Dwelling Unit Load Calculations (NEC 220) — NEC 2020 Edition

Free NEC 2020 practice test on dwelling unit load calculations. Covers general lighting loads, small appliance and laundry circuits, demand factors, dryer and appliance loads, and service conductor sizing. Simple English, full explanations.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).

How to Use This Practice Test

This Dwelling Unit Load Calculations (NEC 220) — NEC 2020 Edition has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Use the NEC index (back of the book) — find answers by keyword, not by article number.

  • Topics covered: NEC articles 100, 210, 220, 240, 250, 300, 310, 430, and special occupancies.
  • Passing score: Aim for 80%+ on NEC code tests before exam day.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2020
Dwelling Unit Load Calculations (NEC 220) — NEC 2020 Edition
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Dwelling Unit Load Calculations (NEC 220) — NEC 2020 Edition — Question List

Question 1: A dwelling unit has 1,600 square feet of living area. Using the NEC general lighting unit load, what is the general lighting load?

  • 4,800 Volt-Amperes
  • 1,600 Volt-Amperes
  • 3,200 Volt-Amperes
  • 6,400 Volt-Amperes

NEC Reference: NEC Table 220.12

Question 2: A quick-recovery electric water heater is rated 5,600 watts at 240 volts. What standard circuit breaker size is required to protect it?

  • 25 amperes
  • 20 amperes
  • 23.3 amperes
  • 30 amperes

NEC Reference: NEC 240.6(A)

Question 3: A dwelling unit has a total connected general lighting and receptacle load of 11,000 VA. What is the calculated demand load?

  • 5,800 VA
  • 11,000 VA
  • 3,850 VA
  • 6,000 VA

NEC Reference: NEC Table 220.42

Question 4: A dwelling unit has an air-conditioning unit with a full-load current of 30 amperes at 230 volts, and 3 fixed heating units of 3 kW each. Since heating and air conditioning will not run at the same time, what load is used for the feeder demand?

  • 9,000 watts
  • 6,900 volt-amperes
  • 15,900 volt-amperes
  • 2,100 watts

NEC Reference: NEC 220.60

Question 5: A dwelling unit has four appliances fastened in place, each rated 800 VA. What is the demand load for these appliances?

  • 2,400 VA
  • 3,200 VA
  • 1,600 VA
  • 800 VA

NEC Reference: NEC 220.53

Question 6: What is the minimum branch-circuit or feeder load that must be used for a single household electric clothes dryer in a dwelling unit?

  • 5,000 Volt-Amperes
  • 1,500 Volt-Amperes
  • 3,000 Volt-Amperes
  • 2,000 Volt-Amperes

NEC Reference: NEC 220.54

Question 7: A multifamily building has 5 household electric clothes dryers, one per dwelling unit. What is the total demand load for these dryers?

  • 21,250 VA
  • 25,000 VA
  • 5,000 VA
  • 18,750 VA

NEC Reference: NEC Table 220.54

Question 8: A 15-unit apartment building has 900 square feet per apartment. What is the total calculated demand load for general lighting, small appliance, and laundry circuits?

  • 39,750 VA
  • 108,000 VA
  • 7,200 VA
  • 75,600 VA

NEC Reference: NEC Table 220.42

Question 9: An 8-unit multifamily building has one 5 kW electric dryer in each unit. What is the total dryer demand load for the building service or feeder?

  • 24 kW
  • 40 kW
  • 20 kW
  • 30 kW

NEC Reference: NEC Table 220.54

Question 10: A 3-phase, 120/230-volt multifamily dwelling building has a total demand load of 220 kVA. Using the standard ampacity method, roughly what current must the service conductors carry?

  • About 552 amperes
  • About 220 amperes
  • About 955 amperes
  • About 380 amperes

NEC Reference: NEC Table 310.16

Question 11: Each small-appliance branch circuit in a dwelling unit is counted at how many volt-amperes for load calculation purposes?

  • 1,500 VA
  • 1,000 VA
  • 3,000 VA
  • 750 VA

NEC Reference: NEC 220.52(A)

Question 12: The laundry branch circuit in a dwelling unit is counted at how many volt-amperes for load calculation purposes?

  • 1,500 VA
  • 1,000 VA
  • 750 VA
  • 2,000 VA

NEC Reference: NEC 220.52(B)

Question 13: What is the minimum number of small-appliance branch circuits required in a dwelling unit kitchen?

  • 2
  • 1
  • 3
  • 4

NEC Reference: NEC 210.11(C)(1)

Question 14: A dwelling unit has one household electric range rated 12 kW or less. What demand load is used for the range, per NEC Table 220.55?

