EPA 608 Universal Practice Exam 1 (100 Questions)

Free EPA 608 Universal practice exam with 100 questions, set up like the real certification test: 25 Core, 25 Type I, 25 Type II and 25 Type III questions. It covers the venting ban, recovery, recycling and reclaiming, cylinder safety, required evacuation levels, leak repair rules, small appliance recovery, high-pressure systems and low-pressure chillers.

Share this test
TOPICS COVERED
epa 608 practice tests

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 150 min for 100 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account needed.

The EPA 608 certification is required by law for any technician who purchases or handles refrigerants. It covers safe handling, leak detection, recovery, and environmental regulations.

Type I covers small appliances (≤5 lbs refrigerant), Type II covers high-pressure systems, Type III covers low-pressure systems, and Universal covers all three. Most HVAC technicians pursue Universal certification.

You must score at least 70% on each section of the exam. The Universal exam has four parts: core, Type I, Type II, and Type III.

Before You Start

  • 100 questions: 25 Core, 25 Type I, 25 Type II, 25 Type III
  • 2½ hours on the timer
  • On the real exam you must pass each section with at least 70% (18 of 25) to earn Universal certification. Count your correct answers per section in the review.
  • Closed book, like the proctored exam

Tip: Know the evacuation level table for Type II and Type III, and the 80%/90% recovery rule for Type I. These are the most-tested numbers.

100
Questions
150 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

EPA 608
EPA 608 Universal Practice Exam 1 (100 Questions)
Q1 / 100
--:-- ON PACE
Auto-save 0% complete
0%
your score

0
Correct
0
Wrong
0
Skipped
0s
Time
How was this test?
One tap, no sign-up.
Share your score
Share it and get the EPA 608 Quick Reference Card free, right now.
Unlocked — thanks for sharing! 🎉
Get the EPA 608 Quick Reference Card
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

EPA 608 Universal Practice Exam 1 (100 Questions) — Question List

Question 1: Which type of refrigerant has the highest ozone depletion potential?

  • HFOs (such as R-1234yf)
  • HCFCs (such as R-22)
  • CFCs (such as R-12)
  • HFCs (such as R-410A)

NEC Reference: 40 CFR Part 82, Subpart F

Question 2: In which layer of the atmosphere does the ozone that protects us from ultraviolet radiation exist?

  • Ionosphere
  • Mesosphere
  • Stratosphere
  • Troposphere

NEC Reference: 40 CFR Part 82, Subpart F

Question 3: Which element in CFC and HCFC refrigerants is responsible for destroying ozone?

  • Hydrogen
  • Chlorine
  • Fluorine
  • Carbon

NEC Reference: 40 CFR Part 82, Subpart F

Question 4: Which international agreement set the schedule for phasing out ozone-depleting substances?

  • The Montreal Protocol
  • The Clean Water Act
  • The Paris Agreement
  • The Kyoto Protocol

NEC Reference: 40 CFR Part 82, Subpart F

Question 5: Under Section 608 of the Clean Air Act, knowingly venting CFC and HCFC refrigerants during service has been prohibited since:

  • November 15, 1995
  • January 1, 2010
  • July 1, 1992
  • January 1, 1996

NEC Reference: 40 CFR 82.154

Question 6: Which of these releases is permitted (not a violation of the venting prohibition)?

  • Venting the last pound of refrigerant when recovery is taking too long
  • De minimis releases that happen during good-faith efforts to recover refrigerant, such as when connecting and disconnecting hoses
  • Venting a small appliance that holds less than 5 pounds of refrigerant
  • Releasing a small amount to make room in a recovery cylinder that is nearly full

NEC Reference: 40 CFR 82.154

Question 7: What does it mean to "recover" refrigerant?

  • To clean refrigerant for reuse by oil separation and filter-driers
  • To destroy refrigerant by incineration
  • To remove refrigerant in any condition from a system and store it in an external container without necessarily testing or processing it
  • To process refrigerant to new-product specifications with chemical analysis

NEC Reference: 40 CFR 82.152

Question 8: What does it mean to "reclaim" refrigerant?

