a service has 1/0 AWG copper ungrounded conductors. What is the minimum size copper grounding electrode conductor required (assuming the electrode is not a rod, pipe, plate, or ground ring)?

  • 8 AWG copper
  • 6 AWG copper
  • 4 AWG copper
  • 2 AWG copper

NEC Reference: NEC Table 250.66

Question 29: Per NEC 250.66(A), when the grounding electrode conductor connects only to a rod, pipe, or plate electrode, it is not required to be larger than what size copper conductor, no matter how large the service conductors are?

  • 3/0 AWG copper
  • 6 AWG copper
  • 2 AWG copper
  • 1/0 AWG copper

NEC Reference: NEC 250.66(A)

Question 30: Per NEC 240.24(D), overcurrent protective devices shall not be located in the vicinity of _____ .

  • Bathrooms only
  • Easily ignitible material, such as in clothes closets
  • Outdoor equipment only
  • Any location above 6 feet

NEC Reference: NEC 240.24(D)

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
EXAM CARD JOURNEYMAN
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)