NEC CODE NEC 2023

Motor Circuit Calculations -3 (NEC Code Questions)

Online Practice Test on Motor Circuit Calculations

TOPICS COVERED
NEC Questions

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 15 min for 10 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — free, no signup required. Each question links to the relevant NEC article so you can study the code directly.

The National Electrical Code (NFPA 70) is the benchmark standard for safe electrical installation in the US. It is updated every 3 years by the NFPA.

Study the edition adopted by your state. As of 2025, most states use the 2020 or 2023 NEC. These tests are written to the 2023 edition.

The most tested articles are 100 (Definitions), 200–250 (Wiring & Grounding), 300–314 (Wiring Methods), 400–411 (Conductors), 430 (Motors), and 700–701 (Emergency Systems).
10
Questions
15 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

NEC CODE · NEC 2023
Motor Circuit Calculations -3 (NEC Code Questions)
Q1 / 10
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Motor Circuit Calculations -3 (NEC Code Questions) — Question List

Question 1: In no-case the rating of a shot circuit ground fault protective device for single motor compressor should not exceed ................ percent of the motor compressor rating?

  • 175
  • 225
  • 200
  • 150

NEC Reference: NEC 440.22(A)

Question 2: What is the minimum ampere rating of short circuit ground fault protective device that can be used for industrial motor compressor?

  • 10 A
  • 15 A
  • 20 A
  • 25 A

NEC Reference: NEC 440.22(A)

Question 3: Which of the following size conductor is required for a 18 A motor compressor connected to 240 V circuit at 75 <sup>0</sup>C?

  • 12 AWG
  • 10 AWG
  • 14 AWG
  • 8 AWG

NEC Reference: NEC 22.5

Question 4: Which size branch circuit protection is required for 20A motor compressor connected to 240 Volts circuit?

  • 40 A
  • 35 A
  • 45 A
  • 50 A

NEC Reference: NEC 440.22(A)

Question 5: What size branch conductor is suitable for 5 HP, 208 V three phase motor?

  • 12 AWG
  • 10 AWG
  • 8 AWG
  • 14 AWG

NEC Reference: NEC 16.7

Question 6: The single pole switches can be used to control the motors when those are rated at ................... hp or less.

  • 1/2
  • 1/4
  • 3/4
  • 1

Question 7: The branch circuit over current device of the stationary motor which are rated less than ........... may serve as the controller of motor.

  • 5 hp
  • 3 hp
  • 1 hp
  • 1/8 hp

NEC Reference: NEC 430.81(A)

Question 8: A 2400 volts motor disconnecting means must be capable of being of being locked in the ......................

  • closed position
  • open position
  • on position
  • both open and close position

Question 9: The overload protection must be provided for the motor if it is rated more than ......... hp

  • 1/8
  • 1/4
  • 1/2
  • 1

NEC Reference: NEC 430.32(A)

Question 10: A disconnecting means should be located in sight from a motor not more than ............... distance.

  • 25 feet
  • 50 feet
  • 70 feet
  • 90 feet
EXAM CARD NEC CODE
Questions10
Time limit15 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate

Timer starts immediately. Progress is auto-saved.