NEC Article 250 — Grounding & Bonding (Full Deck) Flashcards
Free printable flashcards — eletest.tthefl.com  ·  Cut along the dashed lines · For study use only

How to use: Cut out each card, fold along the center line, and read the term on one side and the definition on the other — or just fold the answer under while you quiz yourself off the sheet.

Q Grounding vs. bonding -- the core distinction
✂ — — — — — — — — — —
A Grounding connects a system/equipment to earth; bonding joins metal parts together to form a continuous, low-impedance path for fault current. Bonding is what actually clears a fault -- earth itself is a poor conductor.
NEC Art. 100
Q Purpose of the equipment grounding conductor (EGC)
✂ — — — — — — — — — —
A Provides a low-impedance path for fault current back to the source, so overcurrent protection operates quickly and clears the fault -- not primarily to "drain" current into earth.
NEC 250.4(A)(5)
Q Grounding electrode system -- required electrodes
✂ — — — — — — — — — —
A All electrodes present at a premises (metal water pipe, concrete-encased electrode, ground ring, rod/pipe/plate electrodes, etc.) must be bonded together to form one grounding electrode system.
NEC 250.50
Q Concrete-encased electrode (Ufer ground) specs
✂ — — — — — — — — — —
A At least 20 ft of 1/2 in.+ rebar or 4 AWG+ bare copper conductor, encased in at least 2 in. of concrete, near the bottom of a footing/foundation in direct contact with earth.
NEC 250.52(A)(3)
Q Rod/pipe electrode -- minimum burial and spacing
✂ — — — — — — — — — —
A Driven to a minimum depth of 8 ft; where two rods are required (single-rod resistance not verified at 25 ohms or less), they must be at least 6 ft apart.
NEC 250.53(A)(2), (G)
Q Grounding electrode conductor (GEC) sizing basis
✂ — — — — — — — — — —
A Sized from Table 250.66, based on the largest ungrounded service-entrance conductor (or equivalent for parallel conductors) -- NOT the same table as the EGC.
NEC 250.66
Q Equipment grounding conductor (EGC) sizing basis
✂ — — — — — — — — — —
A Sized from Table 250.122, based on the rating of the circuit's overcurrent device -- a completely different table/basis than the GEC.
NEC 250.122
Q Main bonding jumper (MBJ)
✂ — — — — — — — — — —
A Connects the grounded (neutral) conductor to the equipment grounding conductor and the enclosure at the service -- installed only at the service, establishing the single ground-neutral bonding point.
NEC 250.28, Art. 100
Q Why the neutral-ground bond exists only at the service
✂ — — — — — — — — — —
A A second neutral-ground bond downstream (e.g. at a subpanel) creates a parallel path for neutral current, which can flow over grounding conductors, metal piping, and equipment enclosures -- a serious shock/fire hazard.
NEC 250.24(A)(5), 250.142
Q Subpanel (feeder) grounding -- 4-wire feed
✂ — — — — — — — — — —
A A subpanel fed with a 4-wire feeder (2 hots + neutral + EGC) keeps the neutral and ground bars separated -- no bonding jumper at the subpanel, unlike at the service.
NEC 250.24, 408.40
Q Separately derived system -- definition
✂ — — — — — — — — — —
A A premises wiring system whose power source (transformer, generator, etc.) has no direct electrical connection to the supply conductors of another system -- requires its own grounding electrode connection and bonding jumper.
NEC Art. 100, 250.30
Q Bonding of metal water piping systems
✂ — — — — — — — — — —
A Interior metal water piping that could become energized must be bonded, typically via the service equipment or grounding electrode system, using a bonding jumper sized per Table 250.66.
NEC 250.104(A)
Q Bonding of other metal piping systems (gas, etc.)
✂ — — — — — — — — — —
A Metal gas piping likely to become energized must be bonded -- often satisfied by the EGC of the circuit supplying equipment likely to energize it, per the equipment grounding conductor sizing rules.
NEC 250.104(B)
Q Ground ring electrode specs
✂ — — — — — — — — — —
A A bare copper conductor not smaller than 2 AWG, at least 20 ft long, encircling the building/structure, buried at least 30 in. deep.
NEC 250.52(A)(4)
Q Objectionable current on grounding conductors
✂ — — — — — — — — — —
A Grounding conductors and paths are not permitted to be used as normal current-carrying conductors -- objectionable (unintended) current on the EGC is itself a code violation to be corrected, not tolerated.
NEC 250.6
Q Equipment grounding conductor types permitted
✂ — — — — — — — — — —
A Includes copper/aluminum conductors (bare or insulated), rigid/intermediate metal conduit, EMT, listed flexible metal conduit under specific conditions, cable armor, and other recognized methods in 250.118.
NEC 250.118
Q Grounding electrode conductor -- can it be spliced?
✂ — — — — — — — — — —
A Generally must be installed in one continuous length without a splice or joint, with narrow exceptions (e.g. irreversible compression connectors, exothermic welding, or busbars).
NEC 250.64(C)
Q Metal underground water pipe as an electrode
✂ — — — — — — — — — —
A Qualifies if in direct contact with earth for 10 ft or more, but can never be the sole grounding electrode -- must always be supplemented by another electrode.
NEC 250.52(A)(1), 250.53(D)(2)
Q Bonding jumper on the supply side of service equipment
✂ — — — — — — — — — —
A Called a "supply-side bonding jumper" (not "equipment bonding jumper") when it connects the grounded conductor to the metal enclosure on the line side of service disconnects.
NEC Art. 100, 250.92
Q Effective ground-fault current path -- required property
✂ — — — — — — — — — —
A Must be permanent, electrically continuous and conductive, and have the capacity to safely carry the maximum ground-fault current likely to be imposed on it.
NEC 250.4(A)(5)