  • To filter it once and put it back in the same system
  • To store it in a recovery cylinder
  • To reprocess it to at least the purity in AHRI Standard 700, verified by chemical analysis
  • To mix it with new refrigerant

NEC Reference: 40 CFR 82.152

Question 9: Recycled refrigerant (cleaned on site, not reclaimed) may be returned to:

  • Any customer's equipment
  • Disposable cylinders for sale
  • A refrigerant wholesaler for resale as new
  • Equipment owned by the same owner

NEC Reference: 40 CFR 82.154

Question 10: Recovery cylinders are normally identified by which colors?

  • All white
  • Gray body with a yellow top
  • Red body
  • Green body with a white top

NEC Reference: DOT / AHRI Guideline K

Question 11: A refillable recovery cylinder should never be filled beyond what percentage of its capacity?

  • 60%
  • 80%
  • 90%
  • 100%

NEC Reference: DOT 49 CFR

Question 12: Refillable refrigerant cylinders must be hydrostatically tested and date-stamped every:

  • 10 years
  • 1 year
  • 5 years
  • 3 years

NEC Reference: DOT 49 CFR 180

Question 13: Disposable cylinders used for new refrigerant must:

  • Never be refilled, and should be recovered to 0 psig and rendered useless before recycling the metal
  • May be used as recovery cylinders if they are painted gray with a yellow top
  • May be refilled once with the same refrigerant if the valve is still in good condition
  • Should be stored with the valve open so pressure cannot build up inside

NEC Reference: 49 CFR / 40 CFR 82

Question 14: Why should a refrigerant cylinder never be heated with an open flame or torch?

  • It changes the refrigerant into a different type
  • The pressure can rise rapidly and rupture the cylinder
  • It voids the cylinder warranty only
  • It makes the refrigerant evaporate too slowly

NEC Reference: Safety

Question 15: Refrigerant leak-testing a system must be done with pressurized:

  • Dry nitrogen, using a pressure regulator and relief valve
  • Oxygen, because it leaves no residue and is easy to find with soap bubbles
  • The system's own refrigerant, heated with a torch to raise the pressure
  • Compressed shop air, filtered through a drier to keep moisture out

NEC Reference: Safety

Question 16: What is the main danger of a large refrigerant leak in a small, enclosed equipment room?

  • The refrigerant raises the room temperature enough to trip equipment overloads
  • The refrigerant is lighter than air and collects at the ceiling, creating a fire hazard
  • The refrigerant reacts with humidity and forms water that shorts electrical equipment
  • The refrigerant is heavier than air and can displace oxygen, causing suffocation

NEC Reference: ASHRAE 15 / Safety

Question 17: Heating CFC or HCFC refrigerant to very high temperatures, such as with an open flame, can produce:

  • Nitrogen
  • Pure oxygen
  • Harmless water vapor
  • Toxic gases such as phosgene

NEC Reference: Safety

Question 18: Under ASHRAE Standard 34, refrigerant safety group A2L means:

  • Higher toxicity and nonflammable
  • Lower toxicity and mildly flammable (low burning velocity)
  • Higher toxicity and highly flammable
  • Lower toxicity and no flame propagation

NEC Reference: ASHRAE 34

Question 19: Since November 15, 1993, recovery and recycling equipment used for EPA Section 608 work must be:

  • Made in the United States and stamped with a serial number
  • Painted yellow and gray so it can be identified on job sites
  • Certified by an EPA-approved testing organization to meet EPA requirements
  • Rated at least 1 horsepower so it can reach the vacuum levels

NEC Reference: 40 CFR 82.158

Question 20: What should a technician do before recovering refrigerant into a cylinder that already contains some refrigerant?

  • Vent the old refrigerant so the cylinder starts empty and clean
  • Add a small amount of nitrogen to push any air out of the cylinder
  • Nothing, because all refrigerants can be mixed and separated later
  • Make sure the cylinder contains the same refrigerant type, because mixed refrigerants may be impossible to reclaim

NEC Reference: AHRI Guideline K

Question 21: Who may purchase refrigerants regulated under Section 608 (other than small cans for motor vehicle use)?

