NEC 2020 Code Questions Practice Test 6

Free NEC 2020 practice test with 30 questions covering service equipment listing requirements, readily-accessible overcurrent devices, portable generator grounding, splice continuity in multiwire circuits, and minimum conductor sizing. Full NEC 2020 references included.

TOPICS COVERED
NEC Practice Tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

How to Use This Practice Test

This NEC 2020 Code Questions Practice Test 6 has 30 questions with detailed answers and NEC references. Take the full test, review every wrong answer, and look up the NEC article it references before moving on.

Tip: Mixed-format test — questions jump between topics just like the real exam. Don't spend more than 90 seconds on any one question.

  • Topics covered: All NEC chapters — branch circuits, grounding, conductors, wiring methods, motors, and more.
  • Passing score: Aim for 80%+ consistently before scheduling your exam.
  • Questions: 30 multiple-choice, one correct answer each
30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC_PRACTICE · NEC 2020
NEC 2020 Code Questions Practice Test 6
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

NEC 2020 Code Questions Practice Test 6 — Question List

Question 1: When two different size conductor wires are connected in series, the maximum fuse rating should be used is one that protects ................

  • smallest size wire
  • Largest size wire
  • combination of both smallest size wire and largest size wire

Question 2: What percentage of rated ampacity is allowed for each conductor when eight current carrying conductors are equipped in flexible cords?

  • 80
  • 70
  • 60
  • 50

NEC Reference: NEC 400.5(A)(3)

Question 3: The conductor amapcity is 150 amperes. What is the maximum allowed conductor ampacity of each conductor if 5 of those conductors are placed in flexible cord?

  • 120 amperes
  • 135 amperes
  • 140 ampere
  • 105 amperes

NEC Reference: NEC 400.5(A)(3)

Question 4: Upto what minimum height the underground conductors must be given mechanical protection if they carried up a pole?

  • 8 feet
  • 12 feet
  • 16 feet
  • 6 feet

NEC Reference: NEC 300.5(C)(1)

Question 5: What is the maximum demand for eight wall-mounted ovens, house hold electric ranges and other house hold cooking appliances rated at over 1 ¾ KW each?

  • 17 KW
  • 23 KW
  • 28 KW
  • 32 KW

NEC Reference: NEC 220.55

Question 6: What is minimum ampere rating of a heavy duty lighting track?

  • 15
  • 20
  • 25
  • 30

NEC Reference: NEC 410.153

Question 7: Which of the following is the ampacity of 4 AWG SE cable?

  • 70 A
  • 65 A
  • 80 A
  • 85 A

NEC Reference: NEC 338.10(B)

Question 8: Equipment grounding conductors can be considered as current carrying conductors in some cases?

  • False
  • True

NEC Reference: NEC 310.15(B)(5)

Question 9: What is the demand factor in percentage for a non-dwelling unit with a receptacle load of 15 kVA?

  • 75 %
  • 50 %
  • 80 %
  • 60 %

NEC Reference: NEC 220.44

Question 10: At one end of the feeder the voltmeter reads 240 volts. What is minimum reading voltage in volt-meter at the outlet of lighting loads?

  • 232.8 volts
  • 240 volts
  • 235 volts
  • 228 volts

NEC Reference: NEC 215.2(A)(4)

Question 11: Overcurrent devices must be located where they will be:

  • Readily accessible
  • Hidden behind a locked door with no key available
  • It does not matter where they are located
  • Embedded in concrete permanently

NEC Reference: NEC 240.24(A)

Question 12: The disconnecting means for outside feeder or branch-circuit conductors run to a separate building must be installed:

  • At a readily accessible location nearest the point of entry
  • Anywhere in the building
  • In a locked closet only
  • On the roof only

NEC Reference: NEC 225.32

Question 13: Service equipment rated 600 volts or less must be:

  • Listed and marked "suitable for use as service equipment"
  • Homemade equipment is acceptable
  • No listing or marking is required
  • Marked only with the installer's name

NEC Reference: NEC 230.66

Question 14: Overcurrent devices are generally not permitted to be located in which of the following rooms or areas?

