Journeyman Exam Essentials Flashcards
Free printable flashcards — eletest.tthefl.com  ·  Cut along the dashed lines · For study use only

How to use: Cut out each card, fold along the center line, and read the term on one side and the definition on the other — or just fold the answer under while you quiz yourself off the sheet.

Q Dwelling receptacle spacing rule
✂ — — — — — — — — — —
A No point along a wall in a dwelling can be more than 6 ft from a receptacle, and any wall space 2 ft or wider must have one -- so no point on the floor line is ever more than 6 ft from an outlet.
NEC 210.52(A)
Q Kitchen countertop receptacle spacing
✂ — — — — — — — — — —
A No point along a countertop wall space can be more than 24 in. from a receptacle, and every countertop space 12 in. or wider needs one.
NEC 210.52(C)
Q Small-appliance branch circuits required in a dwelling kitchen
✂ — — — — — — — — — —
A A minimum of two 20A small-appliance circuits must serve kitchen, pantry, and dining area receptacles -- and those circuits can't feed anything else.
NEC 210.11(C)(1), 210.52(B)
Q Box fill allowance for one 12 AWG conductor
✂ — — — — — — — — — —
A Each 12 AWG conductor counts as 2.25 cu in. of box fill volume (14 AWG = 2.0 cu in., 10 AWG = 2.5 cu in.).
NEC 314.16(B)
Q Box fill: device count
✂ — — — — — — — — — —
A Each yoke/strap (switch or receptacle) counts as two conductor volume allowances, based on the largest conductor connected to it.
NEC 314.16(B)(4)
Q Working clearance in front of electrical equipment (typical)
✂ — — — — — — — — — —
A A minimum of 30 in. wide, 36 in. deep for 0-150V to ground (condition 1); depth increases to 42 in. or more at higher voltages or exposed live parts on both sides.
NEC 110.26(A)
Q Working space headroom
✂ — — — — — — — — — —
A Minimum 6.5 ft (or the height of the equipment, if taller) of clear working space above the floor in front of electrical equipment.
NEC 110.26(E)
Q Service disconnect maximum number
✂ — — — — — — — — — —
A Up to six disconnects grouped in one location are permitted to disconnect all ungrounded conductors from the service.
NEC 230.71
Q Grounding electrode: metal water pipe
✂ — — — — — — — — — —
A A metal underground water pipe in direct contact with earth for 10 ft or more qualifies as a grounding electrode, but it can't be the sole electrode -- it must be supplemented.
NEC 250.52(A)(1), 250.53(D)(2)
Q Ufer ground (concrete-encased electrode)
✂ — — — — — — — — — —
A At least 20 ft of rebar (1/2 in.+) or bare copper conductor (4 AWG+) encased in at least 2 in. of concrete, near the bottom of a foundation footing in direct contact with earth.
NEC 250.52(A)(3)
Q Grounding electrode conductor sizing basis
✂ — — — — — — — — — —
A Sized from NEC Table 250.66, based on the size of the largest ungrounded service-entrance conductor (or equivalent area for parallel sets).
NEC 250.66
Q Neutral conductor -- when can it be switched?
✂ — — — — — — — — — —
A Generally never on its own -- a switch or breaker must open all ungrounded conductors together with the neutral, not the neutral alone. This keeps the load from staying energized when the switch reads "off."
NEC 404.2(B)
Q AFCI-protected areas in a dwelling
✂ — — — — — — — — — —
A Kitchens, family rooms, dining rooms, living rooms, bedrooms, sunrooms, closets, hallways, and similar rooms -- essentially all 120V, 15A/20A branch circuits.
NEC 210.12(A)
Q Bathroom receptacle circuit rule
✂ — — — — — — — — — —
A At least one 20A branch circuit must supply bathroom receptacles, and it can serve only bathroom receptacles in one or more bathrooms (no lighting mixed in unless entirely within one bathroom).
NEC 210.11(C)(3)
Q Conductor ampacity derating -- more than 3 current-carrying conductors in a raceway
✂ — — — — — — — — — —
A Ampacity must be adjusted per the NEC 310.15(C)(1) adjustment table -- e.g. 4-6 conductors are derated to 80% of the table ampacity.
NEC 310.15(C)(1)
Q Tandem (3-way) switch identification
✂ — — — — — — — — — —
A A 3-way switch has three terminals: one common and two travelers -- it has no "off" position by itself, only a choice of which traveler is connected to common.
Q Equipment bonding jumper vs. main bonding jumper
✂ — — — — — — — — — —
A A main bonding jumper connects the grounded (neutral) conductor to the equipment grounding conductor and enclosure -- only at the service. An equipment bonding jumper connects EGCs together elsewhere, like at a subpanel or raceway.
NEC Art. 100, 250.28
Q Panel clearance to sides for equipment 1200A or less
✂ — — — — — — — — — —
A No side clearance is required if the equipment is not likely to require examination while energized -- but front working space per 110.26(A) still applies. Don't confuse "no side clearance needed" with "no front clearance needed."
NEC 110.26
Q Ampacity of 12 AWG copper THHN at 90 degC (before any derating/termination limits)
✂ — — — — — — — — — —
A 30A in the 90 degC column of Table 310.16 -- but termination temperature ratings (usually 60 degC or 75 degC) typically cap the usable ampacity of 12 AWG at 20A on a standard breaker.
NEC Table 310.16, 110.14(C)
Q Wet vs. damp vs. dry location
✂ — — — — — — — — — —
A A wet location is subject to saturation with water (e.g. exterior, below grade); a damp location is subject to moderate moisture (e.g. under a roofed open porch); a dry location is normally not subject to either.
NEC Art. 100