  • Only refrigerant wholesalers who resell it to building owners
  • Technicians certified under Section 608 (or 609 for MVAC refrigerant), and certain businesses that employ them
  • Only appliance manufacturers and their factory service centers
  • Anyone over 18 years old who shows a valid photo ID at the counter

NEC Reference: 40 CFR 82.154(c)

Question 22: Technicians who maintain, service or repair appliances must keep a copy of their certification and:

  • Post it in the customer's home
  • Renew it every year
  • Return it to the EPA every 3 years
  • Make it available when buying refrigerant and when asked by the EPA

NEC Reference: 40 CFR 82.161

Question 23: Under the EPA leak repair rules for ozone-depleting refrigerants, comfort cooling appliances with 50 or more pounds of charge must be repaired when the annual leak rate exceeds:

  • 10%
  • 30%
  • 20%
  • 35%

NEC Reference: 40 CFR 82.157

Question 24: In a refrigeration system, refrigerant at its saturation temperature and pressure is:

  • Below its freezing point, so it can no longer change state
  • Always 100% liquid, with no vapor present at any point in the system
  • Always 100% superheated vapor, well above its boiling temperature
  • A mixture of liquid and vapor where the pressure and temperature are directly related

NEC Reference: Refrigeration Basics

Question 25: The main purpose of evacuating (pulling a deep vacuum on) a system before charging is to remove:

  • Refrigerant from the cylinder
  • Copper filings
  • Oil
  • Air (noncondensables) and moisture

NEC Reference: Refrigeration Basics

Question 26: Under EPA rules, a "small appliance" is a product that is fully manufactured, charged and hermetically sealed at the factory with:

  • 50 pounds or less
  • 15 pounds or less
  • 5 pounds or less of refrigerant
  • 2 pounds or less

NEC Reference: 40 CFR 82.152

Question 27: Which of these is a Type I small appliance?

  • A 300-ton centrifugal chiller
  • A supermarket rack system
  • A 5-ton residential split system
  • A household refrigerator

NEC Reference: 40 CFR 82.152

Question 28: Using recovery equipment made after November 15, 1993, how much refrigerant must be recovered from a small appliance whose compressor is operating?

  • 50% of the refrigerant
  • 90% of the refrigerant, or a 4-inch Hg vacuum
  • 100% of the refrigerant
  • 80% of the refrigerant

NEC Reference: 40 CFR 82.156

Question 29: Using recovery equipment made after November 15, 1993, how much refrigerant must be recovered from a small appliance whose compressor is NOT operating?

  • 90% of the refrigerant
  • 80% of the refrigerant, or a 4-inch Hg vacuum
  • 100% of the refrigerant
  • 70% of the refrigerant

NEC Reference: 40 CFR 82.156

Question 30: Recovery equipment made before November 15, 1993 must recover what percentage of the refrigerant from a small appliance?

  • 80%, or a 4-inch Hg vacuum
  • 90%
  • 100%
  • 50%

NEC Reference: 40 CFR 82.156

Question 31: A "system-dependent" (passive) recovery process:

  • Is used only on large low-pressure chillers that have purge units
  • Uses the appliance's own compressor or internal pressure to move refrigerant out
  • Has its own built-in compressor and can be used on any size system
  • Is not allowed by the EPA on any appliance with less than 50 pounds

NEC Reference: 40 CFR 82.152

Question 32: System-dependent recovery equipment may be used only on appliances containing:

  • 200 pounds or less
  • 50 pounds or less
  • Any amount
  • 15 pounds of refrigerant or less

NEC Reference: 40 CFR 82.156

Question 33: When using system-dependent recovery on a small appliance with an inoperative compressor, the technician should:

  • Cut the process tube and let the refrigerant drain into an open container
  • Vent the remaining refrigerant once half of the charge has been recovered
  • Install a fitting on the high side only and wait for the pressure to equalize
  • Install access fittings on both the high and low sides, and heat or tap the compressor to free refrigerant from the oil

NEC Reference: Type I Procedures

Question 34: Solderless piercing-type access valves used on small appliances:

  • Are not allowed on small appliances
  • Must be welded in place
  • Are permanent and never leak
  • Can leak over time and should not be left on the appliance permanently

NEC Reference: Type I Procedures

Question 35: Before installing a piercing access valve on a small appliance, the technician should:

  • Make sure the valve fits the tubing size and the line is clean, and check that the gasket seals
  • Drain the oil from the compressor so the valve does not become clogged
  • Heat the tubing until it is red hot so the valve pierces it more easily
  • Apply refrigerant oil to the outside of the valve body but not the gasket

NEC Reference: Type I Procedures

Question 36: When recovering refrigerant from a small appliance into a non-pressurized container (such as a recovery bag), what must be done first?

