Single Family Dwelling Practice Questions -1 (NEC Code)
Quiz-summary
0 of 9 questions completed
Questions:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
Information
NEC Code Questions : Single family dwelling unit calculations
You have already completed the quiz before. Hence you can not start it again.
Quiz is loading...
You must sign in or sign up to start the quiz.
You have to finish following quiz, to start this quiz:
Results
0 of 9 questions answered correctly
Your time:
Time has elapsed
You have reached 0 of 0 points, (0)
Average score |
|
Your score |
|
Categories
- Not categorized 0%
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- Answered
- Review
-
Question 1 of 9
1. Question
1 pointsWhat is the minimum feeder or service load for cloth dryers in a dwelling unit?
Correct
Incorrect
Refer: NEC 220.54
-
Question 2 of 9
2. Question
1 pointsIf a single family unit consists of one air conditioner rated at 3 kW and fixed heating equipment rated at 2.5 kw? What is the total dwelling calculated load for both?
Correct
Incorrect
Refer: NEC 220.60
Because both will not operate simultaneously, the smaller of the two loads can be omitted.
Total calculated load will be 3 kW
-
Question 3 of 9
3. Question
1 pointsService conductors supplying the entire one dwelling unit load can have an ampacity of ………….. percentage the service rating.
Correct
Incorrect
Refer: NEC 310.15(B)(7)
-
Question 4 of 9
4. Question
1 pointsAs per NEC what is the minimum general lighting load that is used for branch circuit and feeder/Service calculations of a single family dwelling unit?
Correct
Incorrect
Refer: NEC 220.12
-
Question 5 of 9
5. Question
1 pointsIn a single family dwelling unit when four or more appliances are fastened in a place and connected to the same feeder then ………………….. percentage demand can be applied in calculating total demand load.
Correct
Incorrect
-
Question 6 of 9
6. Question
1 pointsWhat is the minimum general lightening load required for 1500 square foot single family house as permissible by NEC?
Correct
Incorrect
For a dwelling unit minimum general lightening load is 3 VA / Square foot
Total load = 1500 * 3 = 4500 VA
-
Question 7 of 9
7. Question
1 pointsWhich of the following lamp holders are used in 15 ampere branch circuit that is used to supply fixed lightening units in dwelling unit?
Correct
Incorrect
-
Question 8 of 9
8. Question
1 pointsAll 15 or 20 ampere receptacle outlets installed in bathrooms of dwelling unit must always require ………………………
Correct
Incorrect
Refer :
NEC 210.8(A)(1)
-
Question 9 of 9
9. Question
1 pointsfor single family dwelling unit what is the minimum allowable rating of a 3 wire service entrance conductor?
Correct
Incorrect
Refer: NEC 230.42 (B)
un grounded service conductors for a specific installations not to be less than service disconnecting means
Refer : NEC 230.79 (C)
disconnecting means for single family dwelling unit must not be less than 100 Amperes