JOURNEYMAN NEC 2023

Journeyman Electrician Practice Test 33

Free Online Journeyman Electrician Exam Practice Test — 33This free 30-question practice test covers a wide range of journeyman electrician exam topics based on the 2023 NEC, including load calculations, lampholders, emergency transfer switches, conduit fill, DC motor theory, AC circuit fundamentals, grounding, GFCI requirements, service equipment, and more.

Share this test
TOPICS COVERED
journeyman electrician

How this test works

Read each question carefully
Look for absolute words like always / never — they often distinguish the right answer.
Manage your time
You have 75 min for 30 questions. Skip tough ones and come back.
Progress is auto-saved
Your answers are saved locally — a page refresh won't lose your work.
Review your answers
After submitting you'll see every explanation and your NEC references.

Frequently Asked Questions

Yes — completely free with no account required. All questions include detailed explanations and NEC references.

Most state Journeyman exams have 80–100 questions covering NEC code, wiring methods, branch circuits, motor controls, and load calculations.

Most states require a 70–75% passing score. This practice test uses the same 70% pass threshold so you know where you stand.

Questions are written to the 2023 NEC. Check your state licensing board to confirm which edition your state has adopted.

Key rules to review before starting: In commercial occupancies, multi-outlet equipment with 4 or more outlets counts at 90 VA per outlet (NEC 220.14(I)). Heavy-duty lampholders on circuits above 20A must be rated at least 660 VA (NEC 210.21(A)). Emergency system transfer switches must be electrically operated and mechanically held (NEC 700.5(C)). Conduit fill for 3 or more conductors must not exceed 40% (NEC Chapter 9, Table 1). GFCI protection is required in dwelling garages (NEC 210.8(A)(2)) and unfinished basements (NEC 210.8(A)(5)). The minimum service disconnect for a single-family dwelling is 100A (NEC 230.79(C)). Overhead service-drop conductors must clear driveways by 12 feet (NEC 230.24(B)(2)).

30
Questions
75 min
Time
70%
Pass

Timer starts immediately. Progress is auto-saved.

JOURNEYMAN · NEC 2023
Journeyman Electrician Practice Test 33
Q1 / 30
--:-- ON PACE
Auto-save 0% complete

0
Correct
0
Wrong
0s
Time
My Missed Questions

Electrician Reviews

No reviews yet — be the first to share your experience!

Leave a Review

5 stars
0/1000

Journeyman Electrician Practice Test 33 — Question List

Question 1: What is the calculated load for a quad receptacle manufactured in a single piece of equipment to use in retails shop?

  • 360 Volt-Ampere
  • 720 Volt-Ampere
  • 800 Volt-Ampere
  • 180 Volt-Ampere

NEC Reference: NEC 220.14(I)

Question 2: In a 3-wire, single-phase system, each hot conductor is 120 V to the neutral. What is the voltage between the two hot conductors?

  • 120 V
  • 208 V
  • 240 V
  • 480 V

Question 3: What is the minimum volt-ampere rating included for heavy duty lamp holder?

  • 660 volt-ampere
  • 560 volt-ampere
  • 460 volt-ampere
  • 760 volt-ampere

NEC Reference: NEC 210.21(A)

Question 4: Which of the following type of automatic transfer switches shall be used in emergency power supply systems?

  • Electrically operated
  • Manually Operated
  • Electrically operated and mechanically held
  • Electrically operated and electrically held

NEC Reference: NEC 700.5(C)

Question 5: When calculating conduit fill, how are equipment grounding conductors treated?

  • Only bare EGCs are counted
  • They count as half a conductor
  • They are ignored
  • They are included

NEC Reference: NEC Chapter 9, Table 1, Note 3

Question 6: An electrical battery delivers 12 amperes for 12 hrs. What is its Ampere Hour rating?

  • 144 Ah
  • 12 Ah
  • 1 Ah
  • 120 Ah

Question 7: A current of 2 A flows through a 50 Ω resistor. How much power does the resistor dissipate?

  • 5,000 W
  • 200 W
  • 100 W
  • 25 W

Question 8: An additional resistor is connected in parallel with an existing circuit. What happens to the total resistance?

  • It stays the same
  • It decreases
  • It doubles
  • It increases

Question 9: Which instrument is used to test the insulation resistance of conductors and motor windings?

  • Megohmmeter
  • Frequency meter
  • Wattmeter
  • Clamp-on ammeter

Question 10: Per NEC 210.63, a 125-volt, 15- or 20-ampere receptacle outlet must be installed for heating, air-conditioning, and refrigeration (HVAC/R) equipment. How close must this outlet be to the equipment?

  • Within 10 feet
  • Within 25 feet
  • Within 50 feet
  • Within 100 feet

NEC Reference: NEC 210.63

Question 11: If the length of a copper conductor is doubled (while keeping the same wire gauge), what happens to its resistance?

  • Resistance is halved
  • Resistance stays the same
  • Resistance doubles
  • Resistance quadruples

Question 12: What voltage rating must be marked on a circuit breaker?

  • Only the control circuit voltage
  • Exactly 600 V on every breaker
  • Any voltage, if the breaker is listed
  • At least the nominal system voltage

NEC Reference: NEC 240.83(E)

Question 13: The size of the grounding electrode conductor (GEC) for an AC service is determined by _____ .

  • Always No. 8 AWG regardless of service size
  • The size of the largest service entrance conductor per NEC Table 250.66
  • Always equal in size to the service entrance conductor
  • The size of the neutral conductor only

NEC Reference: NEC Table 250.66

Question 14: For a torque motor, which current is used to size the branch-circuit conductors and protection?