  • Evacuate the container to remove air before using it
  • Heat it
  • Fill it with nitrogen
  • Nothing; it can be used as-is

NEC Reference: Type I Procedures

Question 37: A household refrigerator manufactured before 1950 may contain which refrigerants that should NOT be recovered with standard EPA-certified equipment?

  • R-134a
  • R-410A
  • Sulfur dioxide, methyl formate or ammonia
  • R-600a

NEC Reference: Type I Safety

Question 38: If the pressure in a recovered small appliance is higher than the saturation pressure for the measured temperature, it most likely contains:

  • Pure refrigerant
  • Water only
  • Too much oil
  • Noncondensables (air)

NEC Reference: Refrigeration Basics

Question 39: Who is responsible for ensuring refrigerant has been removed from a small appliance before it is disposed of?

  • The EPA, through disposal inspectors stationed at each landfill
  • The original manufacturer, through its product take-back program
  • The final person in the disposal chain, such as a scrap recycler or landfill operator
  • The homeowner's insurance company, at the time of the claim

NEC Reference: 40 CFR 82.155

Question 40: Are leak repairs required by EPA for small appliances under the federal leak repair rule?

  • Yes, whenever the annual leak rate is more than 5% of the full charge
  • Yes, all leaks must be repaired within 30 days of being discovered
  • No, the leak repair requirements apply to appliances with 50 or more pounds of ODS refrigerant
  • Yes, leaks on every appliance must be repaired within 10 days

NEC Reference: 40 CFR 82.157

Question 41: Section 608 Type I certification exams may be taken open book. What score is needed to pass the open-book Type I test?

  • 90% (23 of 25)
  • 84% (21 of 25)
  • 70% (18 of 25)
  • 60% (15 of 25)

NEC Reference: EPA Certification

Question 42: Many new household refrigerators use R-600a (isobutane). What extra precaution is needed when servicing them?

  • None, because R-600a is nonflammable and has the same safety class as R-134a
  • It must be recovered only into red disposable cylinders marked for hydrocarbons
  • It can be pushed out of the system safely using compressed air or oxygen
  • It is flammable, so keep ignition sources away and use tools and procedures rated for flammable refrigerants

NEC Reference: Type I Safety

Question 43: A small appliance system has a refrigerant leak. Which is the best way to find it?

  • Vent the system and watch where the frost forms
  • Add refrigerant until the system frosts
  • Smell for the refrigerant
  • Use an electronic leak detector or soap bubbles after confirming the system holds pressure

NEC Reference: Type I Procedures

Question 44: Self-contained recovery equipment used on small appliances:

  • Must always recover into a non-pressurized bag instead of a cylinder
  • Works only when the appliance's own compressor is running
  • Must never be used on small appliances because it pulls too deep a vacuum
  • Has its own compressor and can recover refrigerant even when the appliance compressor does not run

NEC Reference: Type I Procedures

Question 45: When a small appliance using R-134a is serviced, which oil is typically found in the compressor?

  • Motor oil
  • Mineral oil only
  • No oil
  • Polyolester (POE) oil

NEC Reference: Refrigeration Basics

Question 46: The process tube of a small appliance is typically:

  • The condensate drain tube that carries water away from the coil
  • The capillary tube that meters refrigerant into the evaporator
  • A short copper or steel tube on the compressor used for factory charging and service access
  • The outlet of the evaporator, where the suction line begins

NEC Reference: Type I Procedures

Question 47: A technician is recovering from a refrigerator with a running compressor using system-dependent recovery. Which step helps the most?

  • Run the appliance compressor and use a high-side access valve so the compressor pushes refrigerant into the container
  • Open the system to the air first so the pressures equalize quickly
  • Recover only from the low side so the running compressor is protected
  • Shut off the appliance compressor and recover through the low side only

NEC Reference: Type I Procedures

Question 48: Why is a recovery cylinder sometimes chilled (for example in ice water) during recovery?

