Master Electrician Practice Test 18 – Special Equipment: Signs, Elevators, Cranes & IT Equipment

This is Master Electrician Practice Test 18 — Special Equipment, covering the smaller but frequently tested equipment articles: electric signs (Article 600), cranes and hoists (Article 610), elevators (Article 620), audio equipment (Article 640), and information technology equipment rooms (Article 645). The test has 25 multiple-choice questions on sign circuits and disconnects, crane runway conductors, elevator disconnects and hoistway wiring, and the special allowances available in IT equipment rooms. Pass score is 70%. Every question includes a full NEC 2023 explanation so you can trace each answer back to the exact code section.

Share this test
TOPICS COVERED
Special Equipment

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 25 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no signup required. All answers include detailed explanations.

Requirements vary by state but typically include 4–8 years of documented electrical work experience plus a valid Journeyman license.

Advanced NEC code interpretation, load calculations, service entrance design, motor controls, generator systems, and electrical system design.

The Master exam focuses more on design, calculations, and planning rather than installation details. Load calculation and service sizing questions are weighted heavily.

Before You Start

  • 25 questions — multiple choice
  • 45 minutes to finish (timer starts when you begin)
  • Pass score is 70% — you need at least 18 correct answers
  • Full NEC 2023 explanation shown for every question after you submit

Topics in This Test

  • Dedicated 20A sign outlet at each pedestrian-accessible entrance (NEC 600.5(A))
  • Sign disconnecting means — within sight or lockable (NEC 600.6(A))
  • Sign grounding and bonding of metal parts (NEC 600.7)
  • Neon secondary (GTO) conductor special wiring rules (NEC 600.32)
  • Crane/hoist disconnecting means — accessible, lockable (NEC 610.31)
  • Bare crane runway contact conductors — guarding requirement (NEC Article 610, Part IV)
  • Crane motor overcurrent protection principles (NEC 610.42)
  • Elevator disconnecting means — single means for all ungrounded conductors (NEC 620.51(A))
  • Elevator disconnect lockable in the open position (NEC 620.51(A))
  • Elevator car lighting/receptacle/ventilation circuit kept separate from power (NEC 620.22)
  • Machine room lighting circuit and switch at point of entry (NEC 620.23/620.24)
  • Elevator hoistway wiring methods (NEC 620.21)
  • Elevator traveling cable — special listed cable type
  • GFCI protection in elevator pit, car top, and machine room (NEC 620.6)
  • Special IT equipment room provisions apply only when all listed conditions are met (NEC 645.4)
  • IT equipment room disconnecting means (NEC 645.10)
  • Under-raised-floor cabling allowance unique to IT rooms (NEC 645.5(E))
  • Flexible cords for certain permanently installed audio equipment (NEC 640.9)
  • Maximum sign branch-circuit ratings — 20 A, or 30 A for neon tubing (NEC 600.5(B))
  • Conditions required to use the Article 645 wiring allowances (NEC 645.4)
  • Elevator car light, receptacle, and ventilation disconnect (NEC 620.53)
  • IT equipment branch-circuit conductors — 125% of connected load (NEC 645.5(A))
  • Extraneous wiring restrictions in an elevator hoistway (NEC 620.37)

Tip: These are "niche" articles individually, but together they make up a meaningful chunk of the master exam. Learn each article's scope first — once you know which article a piece of equipment falls under, most of the specific rules follow logically from the equipment's obvious safety concerns (moving parts, exposed conductors, continuous operation).

25
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

MASTER · NEC 2023
Master Electrician Practice Test 18 – Special Equipment: Signs, Elevators, Cranes & IT Equipment
Q1 / 25
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Master Electrician Practice Test 18 – Special Equipment: Signs, Elevators, Cranes & IT Equipment — Question List

Question 1: NEC 600.5(A) requires each commercial building and occupancy accessible to pedestrians to have at least one sign outlet supplied by:

  • A dedicated 20A branch circuit
  • Any shared general-purpose lighting circuit
  • A Class 2 power-limited circuit only
  • No circuit is required if the sign is battery-powered

NEC Reference: NEC 600.5(A)

Question 2: NEC 600.6(A) requires the disconnecting means for an electric sign to be:

  • Within sight of the sign, or lockable in the open position if not
  • Located only inside the building, regardless of sign location
  • Optional for signs under 20A
  • Never required for outline lighting

NEC Reference: NEC 600.6(A)

