Question 1 of 10
1. Question
1 pointsIn no-case the rating of a shot circuit ground fault protective device for single motor compressor should not exceed ……………. percent of the motor compressor rating?
Correct
Incorrect
Refer: NEC 440.22 (A)
-
Question 2 of 10
2. Question
1 pointsWhat is the minimum ampere rating of short circuit ground fault protective device that can be used for industrial motor compressor?
Correct
Incorrect
Refer: NEC 440.22 (A) Exception
-
Question 3 of 10
3. Question
1 pointsWhich of the following size conductor is required for a 18 A motor compressor connected to 240 V circuit at 75 0C?
Correct
Incorrect
Branch circuit conductor rating should be 125% of motor compressor ampere rating
Branch circuit conductor = 18 * 1.25 = 22.5 A
Refer NEC Table 310.15(B)(16) 12 AWG with 25 A at 750C is suitable conductor
-
Question 4 of 10
4. Question
1 pointsWhich size branch circuit protection is required for 20A motor compressor connected to 240 Volts circuit?
Correct
Incorrect
Refer NEC 440.22(A) Branch circuit protection should be 175% of motor compressor rating.
Branch circuit protection = 1.75 * 20 = 35 A
-
Question 5 of 10
5. Question
1 pointsWhat size branch conductor is suitable for 5 HP, 208 V three phase motor?
Correct
Incorrect
Motor full load current for 5hp = 16.7 A [ Refer NEC Table 430.250]
Conductor size of s single motor should not be less than 125% of motor full load rating
Conductor size = 16.7 * 1.25 = 20.875
12 AWG rated at 25 A at 750C as per NEC Table 310.15(B)(16) is suitable conductor
-
Question 6 of 10
6. Question
1 pointsThe single pole switches can be used to control the motors when those are rated at ………………. hp or less.
Correct
Incorrect
-
Question 7 of 10
7. Question
1 pointsThe branch circuit over current device of the stationary motor which are rated less than ……….. may serve as the controller of motor.
Correct
Incorrect
Ref: NEC 430.81(A)
-
Question 8 of 10
8. Question
1 pointsA 2400 volts motor disconnecting means must be capable of being of being locked in the ………………….
Correct
Incorrect
Refer:
The disconnecting means should be locked in open position to avoid closing inadvertently when some person in working.
-
Question 9 of 10
9. Question
1 pointsThe overload protection must be provided for the motor if it is rated more than ……… hp
Correct
Incorrect
Refer : NEC 430.32 (A)
The motor rated more than one horse power must be provided with an approved overload protection.
-
Question 10 of 10
10. Question
1 pointsA disconnecting means should be located in sight from a motor not more than …………… distance.
Correct
Incorrect
Refer: NEC 100 : Disconnecting means definition