  • To stop the cylinder from leaking
  • To freeze the refrigerant solid
  • A colder cylinder has lower pressure, so refrigerant moves into it faster
  • Because recovery cylinders must be kept below 0°F

NEC Reference: Recovery Procedures

Question 49: Small appliances such as window air conditioners are subject to which Section 608 rule?

  • Only the DOT shipping rules for the recovery cylinders
  • The venting prohibition and the required recovery levels
  • Only the leak repair rule, which applies to every appliance
  • No Section 608 rules, because they hold 5 pounds or less of refrigerant

NEC Reference: 40 CFR 82.154

Question 50: Under EPA rules, a technician needs Type I certification to service:

  • Small appliances only
  • Low-pressure chillers
  • Motor vehicle air conditioners
  • High-pressure systems over 5 pounds

NEC Reference: EPA Certification

Question 51: Which refrigerant is used in high-pressure (Type II) appliances?

  • R-410A
  • R-11
  • R-113
  • R-123

NEC Reference: 40 CFR 82.152

Question 52: Using recovery equipment made after November 15, 1993, an R-22 appliance with less than 200 pounds of charge must be evacuated to what level before opening for major repair or disposal?

  • 10 inches Hg vacuum
  • 0 inches Hg (atmospheric pressure)
  • 25 mm Hg absolute
  • 15 inches Hg vacuum

NEC Reference: 40 CFR 82.156 Table 1

Question 53: Using recovery equipment made after November 15, 1993, an R-22 appliance with 200 pounds or more of charge must be evacuated to:

  • 10 inches Hg vacuum
  • 0 inches Hg
  • 15 inches Hg vacuum
  • 4 inches Hg vacuum

NEC Reference: 40 CFR 82.156 Table 1

Question 54: Using recovery equipment made after November 15, 1993, a high-pressure appliance (other than R-22) with less than 200 pounds of charge, such as an R-410A system, must be evacuated to:

  • 15 inches Hg vacuum
  • 0 inches Hg
  • 10 inches Hg vacuum
  • 25 inches Hg vacuum

NEC Reference: 40 CFR 82.156 Table 1

Question 55: Using recovery equipment made after November 15, 1993, a high-pressure appliance (other than R-22) with 200 pounds or more of charge must be evacuated to:

  • 0 inches Hg
  • 15 inches Hg vacuum
  • 29 inches Hg vacuum
  • 10 inches Hg vacuum

NEC Reference: 40 CFR 82.156 Table 1

Question 56: Using recovery equipment made BEFORE November 15, 1993, what evacuation level is required for an R-22 appliance with 200 pounds or more?

  • 4 inches Hg vacuum
  • 10 inches Hg vacuum
  • 15 inches Hg vacuum
  • 0 inches Hg

NEC Reference: 40 CFR 82.156 Table 1

Question 57: Very high-pressure appliances (such as those using R-13 or R-503) must be evacuated to:

  • 10 inches Hg vacuum
  • 25 mm Hg absolute
  • 15 inches Hg vacuum
  • 0 inches Hg (atmospheric pressure)

NEC Reference: 40 CFR 82.156 Table 1

Question 58: Under EPA rules, which of the following is considered a "major repair"?

  • Replacing a condenser fan motor or a run capacitor on the outdoor unit
  • Replacing a thermostat or a low-voltage control transformer
  • Removal of the compressor, condenser, evaporator or auxiliary heat exchanger coil
  • Changing an air filter or cleaning the condensate drain line

NEC Reference: 40 CFR 82.152

Question 59: If a high-pressure system is opened for a repair that is NOT major and will not be followed by an evacuation of the whole appliance, it must first be:

  • Pressurized to 0 psig or lower (not above atmospheric pressure)
  • Filled with oxygen to keep moisture out while it is open
  • Left at full charge, since the repair is only minor
  • Evacuated to 15 inches Hg vacuum, the same as for a major repair

NEC Reference: 40 CFR 82.156

Question 60: If leaks make it impossible to reach the required evacuation level on a Type II system, the technician must:

  • Vent the rest of the refrigerant, since the required level cannot be reached anyway
  • Leave the system charged, open it anyway, and report the leak to the owner later
  • Add more refrigerant and keep trying until the required level is finally reached
  • Isolate the leaking parts if possible, evacuate the rest to the required level, and evacuate the leaking parts to the lowest level that can be reached

NEC Reference: 40 CFR 82.156

Question 61: After a Type II system reaches the required evacuation level, the technician should wait a few minutes. If the pressure rises, it means:

  • The system is fully recovered and can be opened right away
  • There is still refrigerant in the system (often trapped in the oil), so recovery must continue
  • The gauges are out of calibration and should be checked before continuing
  • The vacuum pump has failed and must be replaced before continuing

NEC Reference: Recovery Procedures

Question 62: Recovery and recycling equipment made after November 15, 1993 must have hoses with:

  • Low-loss fittings (or manual valves) that minimize refrigerant release when hoses are disconnected
  • Quick-connect fittings that release the refrigerant in the hose to the air
  • Brass caps only, which must be tightened by hand after each use
  • No valves, so the hoses can drain completely between jobs

NEC Reference: 40 CFR 82.158

Question 63: On a system with a receiver, recovering refrigerant as a liquid first:

  • Damages the recovery machine always
  • Is not permitted
  • Speeds up recovery because most of the charge is removed quickly
  • Must be done from the suction line

NEC Reference: Recovery Procedures

Question 64: The "push-pull" recovery method:

  • Works only on small appliances
  • Uses vapor from the recovery cylinder to push liquid out of the system into the cylinder
  • Pumps oil out of the compressor
  • Pushes nitrogen through the system first

NEC Reference: Recovery Procedures

Question 65: When a compressor in a high-pressure system has burned out, the technician should check for:

  • Too much refrigerant in the receiver, which should be vented before repair
  • A dirty indoor air filter, which is the most common cause of burnouts
  • Acid in the oil and system, and install suction and liquid line filter-driers after repair
  • Low ambient temperature only, since burnouts are caused by cold starts

NEC Reference: Type II Procedures

Question 66: Under the leak repair rule, a commercial refrigeration appliance with 50 or more pounds of ozone-depleting refrigerant must be repaired when the annual leak rate exceeds:

  • 10%
  • 20%
  • 30%
  • 35%

NEC Reference: 40 CFR 82.157

Question 67: Under the leak repair rule, how many days does the owner generally have to repair a leak once the leak rate threshold is exceeded?

  • 120 days
  • 10 days
  • 30 days
  • 60 days

NEC Reference: 40 CFR 82.157

Question 68: Which is a common sign of a refrigerant undercharge (leak) in a high-pressure system?

  • Low superheat and high suction pressure
  • Frost on the condenser coil
  • Very high head pressure with a full sight glass
  • High evaporator superheat and low suction pressure

NEC Reference: Type II Procedures

Question 69: When charging a system that uses a near-azeotropic blend such as R-410A, the refrigerant should be charged:

  • Through the liquid line with the system running backward
  • As a vapor only
  • As a liquid, so the blend composition stays correct
  • From the top of the cylinder as vapor in all cases

NEC Reference: Type II Procedures

Question 70: Which method is NOT acceptable for leak testing a high-pressure system?

  • Using a soap bubble solution
  • Using an electronic leak detector
  • Using dry nitrogen with a small trace amount of HCFC-22
  • Pressurizing it with oxygen

NEC Reference: Type II Safety

Question 71: Before a high-pressure system is dehydrated with a vacuum pump, which practice speeds up evacuation?

  • Using short, large-diameter hoses and removing Schrader valve cores
  • Leaving the refrigerant in the system
  • Using long, small-diameter hoses
  • Running the system compressor during evacuation

NEC Reference: Type II Procedures

Question 72: Why should the compressor of a hermetic system never be started while the system is in a deep vacuum?

  • It will damage the vacuum gauge by pulling too deep a vacuum
  • It will freeze the oil in the crankcase and lock up the compressor
  • The motor windings can be damaged because insulation strength drops in a vacuum
  • It will overcharge the system by drawing refrigerant from the hoses

NEC Reference: Type II Safety

Question 73: A residential split system (5 tons, 12 pounds of R-410A) requires which type of certification to service?