Question 3: NEC 600.7 requires the metal parts of an electric sign to be:

  • Grounded and bonded
  • Left ungrounded to avoid stray current
  • Insulated from all metal, not grounded
  • Bonded only if the sign is illuminated

NEC Reference: NEC 600.7

Question 4: Neon and other electric-discharge lighting secondary (GTO) conductors are subject to:

  • Special high-voltage secondary wiring rules distinct from standard branch-circuit wiring
  • No special rules — treated identically to ordinary NM cable
  • A total prohibition under the NEC
  • Rules identical to service-entrance conductors

NEC Reference: NEC 600.32

Question 5: NEC 610.31 requires the disconnecting means for a crane or monorail hoist to be:

  • Readily accessible and operable from the ground or floor level, lockable
  • Located only in the crane cab, inaccessible from the floor
  • Optional for cranes under 5 tons
  • Not required if the crane is manually operated

NEC Reference: NEC 610.31

Question 6: Bare runway contact conductors that supply a traveling crane, per NEC Article 610, Part IV (Contact Conductors), must be:

  • Guarded or positioned to prevent accidental contact
  • Left fully exposed at floor level with no guarding
  • Insulated with standard THHN, eliminating any guarding need
  • Prohibited entirely under the current NEC

NEC Reference: NEC Article 610, Part IV

Question 7: Overcurrent protection for crane and hoist motors under NEC 610.42 is generally based on principles similar to:

  • Article 430 motor overcurrent protection principles
  • Article 680 pool bonding principles
  • Article 800 communications principles
  • No overcurrent protection is required for crane motors

NEC Reference: NEC 610.42

Question 8: NEC 620.51(A) requires an elevator to have:

  • A single disconnecting means for all ungrounded conductors
  • A separate disconnect for every individual motor in the system
  • No disconnecting means at all
  • A disconnect located only inside the elevator car

NEC Reference: NEC 620.51(A)

Question 9: NEC 620.51(A) requires the elevator disconnecting means to be:

  • Capable of being locked in the open position
  • Automatically reset after 30 seconds
  • Rated at exactly 15A regardless of load
  • Prohibited from being locked, for fire code reasons

NEC Reference: NEC 620.51(A)

Question 10: NEC 620.22 requires an elevator car's lighting, receptacle, and ventilation/air-conditioning circuit to be:

  • Kept separate from the elevator's power circuits
  • Combined with the main drive motor circuit to save wiring
  • Eliminated entirely — elevator cars require no lighting circuit
  • Supplied only by battery power, never by branch circuit

NEC Reference: NEC 620.22

Question 11: NEC 620.23/620.24 require the elevator machine room lighting circuit to have:

  • A switch located at the point of entry to the space
  • No switch — the lighting is always on
  • A switch located only inside the elevator car
  • A motion sensor is mandatory, with no manual switch permitted

NEC Reference: NEC 620.23/620.24

Question 12: NEC 620.21 requires wiring installed in an elevator hoistway to use which type of wiring methods?

  • Recognized raceways or cables such as RMC, IMC, EMT, or listed MC/MI cable
  • Open, unsupported conductors with no raceway
  • Only bare copper busbar
  • Only Class 2 low-voltage cable

NEC Reference: NEC 620.21

Question 13: The flexible cable that connects a moving elevator car to a fixed termination point in the hoistway is known as:

  • A traveling cable
  • A service lateral
  • A tap conductor
  • A drip loop

NEC Reference: NEC Article 620

Question 14: NEC 620.6 requires GFCI protection for 125V, single-phase, 15A and 20A receptacles located in which elevator-related spaces?

  • The elevator pit, car top, and machine room
  • Only the lobby waiting area
  • Only the building's main electrical room
  • GFCI is never required anywhere in an elevator installation

NEC Reference: NEC 620.6

Question 15: NEC 645.4 permits the special wiring allowances of Article 645 (Information Technology Equipment) to be used only when:

  • All of the article's listed conditions are met together
  • The room is larger than 500 sq ft
  • The building has more than five stories
  • Any one condition alone is sufficient

NEC Reference: NEC 645.4

Question 16: NEC 645.10 requires an information technology equipment room to have:

  • A disconnecting means for power to all IT equipment in the room
  • No disconnecting means, ever, to avoid accidental data loss
  • A disconnect rated for exactly 15A regardless of room size
  • A requirement that the room never have a fire alarm connection

NEC Reference: NEC 645.10

Question 17: When all the conditions of NEC 645.4 are met, what does NEC 645.5(E) permit for power cables under a raised floor in an information technology equipment room?

