HVAC NEC 2023

HVAC Certification Practice Test 20

A mixed diagnostic review combining superheat/subcooling readings with electrical fault scenarios — meters, motor nameplate data, safety switches, and anti-short-cycle protection.

TOPICS COVERED
HVAC Practice tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 25 min for 25 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no signup required.

HVAC electrical exams cover electrical theory (Ohm's Law, circuits), transformers, single-phase and three-phase motors, control wiring, safety, and troubleshooting.

Requirements vary by state. HVAC technicians typically need EPA 608 certification and may need a separate electrical license for line voltage work.

Exam Tip: Real troubleshooting often blends refrigerant-side readings with electrical checks — practice thinking across both at once.

25
Questions
25 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

HVAC · NEC 2023
HVAC Certification Practice Test 20
Q1 / 25
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

HVAC Certification Practice Test 20 — Question List

Question 1: A system shows high superheat and the compressor draws a sustained current near its nameplate LRA without settling to RLA. What is likely happening?

  • This combination is entirely normal and needs no action
  • The compressor is stalled at locked rotor current and not actually starting, which is a separate issue from the refrigerant-side superheat reading
  • High superheat always means the compressor windings are grounded
  • LRA-level current always means the system is overcharged

Question 2: A system has high superheat, low subcooling, and the low-pressure switch has tripped, shutting down the compressor. What single root cause would explain all three symptoms?

  • An undercharged system (or a significant refrigerant leak)
  • An overcharged system
  • A failed run capacitor only
  • A miswired G terminal

Question 3: A technician clamps around both compressor leads together and reads 0.2A on a unit rated 16A RLA, and concludes the compressor is off. The compressor is actually running. What mistake was made?

  • Clamping around both conductors of the same circuit, causing their magnetic fields to cancel and give a falsely low reading
  • The meter was set to measure resistance instead of current
  • The compressor nameplate must be incorrect
  • This reading proves the compressor is grounded

Question 4: A furnace fires, runs briefly, then trips its limit switch. A very dirty filter is found. What single underlying issue likely explains this, and could it also have affected the sail switch earlier?

  • Restricted airflow from the dirty filter — severe enough to eventually trip the limit switch, and possibly marginal enough to have still allowed the sail switch to initially close
  • The refrigerant charge is definitely the cause
  • The run capacitor is definitely the cause
  • The condenser fan motor is definitely the cause

Question 5: A compressor's running current matches its nameplate RLA closely, but a GFCI-protected disconnect keeps tripping. Continuity checks are normal. What tool and test should the technician use next?

  • A megohmmeter, to check insulation resistance to ground for a grounded winding
  • A capacitor tester only
  • A pressure gauge set only
  • A thermostat wire color chart

Question 6: After a brief power flicker, a customer calls saying the AC "won't turn on" even though it was working fine before. Before assuming a failure, what should be checked first?

  • Whether enough time has passed for the anti-short-cycle delay to clear
  • Whether the refrigerant has completely leaked out
  • Whether the compressor has permanently failed
  • Whether the ductwork needs to be replaced

Question 7: A TXV system shows normal subcooling but the compressor briefly hits an amp reading near LRA before settling well below RLA. Is the electrical behavior concerning?

  • Yes, this always indicates a failing compressor
  • No — a brief spike near LRA settling to a value at or below RLA is normal starting behavior, unrelated to the subcooling reading
  • Yes, this always means the TXV has failed
  • No conclusion can be drawn without knowing the thermostat wire colors

Question 8: Before megger-testing a compressor motor, why should a technician also make sure any related run capacitor has been safely discharged first?

  • A charged capacitor connected to the circuit could interfere with the test or pose a shock hazard during setup
  • Capacitors never retain any charge under any circumstances
  • This step is only relevant to three-phase motors
  • Megger tests are impossible if a capacitor is present anywhere in the building

Question 9: A three-phase scroll compressor was just reconnected after service. It draws a sustained high current and runs hot without building proper pressure. What two things should the technician check, in order?

  • First verify phase rotation with a meter, since reversed rotation causes exactly this symptom; then re-check pressures once rotation is confirmed correct
  • Immediately replace the compressor without further checks
  • Immediately add more refrigerant without further checks
  • Immediately replace the thermostat without further checks

Question 10: A compressor that sat without power in cold weather is started immediately after power is restored, without the manufacturer-specified wait time. What refrigerant-and-electrical-related risk does this create?

  • Refrigerant that migrated into the cold oil can flash to vapor on startup, foaming the oil and risking mechanical damage
  • There is no risk at all in this situation
  • This only affects the thermostat display
  • This only affects the outdoor air damper

Question 11: A blower motor with SF 1.0 has been running continuously above its rated horsepower for months due to a duct restriction. What is a reasonable expectation for this motor's service life?

  • It is likely to wear out or fail sooner than expected due to sustained operation beyond its rated capacity with no margin
  • Service factor has no bearing on motor life expectancy
  • The motor will automatically last longer under these conditions
  • This scenario has no effect since SF only matters at start-up

Question 12: A TXV system shows superheat swinging erratically, and the compressor's running amp draw is also fluctuating noticeably in step with it. What does this pattern suggest?

  • The TXV may be hunting/malfunctioning, causing the compressor load (and therefore current draw) to vary along with the unstable superheat
  • This pattern is always caused by a bad thermostat C wire
  • This pattern is always caused by a tripped limit switch
  • This pattern has no relationship between the two readings

Question 13: An outdoor GFCI service receptacle near a condensing unit trips whenever it rains. Is this necessarily a sign the condensing unit's electrical system has failed?