  • Type III
  • No certification
  • Type II
  • Type I

NEC Reference: EPA Certification

Question 74: Polyolester (POE) oil used with HFC refrigerants:

  • Can be mixed with any refrigerant without problems
  • Never needs to be changed
  • Repels all water
  • Absorbs moisture quickly, so systems and oil containers must be kept sealed

NEC Reference: Type II Procedures

Question 75: What is the purpose of a crankcase heater on a compressor in a high-pressure system?

  • To raise the head pressure during low-load summer operation
  • To defrost the evaporator coil during the heating season
  • To keep refrigerant from migrating into and mixing with the compressor oil during the off cycle
  • To heat the equipment room during winter shutdowns

NEC Reference: Type II Procedures

Question 76: Which refrigerant is used in low-pressure (Type III) appliances such as centrifugal chillers?

  • R-404A
  • R-123
  • R-410A
  • R-22

NEC Reference: 40 CFR 82.152

Question 77: Because the low side of a low-pressure chiller operates below atmospheric pressure, a leak usually causes:

  • The compressor to overspeed
  • Refrigerant to spray out at high pressure
  • Air and moisture to be drawn into the system
  • The rupture disc to burst immediately

NEC Reference: Type III Basics

Question 78: What device removes air and other noncondensables from a low-pressure chiller?

  • A purge unit
  • An economizer
  • A rupture disc
  • An oil separator

NEC Reference: Type III Basics

Question 79: A purge unit that runs very often on a low-pressure chiller usually means:

  • The condenser water is too cold
  • The chiller has a leak letting air in
  • The chiller is overcharged
  • The chiller is perfectly tight

NEC Reference: Type III Procedures

Question 80: The rupture disc on the evaporator of a low-pressure chiller is designed to relieve pressure at:

  • 50 psig
  • 15 psig
  • 10 psig
  • 150 psig

NEC Reference: ASHRAE 15 / Type III Safety

Question 81: When pressurizing a low-pressure chiller for a leak test, the pressure should not exceed:

  • 50 psig
  • 25 psig
  • 15 psig
  • 10 psig

NEC Reference: Type III Procedures

Question 82: Which is the preferred method of raising pressure in a low-pressure chiller for leak checking?

  • Compressed shop air
  • An open flame on the shell
  • Controlled hot water in the tubes or heating blankets
  • Oxygen

NEC Reference: Type III Procedures

Question 83: Using recovery equipment made after November 15, 1993, a low-pressure appliance must be evacuated to:

  • 25 mm Hg absolute
  • 25 inches Hg vacuum
  • 0 inches Hg
  • 15 inches Hg vacuum

NEC Reference: 40 CFR 82.156 Table 1

Question 84: Using recovery equipment made before November 15, 1993, a low-pressure appliance must be evacuated to:

  • 4 inches Hg vacuum
  • 10 inches Hg vacuum
  • 25 mm Hg absolute
  • 25 inches Hg vacuum

NEC Reference: 40 CFR 82.156 Table 1

Question 85: When recovering refrigerant from a low-pressure chiller, which is removed first?

  • The purge unit gases
  • The liquid refrigerant
  • The vapor refrigerant
  • The oil

NEC Reference: Type III Procedures

Question 86: During refrigerant recovery from a low-pressure chiller, why must water be circulated through (or drained from) the chiller tubes?

  • To prevent the water in the tubes from freezing as the refrigerant pressure and temperature drop
  • To clean scale out of the tubes while the system is open
  • To cool the recovery cylinder so it fills faster
  • To speed up the purge unit by warming the condenser shell

NEC Reference: Type III Procedures

Question 87: When charging refrigerant into an evacuated low-pressure chiller, the technician should first introduce:

  • Oil, so the compressor is lubricated before refrigerant enters
  • Nitrogen, to raise the pressure above atmospheric first
  • Liquid, as fast as possible, to shorten the charging time
  • Vapor, until the saturation temperature is above the freezing point of water

NEC Reference: Type III Procedures

Question 88: Where is refrigerant usually charged into a low-pressure chiller?

