JOURNEYMAN NEC 2023

Journeyman Electrician Practice Test 18

Free practice test 18 for the journeyman electrician exam. Covers grounding systems, lightning protection, ground rod resistance, standby power requirements, current transformer calculations, synchronous motor power factors, and emergency power rules.

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 45 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account required. All questions include detailed explanations and NEC references.

Most state Journeyman exams have 80–100 questions covering NEC code, wiring methods, branch circuits, motor controls, and load calculations.

Most states require a 70–75% passing score. This practice test uses the same 70% pass threshold so you know where you stand.

Questions are written to the 2023 NEC. Check your state licensing board to confirm which edition your state has adopted.

This test covers grounding and emergency power systems. Know that ground rod resistance must not exceed 25 ohms (NEC 250.56). Review NEC Article 700 (emergency systems) and NEC 225.6 (overhead conductor sizes). Understand the difference between leading and lagging power factor in synchronous motors.

30
Questions
45 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

JOURNEYMAN · NEC 2023
Journeyman Electrician Practice Test 18
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Journeyman Electrician Practice Test 18 — Question List

Question 1: A good grounding system can also protect the electrical system from lightning effects.

  • True
  • False

Question 2: The resistance between a driven pipe or ground rod, and the earth should not exceed ............... ohms.

  • 25
  • 30
  • 20

NEC Reference: NEC 250.84

Question 3: If a house having less than two branch circuits with an ampere rating of 25 ampere. what is the minimum wire size that can be used?

  • No 8
  • No 6
  • No 10

Question 4: As per NEC, minimum ........................ size wire is required for overhead spas up to 50 ft.

  • No 8
  • No 10
  • No 6

NEC Reference: NEC 225.6(A)

Question 5: If the service entrance current transformer has a turns ratio of 200:5. If the primary of  transformer has a current of a 100 amp what is its secondary current in amperes?

  • 5 amps
  • 10 amps
  • 2.5 amps

Question 6: The standby power plant should be capable of delivering the full power within ............... sec of the general power failure.

  • 60 sec
  • 120 sec
  • 90 sec
  • 75 sec

Question 7: The emergency power plant, once started after a loss of normal power, must continue to run at least 60 minutes after the power is re-established in a hospital.

  • True
  • False

Question 8: The power factor of a under excited synchronous motor is always.................

  • unity
  • leading
  • lagging

Question 9: Which of the following motor is most suitable for timing and signalling devices?

  • reluctance motor
  • D.C Series motor
  • linear motor

Question 10: Regulating transformers in power system are used in power system to control ............................

  • power factor
  • load flow
  • voltage

Question 11: What is unique about the speed of a synchronous motor compared to an induction motor?

  • It runs above synchronous speed
  • It runs at exactly synchronous speed with no slip
  • It runs below synchronous speed like an induction motor
  • Speed varies continuously with load

Question 12: A 4-pole motor is operated on a 60 Hz supply. What is the synchronous speed?

  • 900 RPM
  • 1200 RPM
  • 1800 RPM
  • 3600 RPM

Question 13: A 3-phase induction motor .............

  • Needs a starting capacitor to start
  • Is self-starting due to the rotating magnetic field
  • Cannot start under load — it must start at no load
  • Requires a manually operated starting switch

Question 14: Why does a single-phase induction motor need a starting winding or capacitor to start?

  • Because single-phase power has lower voltage
  • Because the single-phase supply creates a pulsating field that cannot self-start
  • Because single-phase motors are always DC motors
  • Because single-phase motors have too many poles

Question 15: When multiple grounding electrodes are present at a building, what does NEC 250.50 require?

  • Only the best one needs to be connected to the panel
  • All grounding electrodes must be bonded together
  • Each electrode connects separately to the panel
  • Only ground rods need to be connected to each other

NEC Reference: NEC 250.50

Question 16: For a metal water pipe to be used as a grounding electrode, how much of the pipe must be in contact with the earth?