  • The nameplate locked-rotor current
  • 125% of the running current only
  • The no-load current
  • The Table 430.250 full-load current

NEC Reference: NEC 430.6(B)

Question 15: Per NEC 220.51, fixed electric space heating loads in a load calculation shall be calculated at _____ percent of the total connected load.

  • 65%
  • 80%
  • 100%
  • 125%

NEC Reference: NEC 220.51

Question 16: A 150 kVA dry-type transformer is installed outdoors next to a wood-frame building. When may it be closer than 12 in. to the building's combustible materials?

  • If it is in a NEMA 1 enclosure
  • Class 155+ insulation, fully enclosed
  • If it is rated under 600 V
  • Never, under any condition

NEC Reference: NEC 450.22

Question 17: Which values must be marked on the nameplate of multimotor air-conditioning equipment (such as a packaged rooftop unit)?

  • The installer's license number
  • Only the refrigerant type and charge
  • Minimum circuit ampacity and max OCPD
  • Only the horsepower of each motor

NEC Reference: NEC 440.4(B)

Question 18: Under the 2023 NEC, which of these dwelling locations requires GFCI protection for receptacles?

  • Hallways
  • Bedrooms
  • Living rooms
  • Indoor damp and wet locations

NEC Reference: NEC 210.8(A)(11)

Question 19: What is the unit of electric charge?

  • Ampere
  • Coulomb
  • Volt
  • Ohm

Question 20: How must each service disconnecting means be marked?

  • With a red handle
  • With the utility account number
  • Permanently marked as a service disconnect
  • It needs no marking

NEC Reference: NEC 230.70(B)

Question 21: What is the minimum vertical clearance of overhead service conductors over railroad tracks?

  • 15 ft
  • 18 ft
  • 22 ft
  • 24.5 ft

NEC Reference: NEC 230.24(B)(5)

Question 22: In a Class I, Division 1 location, when may PVC conduit be used underground?

  • Concrete-encased with 24 in. cover
  • Whenever it is Schedule 80 PVC
  • Never in any form
  • When buried at least 18 in. deep

NEC Reference: NEC 501.10(A)(1)(a) Exception

Question 23: GFCI protection is required for 125-volt through 250-volt receptacles in which dwelling location?

  • Bedrooms
  • Closets
  • Dining rooms
  • Boathouses

NEC Reference: NEC 210.8(A)(8)

Question 24: When may working space depths smaller than Table 110.26(A)(1) be permitted?

  • By special permission, at 30 V rms or less
  • In any dwelling unit
  • For equipment rated under 100 A
  • Never; the table always applies

NEC Reference: NEC 110.26(A)(1)(b)

Question 25: A 2-wire NM cable is run from a ceiling box to a wall switch (a switch loop). The white conductor is used as the ungrounded (hot) conductor feeding the switch. Per NEC 200.7(C)(1), this white conductor must be _____ at each location where it is accessible.

  • Left as-is — white wire can always serve as a hot conductor
  • Permanently re-identified with black tape or other marking
  • Replaced with a black conductor before installation
  • Insulated with green tape to show it is grounded

NEC Reference: NEC 200.7(C)(1)

Question 26: What is the minimum size of overhead service conductors (other than for limited loads)?

  • 8 AWG Cu or 6 AWG Al
  • 10 AWG copper
  • 12 AWG copper
  • 14 AWG copper

NEC Reference: NEC 230.23(B)

Question 27: In a purely inductive AC circuit, the current _____ the voltage by 90 degrees.

  • Leads
  • Is in phase with
  • Lags
  • Is 180 degrees from

Question 28: A permanently installed electric baseboard heater has a factory-installed receptacle outlet. Which statement is correct?

  • It may never count toward required outlets
  • It must be a 240-volt receptacle
  • It counts, but not on the heater circuit
  • It may be fed from the heater circuit

NEC Reference: NEC 424.9

Question 29: Outlets other than receptacles, lighting and switching (such as for a remote-control or signaling device) must be at least how far from the inside walls of a pool?

  • 5 ft
  • 6 ft
  • 10 ft
  • 20 ft

NEC Reference: NEC 680.22(D)

Question 30: When a load is calculated on a VA-per-square-foot basis, how must it be distributed among the multioutlet branch circuits in the panelboard?

  • All on one circuit
  • Evenly among the multioutlet circuits
  • On as few circuits as possible
  • Any way the installer chooses

NEC Reference: NEC 210.11(B)

Key NEC References for This Test

ArticleWhat It Covers
Art. 100Definitions — know: feeder, branch circuit, OCPD, dwelling unit
Art. 210Branch Circuits — GFCI/AFCI locations, circuit ratings, outlet spacing (most tested)
Art. 220Load Calculations — dwelling unit standard method
Art. 250Grounding & Bonding — GEC sizing, electrode system, EGC
Art. 310Conductors — ampacity (Table 310.12), insulation, derate rules
Art. 430Motors — conductor 125% FLA, OCPD 250% FLA, overloads, disconnects
Study Tip: Tab Articles 210, 250, and 430 in your NEC before the exam. Know the Table 310.12 ampacity values for 14, 12, 10, 8, 6, and 4 AWG copper.
EXAM CARD JOURNEYMAN
Questions30
Time limit75 min
Pass score70%
Code editionNEC 2023
DifficultyIntermediate
Last reviewedJun 2026

Timer starts immediately. Progress is auto-saved.

Source: NEC 2026 (NFPA 70)