  • Yes, this always means the condensing unit itself has a wiring fault
  • Not necessarily — it could simply be the GFCI doing its job in response to a wet connection or compromised cord/tool, separate from the unit's own wiring
  • Yes, this always means the refrigerant charge is wrong
  • GFCIs cannot be affected by moisture at all

Question 14: Before replacing a run capacitor, what is the correct safety sequence a technician should follow, combining lockout/tagout and capacitor discharge practices?

  • De-energize and lock/tag the disconnect, verify zero energy with a meter, then safely discharge the capacitor with an insulated tool before removing it
  • Simply unplug the thermostat and begin work immediately
  • Short the capacitor with a bare screwdriver as the first step
  • No precautions are needed since capacitors are always safe once the breaker is off

Question 15: A blower motor's amp draw reads well below its nameplate FLA, and the sail switch never proves airflow. What single underlying cause could explain both symptoms?

  • A failing blower motor not moving enough air (and drawing less current as a result), or a blower belt/coupling problem preventing proper airflow
  • The refrigerant charge is always the explanation for this pattern
  • The compressor contactor is always the explanation for this pattern
  • The reversing valve is always the explanation for this pattern

Question 16: On a mild day, a rooftop unit's compressor runs constantly at full capacity instead of using outdoor air first. What component would a technician reasonably investigate?

  • The economizer damper actuator and its control logic, to see if it is failing to open and use available free cooling
  • The thermostat wire color scheme only
  • The crankcase heater only
  • The recovery cylinder fill level

Question 17: A technician's logged megger readings on a compressor have been trending downward over the past three service visits, though still passing. What is a reasonable proactive recommendation to the customer?

  • Monitor the trend and plan for a possible future compressor replacement, rather than waiting for a sudden failure
  • Ignore the trend entirely since the reading currently passes
  • Immediately replace the thermostat instead
  • Immediately void the equipment warranty

Question 18: A building experiences a brief, noticeable light flicker every time a large rooftop compressor starts. What electrical concept explains this?

  • The compressor's brief high inrush (LRA) current draw momentarily loading down the supply voltage
  • This has no relationship to the compressor at all
  • This always means the building wiring is undersized beyond any acceptable limit
  • This always means the compressor is grounded

Question 19: A system with confirmed low refrigerant charge (high superheat, low subcooling) also shows the compressor running current below its nameplate RLA. Why might undercharge cause lower-than-normal running current?

  • With less refrigerant mass flowing through the system, the compressor may be working against a lighter load than normal, drawing less current
  • Undercharge always increases running current well above RLA in every case
  • Refrigerant charge has no relationship to compressor current draw
  • This pattern proves the thermostat is miswired

Question 20: On a system with a variable-speed (ECM/inverter) blower motor, why might a sail switch calibrated for a fixed-speed blower cause nuisance issues at very low blower speed settings?

  • At a low modulated speed, actual airflow may be lower than what a switch calibrated for full-speed operation expects, even though the system is operating normally
  • Variable-speed blowers never move any air at all
  • Sail switches are never used with variable-speed equipment under any circumstances
  • This scenario is impossible and cannot occur

Question 21: A condenser fan motor's run capacitor tests at 28 MFD against a 35 MFD ±6% rating, and the motor's running amp draw is noticeably above its nameplate FLA. Are these two findings related?

  • No, capacitor condition and current draw are always unrelated
  • Yes — a weak capacitor outside tolerance can cause the motor to work harder and draw more current than normal
  • Yes, but only because the refrigerant charge is definitely also wrong
  • No, 28 MFD is actually within the acceptable range for this capacitor

Question 22: After reconnecting a three-phase compressor following a repair, what two checks should generally be completed before considering the job finished, based on topics covered in this test series?

  • Verify correct phase rotation with a meter, and confirm winding insulation is healthy (e.g., via a megger check) if there is any reason to suspect it was disturbed
  • Neither check is ever necessary after a repair
  • Only the thermostat wire colors need to be checked
  • Only the outdoor air damper needs to be checked

Question 23: Why is it valuable for a technician to consider both refrigerant-side readings (superheat/subcooling) and electrical readings (amp draw, voltage) together when diagnosing a system?

  • Many real-world faults produce related symptoms on both sides, and looking at only one can miss the full picture or the true root cause
  • Refrigerant-side and electrical readings are always completely unrelated
  • Only electrical readings are ever useful in real diagnostics
  • Only refrigerant-side readings are ever useful in real diagnostics

Question 24: A compressor nameplate lists RLA 20A. A technician properly isolates one conductor and measures 31A during steady running operation, well past start-up. What should this prompt the technician to do?

  • Do nothing further, since any running current is acceptable
  • Investigate further — a sustained running current well above nameplate RLA is not normal and needs a cause identified
  • Assume the meter is always wrong in this situation
  • Assume the nameplate must be misprinted in every such case

Question 25: A system shows low superheat, high subcooling, a compressor running current above nameplate RLA, and normal continuity/megger readings on the windings. What is the most likely explanation tying these findings together?

  • The system is overcharged, causing the compressor to work harder (higher current) while the windings themselves remain electrically healthy
  • The compressor windings are definitely grounded despite the normal megger reading
  • The system is definitely undercharged
  • The thermostat is definitely miswired

Key NEC References for This Test

ArticleWhat It Covers
Art. 440Air Conditioning Equipment — use nameplate MCA and MOCP, not FLA alone
Art. 430Motors — general motor rules that Art. 440 modifies
Study Tip: Practice reading ladder diagrams. Trace each rung from L1 to the load: contacts open → circuit dead. Contacts closed → current flows. This is how HVAC electrical troubleshooting works.
EXAM CARD HVAC
Questions25
Time limit25 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 Art. 440 & electrical theory