Question 1 of 10
1. Question
1 pointsWhat is the required size of a neutral conductor for a dwelling unit with a calculated load of 220 A. The unbalanced load is 120 A and service disconnect rating is 250A.
Correct
Incorrect
Answer: 1 AWG
83% deduction is not applicable for neutral conductor so the conductor size should be rated 100% of unbalanced load.
Refer : NEC Table 310.15(B)(16)
1 AWG is suitable as neutral conductor which ampacity of 130 A ( 75 C)
-
Question 2 of 10
2. Question
1 pointsIf a service is fed by three parallel sets of 400 kcmil conductors, what is the required conductor size for GEC?
Correct
Incorrect
The total underground conductor size = 3 * 400 = 1200 kcmil
Refer NEC Table 250.166
The required GEC is 3/0 AWG for 1200 kcmil size
-
Question 3 of 10
3. Question
1 pointsA 400 breaker protects a set of 450 kcmil feeder conductors. A feeder fed from 450 kcmil feeder that supply disconnects with 25 A over current device. What is the minimum size conductor for these tap?
Correct
Incorrect
Answer : 8 AWG
The over current device 25 A is less than 10 percent of the rating of the feeder breaker (400A.) As per code it cannot be less than 40 A.
Refer : NEC Table 310.15(B)(16)
so 8 AWG at 40A 60 C is the minimum size required.
-
Question 4 of 10
4. Question
1 pointsWhat size service entrance conductors are required for 250 A continuous three phase load if the terminals are at ambient temperature of 70 C?
Correct
Incorrect
The load is continous so the service entrance 125% rated ampacity
Service entrance ampacity = 1.25 * 250 = 312.5
According to NEC Table 310.15(B)(16) at 75 C 400 kcmil conductors with rating of 335 amperes are suitable has service conductors.
-
Question 5 of 10
5. Question
1 pointsUnder which of the following condition the on-site generator is not considered as separately derived system?
Correct
Incorrect
Refer : NEC 250.30 Note 1
The alternating generator is not considered as separately derived system as long as the neutral is coupled with service system neutral
-
Question 6 of 10
6. Question
1 pointsWhen the circuits are protected by a over current device rating of 1000 A, what size bonding jumper is required for each metal raceway?
Correct
Incorrect
The bonding jumper must be sized in accordance with NEC Table 250.122 if the circuits are protected by over current devices.
Refer : NEC Table 250.122
The 2/0 AWG copper conductor is suitable size, if the over current device rating is 1000 A
-
Question 7 of 10
7. Question
1 pointsWhen five conductors each with an ampacity of 25 A bundled through NM cable, what is the adjusted ampacity of each cable.
Correct
Incorrect
When multiple conductors are equipped in a single cable, the ampacity should be adjusted according to Table 310.15(B)(3)(a).
So for five conductors the adjustment factor is 80% or 0.8
The adjusted ampacity of each conductor = 25 * 0.8 = 20 Amperes
-
Question 8 of 10
8. Question
1 pointsA 40 KVA , 480 V three phase transformer has a primary over current protection device is rated at 75 A. What is the size of primary conductor that can be used?
Correct
Incorrect
The primary current = 40000 / (480 * 1.732) = 48 A
The primary conductor should be rated 125 % of primary current
48 * 1.25 = 60A.
Refer : NEC Table 310.15(B)(16)
4 AWG with 70 A at 60 C is suitable as primary conductor
This conductor can be protected 75 A OCPD.
-
Question 9 of 10
9. Question
1 pointsHow many number of 500 kcmil THWN conductors that can be installed in a 4 in. * 4 in. wireway?
Correct
Incorrect
Wireway area = 4 * 4 = 16 sq. in.
Refer NEC . [376.22(A)]
The conductor fill area should be maximum 20% of wireway area.
WireWay conductor fill = 16 * 0.2 = 3.2 sq. in.
Area of 500 kcmil THHN = 0.7073 sq in. [Chapter 9, Table 5]
Number of 500 kcmil THWN conductors = 3.2 / 0.7073 = 4.5 ( 4 conductors)
-
Question 10 of 10
10. Question
1 pointsWhat size service entrance conductors are required for 250 A continuous three phase load if the terminals are at ambient temperature of 70 C?
Correct
Incorrect
The load is continuous so the service entrance 125% rated ampacity
Service entrance ampacity = 1.25 * 250 = 312.5
According to NEC Table 310.15(B)(16) at 75 C 400 kcmil conductors with rating of 335 amperes are suitable has service conductors.