HVAC NEC 2023

HVAC Certification Practice Test 2

This test focuses on HVAC motor types, including PSC, CSIR, CSCR, ECM, and shaded-pole motors. You will also practice diagnosing run and start capacitor failures using symptoms and microfarad tolerance math.

TOPICS COVERED
HVAC Practice tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 25 min for 25 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no signup required.

HVAC electrical exams cover electrical theory (Ohm's Law, circuits), transformers, single-phase and three-phase motors, control wiring, safety, and troubleshooting.

Requirements vary by state. HVAC technicians typically need EPA 608 certification and may need a separate electrical license for line voltage work.

Exam Tip: When a capacitor question gives you a rated value and a tolerance, calculate the acceptable range first (rated value plus or minus the percentage), then compare the measured reading to that range.

25
Questions
25 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

HVAC · NEC 2023
HVAC Certification Practice Test 2
Q1 / 25
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time

Student Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

HVAC Certification Practice Test 2 — Question List

Question 1: What does PSC stand for in HVAC motors?

  • Parallel Start Circuit
  • Permanent Split Capacitor
  • Power Supply Controller
  • Primary Speed Control

Question 2: Which of these statements is true about a PSC motor?

  • It always needs both a start and run capacitor
  • It has no capacitor at all
  • It uses a run capacitor only, with no start capacitor
  • It uses a centrifugal switch to disconnect its start winding

Question 3: What does CSIR stand for?

  • Capacitor Start Inverter Run
  • Continuous Speed Induction Relay
  • Capacitor Switch Ignition Relay
  • Capacitor Start Induction Run

Question 4: In a CSIR motor, what disconnects the start capacitor once the motor is running?

  • A centrifugal switch
  • A run capacitor
  • A contactor
  • A defrost board

Question 5: A compressor needs high starting torque, more than a CSIR motor can give. Which motor type is often used instead?

  • PSC
  • CSCR (Capacitor Start Capacitor Run)
  • ECM
  • Shaded pole

Question 6: What is an ECM motor?

  • A single-speed motor that always uses a run capacitor
  • A motor found only in window units
  • An Electronically Commutated Motor with a built-in inverter and no capacitor
  • A three-phase compressor motor

Question 7: Where are shaded-pole motors most commonly used in HVAC equipment?

  • Large three-phase compressors
  • Condenser fans on rooftop units
  • Variable-speed blowers
  • Small evaporator fans

Question 8: A PSC condenser fan motor runs but struggles and draws higher-than-normal amps. What is the most likely cause?

  • A weak or failing run capacitor
  • A shorted centrifugal switch
  • An oversized crankcase heater
  • A tripped high-pressure switch

Question 9: A motor hums but will not start turning. What does this symptom usually point to?

  • A tripped GFCI
  • A failed capacitor
  • Low refrigerant charge
  • A miswired thermostat

Question 10: A blower motor runs, but noticeably slower than normal. Which component should be checked first?

  • The thermostat batteries
  • The evaporator coil
  • The run capacitor
  • The disconnect switch

Question 11: When testing a run capacitor with a capacitor meter, the reading should be within about how much of the rated microfarad (MFD) value?

  • About ±25%
  • Exactly the rated value with zero tolerance
  • About ±50%
  • About ±6%

Question 12: A run capacitor is rated 35 MFD ±6%. A technician measures 32.5 MFD. Is this capacitor within spec?

  • No, because the acceptable range is about 32.9-37.1 MFD and 32.5 is below it
  • Yes, because 32.5 is close to 35
  • Yes, because any reading below the rated value is acceptable
  • No, because the capacitor should read exactly 35 MFD

Question 13: In a CSIR motor, the centrifugal switch fails and stays closed even after the motor reaches full speed. What is the likely result?

  • The motor runs cooler than normal
  • The start winding stays energized and overheats
  • The run capacitor is bypassed
  • The motor automatically switches to three-phase power

Question 14: What is the main wiring difference between a CSIR motor and a CSCR motor?

  • A CSIR motor never uses a capacitor
  • A CSCR motor has no centrifugal switch or start components at all
  • A CSCR motor keeps a run capacitor in the circuit after starting, in addition to the start capacitor used briefly at startup
  • A CSIR motor runs on three-phase power only

Question 15: Which statement about PSC motors is correct?

  • A PSC motor always needs a start capacitor and a centrifugal switch
  • A PSC motor cannot use any capacitor
  • A PSC motor only works on three-phase power
  • A PSC motor starts and runs using only a run capacitor, no start capacitor needed

Question 16: Which motor type is most common in modern variable-speed blowers?

  • ECM (Electronically Commutated Motor)
  • Shaded pole
  • CSIR
  • Wound rotor

Question 17: Why doesn't an ECM motor need a run or start capacitor?

  • It runs on 24V control voltage only
  • It has a built-in inverter that electronically controls the motor
  • It has no moving rotor
  • It only operates on three-phase power

Question 18: A PSC condenser fan motor hums but does not spin. Its capacitor is rated 5 MFD ±6% and tests at 4.2 MFD. What should the technician do?

  • Leave the capacitor alone, since 4.2 MFD is close enough
  • Replace the entire motor without checking the capacitor further
  • Replace the capacitor, since 4.2 MFD is well below the acceptable range
  • Add a second run capacitor in series

Question 19: Why does a true three-phase induction motor not need a start or run capacitor?

  • It uses a centrifugal switch instead
  • It runs at a fixed low voltage
  • It has no start winding at all
  • The three offset phases naturally create a rotating magnetic field

Question 20: Which motor design uses both a start capacitor and a run capacitor to provide high starting torque for a demanding compressor?

  • CSCR (Capacitor Start Capacitor Run)
  • PSC
  • Shaded pole
  • ECM

Question 21: How does a shaded-pole motor compare to a PSC motor in torque and efficiency?

  • Shaded-pole motors have higher torque and higher efficiency
  • Shaded-pole motors have lower torque and lower efficiency
  • They are identical in torque and efficiency
  • Shaded-pole motors run only on three-phase power

Question 22: What is the purpose of a run capacitor in a single-phase motor?

  • It only helps the motor start, then disconnects
  • It protects the motor from high pressure
  • It improves running efficiency and torque while the motor operates
  • It converts AC power to DC power

Question 23: What happens if a start capacitor is left connected in the circuit continuously, instead of disconnecting after startup?

  • It saves energy over time
  • It improves motor torque with no downside
  • It has no effect on the motor
  • It overheats the start winding

Question 24: A run capacitor is rated 45 MFD ±6%. A technician measures 46 MFD. Is this capacitor within spec?

  • Yes, because the acceptable range is about 42.3-47.7 MFD and 46 falls within it
  • No, because any reading above the rated value fails
  • Yes, because capacitors have no real tolerance
  • No, because it must read exactly 45 MFD

Question 25: A technician opens a compressor's electrical compartment and finds both a start capacitor with a start relay, and a separate run capacitor wired in. What motor type is this compressor most likely using?

  • PSC
  • CSCR (Capacitor Start Capacitor Run)
  • Shaded pole
  • ECM

Key NEC References for This Test

ArticleWhat It Covers
Art. 440Air Conditioning Equipment — use nameplate MCA and MOCP, not FLA alone
Art. 430Motors — general motor rules that Art. 440 modifies
Study Tip: Practice reading ladder diagrams. Trace each rung from L1 to the load: contacts open → circuit dead. Contacts closed → current flows. This is how HVAC electrical troubleshooting works.
EXAM CARD HVAC
Questions25
Time limit25 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 Art. 440 & electrical theory