  • 8 kW
  • 12 kW
  • 6 kW
  • 10 kW

NEC Reference: NEC Table 220.55

Question 15: For a one-family dwelling, the service disconnecting means must have a rating of not less than what value?

  • 100 amperes
  • 60 amperes
  • 125 amperes
  • 200 amperes

NEC Reference: NEC 230.79(C)

Question 16: For a single-phase dwelling unit service or feeder rated 100 to 400 amperes serving the entire dwelling load, conductors may be sized at not less than what percent of the service or feeder rating?

  • 83%
  • 75%
  • 95%
  • 100%

NEC Reference: NEC 310.12

Question 17: Per NEC Table 220.54, what demand factor applies when there are 4 or fewer household electric clothes dryers?

  • 100%
  • 85%
  • 75%
  • 70%

NEC Reference: NEC Table 220.54

Question 18: For a single dwelling unit, the "optional" load calculation method can be used instead of the standard method under which condition?

  • Single 120/240V or 208Y/120V service, 100A or more
  • Only for buildings with 3-phase power
  • Only for services under 60 amperes
  • It can never be used for dwellings

NEC Reference: NEC 220.82

Question 19: Using the NEC 220.82 optional dwelling calculation method, what demand factor applies to the first 10 kVA of the "other load" total?

  • 100%
  • 40%
  • 75%
  • 50%

NEC Reference: NEC 220.82(B)

Question 20: Using the NEC 220.82 optional dwelling calculation method, what demand factor applies to the "other load" amount ABOVE the first 10 kVA?

  • 40%
  • 100%
  • 25%
  • 60%

NEC Reference: NEC 220.82(B)

Question 21: A 2,000 square foot dwelling unit has no receptacle or appliance loads beyond the general lighting, small appliance, and laundry circuits. What is the total CONNECTED (before demand factor) load?

  • 10,500 VA
  • 6,000 VA
  • 4,500 VA
  • 13,500 VA

NEC Reference: NEC 220.52

Question 22: Using the 10,500 VA connected load from the previous example, what is the demand load after applying NEC Table 220.42?

  • 5,625 VA
  • 10,500 VA
  • 3,675 VA
  • 3,000 VA

NEC Reference: NEC Table 220.42

Question 23: The NEC 220.53 75% demand factor for fastened-in-place appliances applies starting at how many qualifying appliances?

  • 4
  • 2
  • 6
  • 3

NEC Reference: NEC 220.53

Question 24: Which of these is EXCLUDED from the NEC 220.53 "four or more fastened appliances" 75% demand factor rule?

  • Electric range
  • Dishwasher
  • Garbage disposal
  • Water heater

NEC Reference: NEC 220.53

Question 25: A 2,800 square foot dwelling unit is being calculated using the general lighting unit load. What is the connected general lighting load?

  • 8,400 VA
  • 2,800 VA
  • 5,600 VA
  • 9,800 VA

NEC Reference: NEC Table 220.12

Question 26: Per NEC Table 220.54, what demand factor applies to exactly 10 household electric clothes dryers?

  • 50%
  • 60%
  • 85%
  • 45%

NEC Reference: NEC Table 220.54

Question 27: When performing a standard-method dwelling unit load calculation, what is generally done right after finding the general lighting, small-appliance, and laundry connected loads?

  • Apply the general lighting demand factor
  • Call the building inspector
  • Skip straight to the service disconnect size
  • Ignore the lighting load entirely

NEC Reference: NEC Article 220

Question 28: A duplex (2 dwelling units) has one 5,000 VA electric dryer per unit. What is the total dryer demand load?

  • 10,000 VA
  • 8,500 VA
  • 5,000 VA
  • 9,000 VA

NEC Reference: NEC Table 220.54

Question 29: A single household electric range rated 12 kW or less needs its branch circuit conductors sized for what minimum load, per NEC Table 220.55?

  • 8 kW
  • 12 kW
  • 5 kW
  • 6 kW

NEC Reference: NEC Table 220.55

Question 30: What is the minimum branch-circuit rating required for the small-appliance and laundry circuits in a dwelling unit?

  • 20 amperes
  • 15 amperes
  • 30 amperes
  • 25 amperes

NEC Reference: NEC 210.11(C)

Key NEC References for This Test

ArticleWhat It Covers
Ch. 1–4General rules — apply to all installations
Ch. 5–7Special rules — override Ch. 1–4 where they conflict
Ch. 8Communications — completely independent of Ch. 1–7
Ch. 9Tables — referenced by articles, not standalone enforceable rules
Art. 210.12AFCI — major expansion in NEC 2026
Art. 230.67Surge protection at service equipment — new NEC 2026
Study Tip: Learn the NEC index — use keywords, not article numbers. Practice finding 5 different topics in under 2 minutes each.
EXAM CARD NEC CODE
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2020
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)