NEC Article 430 — Motors & Motor Circuits (Full Deck) Flashcards
Free printable flashcards — eletest.tthefl.com  ·  Cut along the dashed lines · For study use only

How to use: Cut out each card, fold along the center line, and read the term on one side and the definition on the other — or just fold the answer under while you quiz yourself off the sheet.

Q FLC vs. FLA -- the distinction that drives every motor calculation
✂ — — — — — — — — — —
A FLC (Full-Load Current, from NEC Tables 430.247-430.250) is used for ALL circuit/conductor/protection sizing calculations. FLA (nameplate Full-Load Amperes) is used ONLY for sizing overload protection.
NEC 430.6(A)
Q The four layers of motor circuit protection
✂ — — — — — — — — — —
A 1) Overload protection (protects the motor from damage), 2) Branch-circuit short-circuit/ground-fault protection, 3) Motor-circuit conductors, 4) Motor controller and disconnecting means -- each sized by a different rule.
NEC Art. 430, Parts III-IX
Q Motor branch-circuit conductor sizing
✂ — — — — — — — — — —
A Sized at not less than 125% of the motor's FLC (from Table 430.250 for a 3-phase motor, for example) -- NOT the nameplate FLA.
NEC 430.22
Q Motor overload protection sizing
✂ — — — — — — — — — —
A Generally 115% of nameplate FLA for motors with a marked service factor of 1.15+ or a temperature rise of 40 degC or less; 125% for other motors.
NEC 430.32(A)(1)
Q Motor branch-circuit short-circuit/ground-fault protection sizing
✂ — — — — — — — — — —
A A percentage of FLC from Table 430.52, varying by device type -- e.g. up to 250% for an inverse-time circuit breaker on a general-purpose motor (with permitted increases if the initial value doesn't allow starting).
NEC 430.52, Table 430.52
Q Disconnecting means rating for a motor
✂ — — — — — — — — — —
A Must be rated at least 115% of the motor's FLC (from the applicable FLC table), and horsepower-rated to safely interrupt the motor's locked-rotor current.
NEC 430.110(A)
Q Disconnect location relative to the motor
✂ — — — — — — — — — —
A Within sight from the motor and driven machinery (unless the disconnect is capable of being locked in the open position and specific conditions are met).
NEC 430.102(B)
Q Motor controller -- disconnect requirement
✂ — — — — — — — — — —
A A disconnecting means must be located within sight of the motor controller as well, not just the motor itself (may be the same device as the motor disconnect in many installations).
NEC 430.102(A)
Q Multiple motors on one branch circuit
✂ — — — — — — — — — —
A Generally not permitted unless each motor has its own overload protection and specific conditions in 430.53 are met (e.g. small motors, or motors meeting horsepower/current limits with group installation permitted).
NEC 430.53
Q Feeder conductor sizing for multiple motors
✂ — — — — — — — — — —
A Sized at 125% of the highest-rated motor's FLC, plus the sum of the FLCs of all other motors on the feeder.
NEC 430.24
Q Motor control circuit conductor protection
✂ — — — — — — — — — —
A Motor control circuit conductors (e.g. to a start/stop station) require their own overcurrent protection, sized per 430.72, separate from the motor's power circuit protection.
NEC 430.72
Q Locked-rotor current vs. full-load current
✂ — — — — — — — — — —
A Locked-rotor current (LRC) is the current drawn the instant a motor starts, before it reaches speed -- much higher than FLC, and it's what horsepower-rated disconnects and short-circuit protection must safely handle at startup.
NEC 430.7, 430.110
Q Motor nameplate -- required marking
✂ — — — — — — — — — —
A Must include (among other items) the manufacturer's name, rated voltage/full-load current, rated frequency and number of phases, rated full-load speed, and rated temperature rise or insulation class.
NEC 430.7(A)
Q Service factor and its effect on overload sizing
✂ — — — — — — — — — —
A A higher marked service factor (1.15 or greater) permits overload protection sized at a slightly higher percentage of FLA (115% vs. 125%), since the motor is designed to handle modest overload conditions without damage.
NEC 430.32(A)(1)
Q Motor short-circuit protection -- when the standard percentage won't allow starting
✂ — — — — — — — — — —
A The next higher standard protective device size (or a specific increased percentage) is permitted if the value from Table 430.52 isn't sufficient for the motor to start.
NEC 430.52(C)(1), Exception 1-2