  • Through the purge unit
  • Through the condenser water box
  • Through the evaporator charging valve
  • Through the compressor oil sump

NEC Reference: Type III Procedures

Question 89: Before removing oil from a low-pressure chiller, it should be heated to about 130°F because:

  • Oil must be heated before it can legally be disposed of
  • Warm oil holds less refrigerant, so less refrigerant is lost with the oil
  • Heating kills bacteria that grow in chiller oil over time
  • Hot oil is easier to see in the sight glass while draining

NEC Reference: Type III Procedures

Question 90: After a low-pressure chiller has been evacuated to the required level, the technician should wait. If the pressure rises to 0 psig or above, this means:

  • The vacuum is perfect and recovery is complete
  • There is still refrigerant in the system or there is a leak, so evacuation must be repeated
  • The rupture disc has failed and must be replaced before continuing
  • The system is ready to open because the pressure has stabilized

NEC Reference: Type III Procedures

Question 91: ASHRAE Standard 15 requires which device in mechanical equipment rooms for most refrigerants?

  • A refrigerant detector (monitor) that triggers an alarm and ventilation
  • A sprinkler head over the chiller
  • A smoke detector only
  • A ground rod

NEC Reference: ASHRAE 15

Question 92: R-123 is classified as safety group B1 under ASHRAE 34. What does "B" mean?

  • Highly flammable
  • Higher toxicity
  • Mildly flammable
  • Lower toxicity

NEC Reference: ASHRAE 34

Question 93: A water leak in a low-pressure chiller's tubes is especially damaging because:

  • Water enters the refrigerant circuit and forms acids that damage the machine
  • It lowers the head pressure, so the chiller loses some capacity
  • It stops the purge unit from working until the leak is fixed
  • It improves efficiency but voids the manufacturer's warranty

NEC Reference: Type III Procedures

Question 94: The recovery unit used on low-pressure chillers usually has a condenser cooled by:

  • Refrigerant from the chiller
  • Water
  • Liquid nitrogen
  • Ambient air only

NEC Reference: Type III Procedures

Question 95: Industrial process refrigeration appliances with 50 or more pounds of ozone-depleting refrigerant must be repaired when the annual leak rate exceeds:

  • 15%
  • 30%
  • 20%
  • 10%

NEC Reference: 40 CFR 82.157

Question 96: Why does a low-pressure chiller's pressure gauge often read in inches of mercury vacuum on the low side during normal operation?

  • The gauge is out of calibration and should be replaced
  • The refrigerant's saturation pressure at evaporator temperature is below atmospheric pressure
  • The purge unit is off, so air is pulling the pressure down
  • The chiller is low on oil, which pulls the evaporator pressure down

NEC Reference: Type III Basics

Question 97: A technician finds high condensing pressure on a low-pressure chiller with clean tubes and correct water flow. The most likely cause is:

  • A failed crankcase heater
  • Noncondensables (air) in the condenser
  • Low oil level
  • Too little refrigerant

NEC Reference: Type III Procedures

Question 98: Type III certification is required to service:

  • Household refrigerators and other small appliances
  • R-410A residential split systems and heat pumps
  • Car air conditioners using R-134a or R-1234yf
  • Low-pressure appliances such as R-123 centrifugal chillers

NEC Reference: EPA Certification

Question 99: Recovery of refrigerant vapor from a large low-pressure chiller after liquid removal:

  • Is done by venting, because refrigerant vapor is not regulated by EPA
  • Takes only a few seconds because refrigerant vapor weighs very little
  • Can still involve a significant amount of refrigerant, so it must be completed to the required level
  • Is optional once all of the liquid refrigerant has been removed

NEC Reference: Type III Procedures

Question 100: The pressure-temperature relationship of R-123 means that at about 80°F, its saturation pressure is:

  • Close to atmospheric pressure (near 0 psig)
  • About 120 psig
  • About 300 psig
  • About 50 psig

NEC Reference: Type III Basics

Study Tip: The EPA 608 exam is closed book. Memorize: recovery is required before opening any refrigerant system. Venting refrigerant is illegal. Know the ODP and GWP values for R-22, R-410A, R-134a, R-32, and R-454B.
EXAM CARD EPA 608
Questions100
Time limit150 min
Pass score70%
RegulationEPA Section 608
DifficultyIntermediate
Last reviewedJun 2026