  • At least 4 feet
  • At least 6 feet
  • At least 10 feet
  • At least 20 feet

NEC Reference: NEC 250.52(A)(1)

Question 17: A concrete-encased grounding electrode (Ufer ground) uses at least how many feet of reinforcing steel bar?

  • 8 feet
  • 10 feet
  • 20 feet
  • 25 feet

NEC Reference: NEC 250.52(A)(3)

Question 18: What is the function of the main bonding jumper at the service entrance?

  • It connects the hot wire to the meter
  • It connects the neutral to the EGC at the service entrance
  • It bonds all branch circuits together
  • It provides a path from the panel to the ground rod only

NEC Reference: NEC 250.28

Question 19: What is the purpose of an equipment bonding jumper?

  • To bond the neutral and hot conductors in a sub-panel
  • To ensure continuity of the equipment grounding conductor path
  • To increase the voltage of the circuit
  • To connect two separate services together

NEC Reference: NEC 250.102

Question 20: Emergency electrical systems must be tested .............

  • Only when the building owner requests it
  • Periodically to verify correct operation when normal power fails
  • Only during the initial installation inspection
  • Emergency systems do not need testing once installed

NEC Reference: NEC 700.3(B)

Question 21: For how long must emergency lighting unit equipment (battery packs) remain on after normal power fails?

  • 30 minutes
  • 60 minutes
  • 90 minutes (1.5 hours)
  • 4 hours

NEC Reference: NEC 700.12(F)(1)

Question 22: An over-excited synchronous motor operates with a power factor that is .............

  • Lagging
  • Leading
  • Unity (1.0) always
  • Zero always

Question 23: Which of the following locations in a dwelling unit requires GFCI protection for 15- and 20-ampere receptacles?

  • Only in the bathroom
  • Only in the kitchen
  • In bathrooms, garages, outdoors, kitchens, basements, and crawl spaces
  • Only in rooms that have plumbing

NEC Reference: NEC 210.8(A)

Question 24: According to NEC 210.12(A), where are arc fault circuit interrupters (AFCI) required in a dwelling unit?

  • Only in bedroom circuits
  • Only where GFCI is not installed
  • All 15- and 20-ampere, 120-volt circuits in all areas of the dwelling
  • Only in kitchens and dining areas

NEC Reference: NEC 210.12(A)

Question 25: When measuring the winding resistance of a motor or transformer with an ohmmeter, what must be done first?

  • Set the motor to its lowest speed first
  • De-energize and turn off all power to the equipment
  • Connect the ohmmeter while the motor is running
  • Measure through the motor nameplate terminals only

Question 26: What instrument is used to test the insulation quality of motor windings?

  • A standard multimeter set to resistance
  • A megohmmeter (megger)
  • A clamp-on ammeter
  • An oscilloscope

Question 27: A digital multimeter (DMM) can measure which of the following quantities?

  • Voltage only
  • Voltage and current only
  • Voltage, current, and resistance
  • Power (watts) only

Question 28: What is the main advantage of using a clamp-on ammeter to measure motor current?

  • It measures both AC and DC with the same accuracy
  • It measures current without breaking the circuit
  • It is cheaper than a standard ammeter
  • It reads in milliamperes only

Question 29: A built-in thermal protector inside a motor will open the circuit when .............

  • The motor speed drops below 75% of rated speed
  • The motor winding temperature becomes dangerously high
  • The supply voltage drops 10% below rated
  • The motor current exceeds its full-load rating by 10%

Question 30: According to NEC Article 100, what is the "service point"?

  • The main circuit breaker in the service panel
  • The point of connection between the utility and the premises wiring
  • The kilowatt-hour meter on the outside of the building
  • The first junction box inside the building

NEC Reference: NEC 100

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
EXAM CARD JOURNEYMAN
Questions30
Time limit45 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)