  • Bathrooms of dwelling units
  • Garages
  • Basements
  • Utility rooms

NEC Reference: NEC 240.24(E)

Question 15: A portable generator that supplies only equipment mounted on the generator, or cord-and-plug-connected equipment through receptacles mounted on the generator, is:

  • Not required to have a separate grounding electrode
  • Always required to have a dedicated ground rod
  • Prohibited from ever being grounded
  • Required to bond to municipal water piping

NEC Reference: NEC 250.34(A)

Question 16: In multiwire branch circuits, the continuity of a grounded (neutral) conductor must not depend on:

  • Device connections, such as at a receptacle
  • The service main breaker
  • The grounding electrode
  • The panelboard bus only

NEC Reference: NEC 300.13(B)

Question 17: Except for specific applications such as fixture wires, flexible cords, and Class 1/2/3 control circuits, the smallest copper conductor permitted for general premises wiring is:

  • 18 AWG
  • 16 AWG
  • 14 AWG
  • 12 AWG

NEC Reference: NEC 310.4

Question 18: Enclosures within the scope of Article 314 must be:

  • Securely and rigidly supported
  • Left to hang freely on the cable
  • Supported only by drywall screws through the cover
  • Never require support if inside a wall

NEC Reference: NEC 314.23

Question 19: Type AC (armored) cable is permitted to be used for which of the following installations?

  • Exposed and concealed work in dry locations
  • Direct burial underground
  • Wet locations without protection
  • Embedded in poured concrete

NEC Reference: NEC 320.10

Question 20: Electrical metallic tubing (EMT) is prohibited from being used where subject to:

  • Severe corrosive influences, unless protected
  • Any dry, indoor location
  • Standard residential branch wiring
  • Above suspended ceilings

NEC Reference: NEC 358.12

Question 21: A switch or circuit breaker installed in a wet location, or outside of a building, must be provided with an enclosure that is:

  • Weatherproof
  • Left open to the elements
  • Wooden
  • No enclosure is required

NEC Reference: NEC 404.4

Question 22: A receptacle mounted in a box that is set back from the finished wall surface, such as with thick paneling, must be installed so that:

  • The mounting yoke is held rigidly at the wall surface
  • The receptacle can be left floating inside the wall
  • No extension or flush mounting is required
  • Tape is used to hold the device in place

NEC Reference: NEC 406.5(A)

Question 23: Lighting systems operating at 30 volts or less (low-voltage lighting systems) must consist of an isolating power supply, low-voltage luminaires, and associated equipment that are all:

  • Listed
  • Homemade is preferred
  • No listing requirement applies
  • Only UL marking on the power supply is needed, nothing else

NEC Reference: NEC 411.3

Question 24: A ceiling (paddle) fan weighing more than 35 pounds must be supported independently of the outlet box, unless the box is:

  • Listed for the weight of the fan
  • Made of PVC
  • Painted
  • A standard lighting outlet box is always sufficient

NEC Reference: NEC 422.18

Question 25: A dwelling unit permanently installed electric baseboard heater with factory-installed receptacle outlets may have those receptacles connected to which circuit?

  • A general-purpose branch circuit, not the heater circuit
  • The same circuit as the heating elements
  • No circuit at all — it must be capped
  • The service disconnect only

NEC Reference: NEC 424.9

Question 26: When fuses are used for motor overload protection, they must be installed:

  • One fuse in each ungrounded conductor
  • One fuse total, regardless of phase count
  • Fuses are never used for overload protection
  • Only in the neutral conductor

NEC Reference: NEC 430.36

Question 27: Hermetic refrigerant motor-compressors must be marked with which of the following on the nameplate, in addition to standard motor markings?

  • Rated-load current or branch-circuit selection current
  • The installer's license number
  • No additional marking is required
  • The building permit number

NEC Reference: NEC 440.4(A)

Question 28: Generators must be protected from overload by which of the following methods?

  • Overcurrent devices, relays, or inherent design protection
  • No overload protection is ever required for generators
  • A padlock on the enclosure only
  • A fire extinguisher nearby only

NEC Reference: NEC 445.12

Question 29: Dry-type transformers rated 600 volts or less and up to 50 kVA are permitted to be installed in fire-rated hollow spaces of buildings, provided they meet ventilation requirements, per which section?

  • 50 kVA
  • 5 kVA
  • 500 kVA
  • There is no limit

NEC Reference: NEC 450.13(B)

Question 30: Class II hazardous (combustible dust) locations are subdivided by material group into which of the following?

  • Groups E, F, and G
  • Groups A, B, C, and D
  • Groups 1 and 2 only
  • There is no subdivision

NEC Reference: NEC 500.6(B)