  • All power wiring under the floor must be in rigid metal conduit
  • Listed power cables may be installed under the raised floor without a raceway
  • Power cables are prohibited under the floor; only data cables are allowed
  • Power cables are allowed only if they are Class 2

NEC Reference: NEC 645.5(E)

Question 18: NEC 640.9 permits flexible cords to be used for certain permanently installed audio equipment. How does this compare to the general rule in Article 400?

  • It is an exception to the general 400.12 prohibition, under specific conditions
  • It duplicates 400.12 exactly with no exception
  • It bans flexible cords for audio equipment entirely
  • It applies only to portable, non-permanent audio equipment

NEC Reference: NEC 640.9

Question 19: Under NEC 600.5(B), what is the maximum branch-circuit rating for signs containing incandescent and fluorescent illumination, and for circuits supplying neon tubing installations?

  • 15 A for incandescent/fluorescent; 20 A for neon tubing
  • 20 A for incandescent/fluorescent; 30 A for neon tubing
  • 30 A for incandescent/fluorescent; 40 A for neon tubing
  • 20 A for both

NEC Reference: NEC 600.5(B)

Question 20: Which of the following is one of the conditions NEC 645.4 requires before the special wiring allowances of Article 645 can be used in an IT equipment room?

  • The room is at least 1,000 sq ft in area
  • The room is located on the building's ground floor
  • The room is separated from other occupancies by fire-resistance-rated walls, floors, and ceilings with protected openings
  • All IT equipment is supplied through a UPS

NEC Reference: NEC 645.4

Question 21: Per NEC 620.53, the disconnecting means for an elevator car's lighting, receptacle(s), and ventilation power-supply conductors must be:

  • The same switch as the main drive-motor disconnect
  • Located on top of the elevator car only
  • Omitted, since these circuits are fed from a lighting panelboard
  • A single means for that car, separate from the drive-motor disconnect, located in the machine room or control room for that car

NEC Reference: NEC 620.53

Question 22: The branch circuit supplying IT equipment in a room that meets NEC 645.4 has a total connected load of 16 A. Under NEC 645.5(A), what minimum ampacity must the branch-circuit conductors have?

  • 16 A
  • 18.4 A
  • 20 A
  • 24 A

NEC Reference: NEC 645.5(A)

Question 23: How does the NEC's approach to bare crane runway contact conductors (Article 610) differ from its approach to overhead service conductors (Article 230)?

  • Crane conductors rely on guarding/positioning; service conductors rely primarily on clearance distances
  • Both use the exact same clearance-only approach with no guarding
  • Crane conductors require no protection of any kind
  • Service conductors are always guarded, never using clearance

NEC Reference: NEC Article 610, Part IV / 230.24

Question 24: NEC 620.37 generally restricts what may be installed within an elevator hoistway?

  • Wiring and equipment not associated with the elevator itself
  • Nothing — any building wiring may pass through freely
  • Only the traveling cable, which is also prohibited
  • Fire alarm wiring only, which is otherwise unrestricted

NEC Reference: NEC 620.37

Question 25: A rooftop channel-letter sign is supplied from a panelboard on the floor below, and the branch-circuit breaker is not within sight of the sign. Which arrangement complies with NEC 600.6(A)?

  • A tag on the breaker marked 'SIGN' is sufficient
  • A snap switch inside the sign body may serve as the only disconnect
  • The breaker is lockable in the open position, with a locking provision that stays in place with or without the lock installed
  • No disconnect is needed because the sign is on a roof

NEC Reference: NEC 600.6(A), 110.25

Key NEC References for This Test

ArticleWhat It Covers
Art. 220Load Calculations — optional and standard methods for multifamily
Art. 230Services — service design, sizing, multiple disconnects
Art. 430Motors — complete branch circuit design (conductor + OCPD + overload + disconnect)
Art. 445Generators — standby systems, transfer switches
Art. 450Transformers — sizing, primary/secondary OCPD, installation
Art. 706Energy Storage Systems — battery/solar storage (major NEC 2026 expansion)
Study Tip: Practice transformer kVA calculations daily. Know the formula: I = kVA × 1000 ÷ (V × 1.732) for three-phase. This comes up on almost every master exam.